![Neol EPC 4 IEC User Manual Download Page 38](http://html1.mh-extra.com/html/neol/epc-4-iec/epc-4-iec_user-manual_719059038.webp)
37
- Choose "higher than" if you want to execute the Rule if the environment value exceeds the value you
defined in the field on the right of "higher than".
- Choose "lower than" if you want to execute the Rule if the environment value is below the value you defined
in the field on the right of "lower than".
For temperature, you can define values between 0C and 50C
For relative humidity, you can define values between 10 RH and 90 RH
Alarm Duration
By checking this box, you can enter a duration for the selected Digital Input. This Digital Input will then trigger
the corresponding action(s) only if the alarm was active for this period. The value can be set between 0 and
60 sec..
Trigger Delay
By checking this box, you can enter a trigger delay for the selected Digital Input. This Digital Input will then
trigger the corresponding action(s) only after the specified delay. The value can be set between 1 and 60 sec
Configuring the Actions
Type of Action
For the Event defined above and depending on your Device, you can choose different Actions:
Set Outputs
This type of Action only appears if:
- your Device has own Power Outlets or has access to Power Outlets of connected xBus Peripheral
Units
- your Device has access to Relay Outputs of connected xBus Peripheral Units
- you have created interface associations (Go to Settings/Associations).
Select this checkbox and choose in the corresponding drop-down lists the Output to use for this Rule.
Each Power Outlet can be switched to On, Off or Restarted.
If you choose "Restart" you can also define a Restart delay between 0 and 3600 seconds.
- If you choose 0 second for the delay, the delay will be the delay defined in the Peripherals page (goto
Settings/Peripherals/Edit).
- If you choose a delay different from 0, this delay will replace the delay defined in the Peripherals page (goto
Settings/Peripherals/Edit).
Each Relay Output can be switched to Open, Close, Pulse Open, Pulse Close.
If you choose Pulse open or Pulse close you can also define a delay between 0 and 3600 seconds.
- If you choose 0 second for the delay, the delay will be the delay defined in the Peripherals page (goto
Settings/Peripherals/Edit).
- If you choose a delay different from 0, this delay will replace the delay defined Peripherals page (goto
Settings/Peripherals/Edit).
Rule to cancel
This type of Action only appears if you already have created a Rule which you want to cancel
Select this checkbox and choose in the corresponding drop-down lists the Rule you want to cancel.
Send Magic to
Your Device has the possibility to send a Magic Word over IP to another Device in order to remotely trigger
an action.
- Send magic: specify the Magic Word to use, it can be from 1 to 32 characters long, and can contain
alphanumeric characters.
- to: specify the IP address of the destination device
- port: specify the Port number used to send the Magic Word, default port number is 52389
Send Syslog Message
This type of Action can only be configured if you have already specified at least one destination
Syslog Server (Go to General/Log Settings Page).
Check this box if you want to send a message to a Syslog server. In the following drop-down lists choose the
facility and the severity of the message to send.
Send Trap Message