8 De-installation
PowerRouter • Back-up / Stand-alone • Installation Manual
44
EN
8
De-installation
DANGER
To safely de-install the PowerRouter, you must follow the instructions in this chapter.
8.1
De-install
To de-install the PowerRouter:
1.
Switch the PowerRouter unit OFF.
2.
Switch the solar disconnect switch OFF (on the bottom of the PowerRouter).
3.
For 24V lead-acid batteries set the external battery disconnect switch to off.
4.
Switch the battery switch OFF.
5.
Switch the AC switches OFF (grid and local out).
6.
Wait at least 5 minutes, to ensure the unit is completely de-energised.
7.
Disconnect the communication wires.
8.
Disconnect any optional connections.
9.
Disconnect the solar panel string wiring with the special tool (figure 8).
10. Disconnect the AC wires.
11. Disconnect the DC wires.
12. Disconnect the battery wires.
13. The PowerRouter can now be removed for disposal or repair.
DANGER
The wires from the solar panels are always energised. The voltage from a string of solar panels can
be as high as 600 V. The current can be as high as 15 A.
CAUTION
•
De-installation must be carried out by qualified personnel. Contact your installer/dealer.
•
48V Li-ion batteries are indicated as dangerous goods and may require special transportation. Check
the documentation of the supplier and local regulations.
Summary of Contents for PowerRouter PR50SB-PR/S24
Page 1: ...Installation Manual PowerRouter Solar Battery Back up Stand alone Date 181213...
Page 9: ...PowerRouter Back up Stand alone Installation Manual Illustrations 7 19 20 21 22...
Page 10: ...Illustrations PowerRouter Back up Stand alone Installation Manual 8 23 24...
Page 50: ...9 Technical specifications PowerRouter Back up Stand alone Installation Manual 48 EN...
Page 51: ......