ELECTRICAL INSTALLATION, WIRING AND TROUBLESHOOTING

 

 

Nederman Customer Service & Technical Support         [email protected] 

   +1 (336) 821-0800

   

 

 

Section 2.0 – Circuit Sizing 

 

 

 

1   

Techtop motor nameplate full

load amps (Used for setting overload only). 

2   

Minimum size based on 75

C (167

F) insulation and copper wire, such as RHW, THHW, THW, THWN, XHHW, 

XHWN,USE, ZW. Verify  with table 310.16. Conductor size may need to be increased based on wire type, length 

and/or run. 

3   

Branch circuit protection to be sized at 250% of motor FLC for (Inverse Time) circuit breaker based on tables 

430.52, 430.248,  and 430.250. Based on 2020 NEC 70 Article 430 and best

practice. 

4   

Branch circuit protection to be sized at 175% motor FLC for Dual Element (Time

Delay) Fuse based on tables 

430.52, 430.248,  and 430.250. Based on 2020 NEC 70 Article 430 and best

practice. 

5   

Branch circuit protection to be sized at 300% motor FLC for Nontime

Delay fuse (Class CC fuses) on tables 

430.52, 430.248, and  430.250. Based on 2020 NEC 70 Article 430 and best

practice. 

6   

Recommended setting for overload on Nederman Push Button Starters based on motor nameplate multiplied by 

service factor. 

7   

Wire

nuts or soldering are 

NOT 

acceptable means to connect motor leads per NFPA 79, 13.5.9. Use appropriate 

components to  make motor connections such as split bolts, crimp

connections and eye

bolts. 

8   

It is the responsibility of the end

user to follow State and Local Codes. This chart is provided as a helpful 

resource only. Use 

of a qualified and licensed  industrial electrician is required for proper installation. 

 

 

TABLE 2 - 3-Phase S-Filter Circuit Sizing Table

8

 

Service Factor 1.0 

Motor FLA

1

 

Conductor Size

2,7

 

Inverse Time 

Breaker Size

3

 

Time

Delay 

Fuse

4

 

Non Time

Delay

5

 

O/L Setting

6

 

 

S

500 

208V 

13.2 

10 

AWG 

45 

30 

50 

17 

230V 

12.4 

12 

AWG 

40 

30 

50 

16 

460V 

6.18 

12 

AWG 

20 

15 

25 

575V 

4.94 

12 

AWG 

20 

15 

20 

 

S

750 

208V 

19.2 

10 

AWG 

70 

45 

80 

24 

230V 

17.7 

10 

AWG 

60 

40 

70 

22 

460V 

8.6 

12 

AWG 

30 

20 

35 

11 

575V 

7.08 

12 

AWG 

25 

20 

30 

 

S

1000 

208V 

26.3 

AWG 

80 

60 

100 

33 

230V 

23.9 

AWG 

70 

50 

90 

30 

460V 

12 

12 

AWG 

35 

25 

45 

15 

575V 

9.55 

12 

AWG 

30 

20 

30 

12 

Summary of Contents for S-Series

Page 1: ...y Filters Bag Filter Dust Collector S SERIES ELECTRICAL Installation Wiring and Troubleshooting No portion of this manual may be reproduced without the written approval of Nederman Original Installation and Service Manual 2022 06 03 Rev 3 1 ...

Page 2: ...stomer Service Technical Support techsupport us nedermen com 1 336 821 0800 2 TABLE OFCONTENTS Section 1 0 Preface 3 Section 2 0 Circuit Sizing 3 4 Section 3 0 Motor Connections 6 Section 4 0 Trouble Shooting 7 8 Section 5 0 Inrush Current 9 Wiring Diagrams 10 11 ...

Page 3: ... conductors and circuit breaker size The data in this table is based on the 2020 NEC and is to be used as recommendations only Final discretion is the responsibility of the Licensed Electrician local codes regulations and the AHJ Dueto the inrushcurrent the fusing breaker must be sizedlarger to protect the wiring in the event of a short circuit The motor overhead not the breaker provides the motor...

Page 4: ... practice 6 Recommended setting for overload on Nederman Push Button Starters based on motor nameplate multiplied by service factor 7 Wire nuts or soldering are NOT acceptable means to connect motor leads per NFPA 79 13 5 9 Use appropriate components to make motor connections such as split bolts crimp connections and eye bolts 8 It is the responsibility of the end user to follow State and Local Co...

Page 5: ...us nedermen com 1 336 821 0800 5 Section 2 0 Circuit Sizing Product Owner End user shall provide branch circuit protection Refer to the Motor Circuit Sizing Tables on previous pages for max breaker and fuse sizes Note F1 represents fuses An Inverse Time Breaker would replace the fuses F1 in the below example ...

Page 6: ...e use of Split Bolts Crimp Connectors Eye Bolts with Screws or other approved motor connection terminals See Figure 2 Figure 2 Acceptable Connectors Split Bolt Insulated Multitap Crimp Product Owner End User 1 Must ensure that you are using dust tight connections on the motor junction box The cord grip used should tightly secure the flexible conduit or cordbeing used The motor junction box cover s...

Page 7: ...re the circuit protection is sized appropriately per section2 0 for thefiltermodel 4 Are the supply conductors the correct size according to the 1 3 Phase Motor Circuit Sizing Table Please confirm correct sizing If the length between the starter and the motor exceeds 150 feet consider upsizing the conductors 1 size to account for voltage drop in the conductors Consult your Licensed Electrician abo...

Page 8: ...ND g T7 to GND h T8 to GND i T9 to GND 4 While the motor is disconnected and the circuit breaker turned off measure the resistance of the supply leads to ground to ensure there is not a direct short from one of the supply leads a L1 to GND b L2 to GND c L3 to GND 5 If you have access to a MEGGER perform an Insulation test from each lead to ground motor frame a T1 to GND b T2 to GND c T3 to GND d T...

Page 9: ...h current occurs during the first half cycle of motor operation and can be more than 10 times the motor s FLA full load amperage As the motor turns the current decreases to the level of the motor s locked rotor current which is often six to eight times the motor s normal operating current As the motor speed and back EMF increases the current further decreases until normal operating speed and curre...

Page 10: ...n servicing our machinery Make sure to choose a certified technician to service your Nederman equipment as they have the correct tools and knowledge to solve any machinery issues and improve its performance Be sure to ask if your technician is certified by Nederman Our services for dust collection systems are customized to your particular needs We work with you to understand your needs then develo...

Reviews: