background image

 

 

 

2.1.2

 

Corner Installation:

 

 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Clearances 

 Corner Installation

 

B (mm)

 

Floor - F (mm)

 

Corner - C (mm)

 

300 

150 

 
 
 

2.2

 

Floor Protector (Hearth)

 

Unless the heater will be standing on a heat resistant floor 
such as concrete slab with slate or tiles, it will be necessary to 
provide a floor protector (hearth). 

The dimensions given in above (Section 2.1) are the minimum 
required for the floor protector. It must extend no less than 
300 mm in front of the door opening, no less than 200mm 
either side of the door opening, and extend under the heater. 
Minimum dimensions for floor protector are 900mm wide by 
900mm deep. It may be desirable, for example aesthetic 
reasons, for the floor protector to be larger than these 
minimum dimensions. 

The floor protector shall be constructed of either: - 

a)

 

10mm thick toughened glass, OR 

b)

 

Non-combustible material no less than 15mm thick 
and with a thermal conductivity not greater than 
0.33W/m 

º

K, eg. compressed cement sheet.  

The floor protector may be laid directly on the combustible 
floor. 

For more details and variations on floor protectors refer to 
AS/NZS 2918:2001 Clause 2.2, 3.3.1, & 3.3.2. 

 

 

If it is necessary to install a heater closer to a combustible 
surface than the stated requirements in Section 2 of this 
Installation Guide, it must be done in accordance with 
Australian Standard AS/NZS 2918:2001 Section 3, Tables 3.1 
& 3.2. 

Shield Construction:- The shield shall be constructed from a 
heat resistant material. The shield must be fixed to the 
surface that requires protection and NOT the heater. 

The Standard allows three options to reduce stated 
clearances. 

 

 

Single layer of continuous material with Minimum Air Gap of 

12mm

Clearance Factor = 0.40 

Single layer of continuous material with Minimum Air Gap of 

25mm

Clearance Factor = 0.30 

Two spaced layers of continuous material with Minimum Air 

Gaps of 12mm + 12mm

Clearance Factor = 0.20 

The shielding must be open at the top and bottom (vented) 
to allow a continuous air flow. It is this air flow that keeps 
the surface requiring protection cool. Fixings should not 
impede this air flow. 

The shielding needs to go far enough along and up the wall 
so that the original side and rear required clearances are not 
compromised. As the flue is now closer to the wall the 
shielding should also protect the wall from the flue pipe. 

 

 

For example:

 

Side wall clearance for the MK3 is 400 mm. 

A 12mm gapped shield on the wall with a factor of 0.40. 

Calculate:- 400 mm x 0.40 = 160 mm. This is the new side 
wall minimum clearance. 

The shielding needs to be large enough so that none of the 
original clearances of 400 mm are compromised. 

Combustible Wall 

Co

mb

u

sti

b

le

 W

all

 

3. REDUCING CLEARANCES TO COMBUSTIBLES

 

Reviews: