MR-CC –
CONDUIT CONNECTION
(Ordered Separately)
Refer to alternate instructions if using Pole, Wall, Yoke or Hook Mount
STEP 1.
Inspect shipping package and contents to ensure no damage has
occurred during shipping. Discard surface/ceiling mounting bracket
provided with MR luminaire.
STEP 2.
Slide anti-rotation lock onto suitably mounted hanging conduit and
install luminaire onto ¾” conduit. Slide anti-rotation lock into place
and tighten set screw to lock unit in place. Tighten the anti-rotation
lock set screw to 5 N-m (44 in-lbs). Fixed Rigid Metal Conduit must
be suitably mounted to prevent rotation.
NOTE:
To aid in assembly and protection against ingress use of a petrolatum or
soap thickened mineral oil based thread lubricant/sealant is necessary.
Un-used conduit opening must be plugged to maintain the integrity of the
enclosure.
STEP 3.
Install Secondary Safety Cable by looping appropriate steel cable or
chain through the outer band of the unit and fastening a closed
loop. Secondary safety hardware must be rated for a minimum of
50lbs.
Install remaining loop of secondary safety chain or steel cable to
suitable mounting location and fasten securely. Secondary safety
hardware must be rated for 50lbs.
STEP 4.
Resume installation instructions provided with Fixture. (STEP 4)
This MR-CC kit is intended for use with UL Listed MR luminaire as
marked on the luminaire nameplate.
Accessory Package Contents
INSTALLATION STEPS
MR-CC
PART NAME
QTY
1
ANTI-ROTATION BRACKET ASSEMBLY
TM
Nemalux
I N D U S T R I A L
MR-GEN
rev. A-15
1-1