7-16
www.nemalux.com | [email protected] | Tel 403•242•7475 | Fax 403•243•6190
MADE IN CANADA
TM
Nemalux
I N D U S T R I A L
AR Series
rev. A-30
WARNING:
The AR Head must not face
upwards by any degree
beyond the vertical position
for Class II, Division 2,
Zone 22, and Class III
hazardous locations.
LIGHT BEAM
HORIZON
ATTENTION:
Le luminaire (AR) ne doit pas
être orientée vers le haut de
quelque degré que ce soit
au-delà de la position verticale
pour les emplacements
dangereux de Classe II,
Division 2, Zone 22 et Classe III
AR-YM – YOKE MOUNT INSTALLATION (Ordered Separately)
Refer to alternate instructions if using Conduit, Hook, Pole, Wall Mount, or High Vibration Yoke
STEP 1.
Inspect shipping package and contents to ensure no damage has occurred
during shipping. Discard surface/ceiling mounting bracket provided with
AR luminaire. Remove 4 x M6 bolts from supply side of luminaire and
disard.
STEP 2.
Install suitable wiring system to the conduit opening per CEC/NEC
requirements for the specific location of install.
NOTE:
To aid in assembly and protection against ingress use of a petrolatum or
soap thickened mineral oil based thread lubricant/sealant is necessary.
Un-used conduit opening must be plugged to maintain the integrity of the
enclosure.
STEP 3.
Loosely assemble Yoke mount with carriage bolts on inside and washers
and nuts on the outside.
NOTE:
Depending on which mounting hole is used in the curved slot, the
luminaire may be configured for an upward or downward adjustable swing.
STEP 4.
Thread installed wiring through openings in yoke mount cheek plate and
yoke mount bracket. Mount yoke assembly to luminaire using 4x M6 Socket
Head Cap Screws and Washers (Provided). Torque fasteners to 5 Nm (45
in-lbs).
STEP 5.
Mount luminaire assembly to desired location using 4x 1/4-20 OR M6
Screws or Bolts (Not Provided).
STEP 6.
Adjust and aim luminaire to desired position. Torque hardware
nuts to 9 N-m (80 in-lbs).
STEP 7.
Resume installation instructions provided with luminaire.
(STEP 4 in AR Installation Instructions provided with Luminaire)
Step 5
Step 3
This AR-YM kit is intended for use with UL Listed AR luminaire as
marked on the luminaire nameplate.
Accessory Package Contents
INSTALLATION STEPS
AR-YM
PART NAME
QTY
1
1
1
4
4
4
4
YOKE MOUNT A
YOKE MOUNT B
CHEEK PLATE
1/4-20 HEX NUT
1/4" FLAT WASHER
1/4-20 x 0.5in CARRIAGE BOLT
M6 x 25mm HEX HEAD CAP SCREW
4.3in
108.15mm
2.3in
59mm
0.27in
6.76mm
0.27in
6.8mm
1.7in
44mm
2.8in
70mm