1.2.

 

INSTALLING THE HEATER 

 

1.2.1.

 

Positioning the Heater 

 

Review the necessary clearances specified in this section 
before considering where to position the heater. 

Also check the practicability of installing the flue system in 
relation to any obstructing roof beams before positioning the 
heater. 

The clearance distances can only be reduced if the 
surrounding walls are made of non-combustible material such 
as stone, brick or concrete. If non-combustible material, 
distance can be reduced to 100 mm. Alternatively, shielding of 
the wall(s) can reduce clearances (refer to next section for 
more detail). 

Clearances to combustible surfaces vary depending on the 
type of flue shielding used. 

 

1.2.2.

 

Standard Installation 

 

Dimensions given in the image below represent the minimum 
clearance (in millimetres) to combustible materials. 

Side clearance = 350mm 

Rear clearance = 125mm 

 

 

 

1.2.3.

 

Corner Installation 

 

If the appliance is placed in the corner of a room, the 
minimum clearance from the corner edge of the appliance to 
the nearest combustible surface is 350mm. 

 

1.2.4.

 

Floor Protector 

 

Unless the heater will be standing on a heat resistant floor 
such as concrete slab with slate or tiles, it will be necessary to 
provide a floor protector. 

The minimum required dimensions for the floor protector are 
shown in the previous image. It must extend no less than 
300mm in front of the door opening, no less than 200mm 
either side of the door opening and extend under the heater. 
Minimum dimensions for the floor protector are 750mm wide 
by 960mm deep. It may be desirable, for example aesthetic 
reasons, for the floor protector to be larger than these 
minimum dimensions. 

The floor protector shall be constructed of non-combustible 
material no less than 12mm thick and with a thermal 
conductivity not greater than 0.33W/m °K, eg. compressed 
cement sheet.  

The floor protector may be laid directly on the combustible 
floor. 

For more details and variations on floor protectors refer to 
AS/NZS 2918 Clause 2.2, 3.3.1, & 3.3.2. 