PROBLEM 

(and/or indication on the 

display)

 

POSSIBLE CAUSE

 

SOLUTION

 

The display indicates the 

message: 

“Compressor” 

 

If the compressor runs for 24 hours 
consecutively without the cabinet reaching 
the temperature set via the SW, the machine 
is locked and the selection disabled. 
The following could be the cause: 
Lack of gas in the refrigeration circuit due to 
possible leaks. 
Failure to the evaporator’s electric fan. 
Failure to the condenser’s electric fan or PTC 
triggered. 
Clogged lower and/or side grille 
Failed probe (in this case the message “probe 
failure” will be displayed) 

Normally two to four hours are required to 
reach the operating temperature 
(according to the load). A longer time 
means that there is a malfunction: check 
for any small leaks in the refrigerating gas 
circuit; if necessary repair the leak and 
charge with the correct dose of gas. 
Check that the electric fans work correctly. 
Check for the correct cooling airflow inside 
the refrigerated box. In the case of failure 
to components, replace with original parts.

The display indicates the 

message 

“Coin mechanism” 

 

If the CPU for more than 30 seconds does 
not receive communication impulses from an 
Executive serial coin mechanism, or 75 
seconds from a BDV serial coin mechanism, 
or if it receives an impulse for longer than 2 
seconds, the machine locks and the 
selections are disabled. 

Replace the coin mechanism with one that 
is certain to work and check the 
communication. Check connections. 
Check the CPU board, and if necessary 
replace with that is certain to work. 
Check that the 24 V DC power supply fuse 
is intact. 

 

The display indicates the 

message 

“RAM data” 

 

One or more areas of the RAM contain wrong 
data, which could change the operating 
default values. 
The machine will continue working, but some 
parameters could have been changed, with 
consequences to the general functioning - 
the RAM needs to be initialised as soon as 
possible to recover data from the EPROM. 
 
 
 

Initialise the CPU again. 
After initialising, all data settings will go 
back to the default settings; restore the 
customised data using the programmer or 
a PC. 
If, in spite of initialising, the malfunction 
persists, replace the CPU board with an 
already tested one that is certain to work. 
It the malfunction persists, replace the 
cables or check the suitability of 
connections. 
The machine was designed to comply with 
the EMC directive, but if located in an 
environment subject to high interference 
immunity problems could arise, therefore 
in the event of such interference persisting 
the vending machine should be moved to 
a different location. 

The display indicates the 

message 

“Probe” 

 

The temperature control probe in the 
refrigerated box is of the NTC type, with the 
internal resistance that lowers as the 
temperature rises. 
If the probe is interrupted, the machine locks 
after 5 minutes from the failure and the 
selections are disabled (THE DISPLAY WILL 
INDICATE THE TEMPERATURE – 5 ° C) 
If there is a short-circuit in the probe, the 
machine locks after 60 minutes and the 
selections are disabled (THE DISPLAY WILL 
INDICATE THE TEMPE32° C) 

NB

: AFTER THE SENSOR FAILURE HAS BEEN 

DISPLAYED FOR TWO HOURS, A 
COMPRESSOR FAILURE WILL ALSO BE 
INDICATED. 

Check the internal resistance in the NTC 
probe using a digital multimeter: A 
resistance of 730 ohm corresponds to a 
temperature of 30° C. 
A resistance of 2612 ohm corresponds to a 
temperature of 0° C (melting ice). 
Replace the probe with an original one; 
before installing the new one check that 
the internal resistance corresponds to the 
above parameters.  
Reset the failures by accessing the special 
software function. See programming 
manual

 

 

7  – TROUBLESHOOTING 

Summary of Contents for Sfera 6-32R / E

Page 1: ...ECTA SPA TECHNICAL MANUAL SFERA Manual SFERA 1 19 SERVICE MANUAL SFERA BASIC TECHNICAL MANUAL THE CONTENTS OF THIS DOCUMENT ARE INTENDED FOR NECTA S AFTER SALES PERSONNEL AFTER SALES SERVICE Snack Foo...

Page 2: ...d configuration Vending systems Power supply and Wiring Cooling unit Cabinet and Door Trouble shooting HACCP directive Use instructions Periodical cleaning and hygiene Daily Weekly Yearly Pages 3 4 5...

Page 3: ...irect for five advertised selections NB2 without such code the machine is supplied with only the 12 button numeric keypad DESCRIPTION VARIABLES TRAYS Up to 6 max HEIGHT 0F TRAYS 96 mm min and up to 21...

Page 4: ...e code is indicated on the side in any case there are many configurations options with simple and quick change operations Release spirals with different pitches are provided as indicated in the user m...

Page 5: ...NECTA SPA TECHNICAL MANUAL SFERA Manual SFERA 5 19 Sfera 6 36R B Sfera 6 36R UK Sfera 6 32R E Sfera 6 36R D Version provided for Spain Version provided for Belgium Version provided for Germany...

Page 6: ...th a 3 x 1 5 mm2 section 1 HO5 VV F 2 HO7 RN F In all configurations the cable is fitted with a SCHUKO plug permanently fixed to the cable NOTE In the event of replacement cables of exactly the same c...

Page 7: ...Board Payment system connections NTC Probe Cooling unit control J12 RATIOMOTOR CONNECTIONS POWER SUPPLY UNIT CPU CENTRAL PROCESSING UNIT BOARD RS232 PORT PRINTER PROGRAMMER PC Phototransistor card Rec...

Page 8: ...during the normal operation YELLOW LED It glows when 5 V DC is present in the board RED LED it glows when the software is reset program malfunction Minidip functions 1 4 REF 20 Coin mechanism setting...

Page 9: ...NECTA SPA TECHNICAL MANUAL SFERA Manual SFERA 9 19 TRAY CONNECTION WIRING DIAGRAM CONNECTOR Detail of spiral control ratiomotor To connector J 12 CPU board 4 5 1 6 3 2...

Page 10: ...FERA 10 19 POWER SUPPLY AND LIGHTING DIAGRAM 2 1 3 4 5 6 7 Wiring diagram of dispensing compartment slider lock device kit 1 2 Power supply EXE 3 4 Connector J14 24 V DC CPU board power supply 5 6 7 8...

Page 11: ...o be able to dispense 20 to 76 mm wide products In addition the spirals can be right or left hand to be used in double compartment configuration with double spiral The ratiomotor is fitted with a mini...

Page 12: ...ile the lamps and the cooling unit are controlled by means of special relay cards at the grid voltage The power supply unit is housed in a removable galvanised steel metal box for greater accessibilit...

Page 13: ...condenser cooling from the lower part of the base through a filter that removes the dust such filter is accessible and easy to remove for cleaning FIG 2 The cooling air is expelled from the front sid...

Page 14: ...by means of a single lock located inside the sliding compartment on the right A sliding compartment is located on the front right side with the user interface integrated on its front panel the CPU bo...

Page 15: ...nge the operating default values The machine will continue working but some parameters could have been changed with consequences to the general functioning the RAM needs to be initialised as soon as p...

Page 16: ...otected against short circuits with two line fuses one on each phase with fuses on the secondary winding and on CPU board power supply see wiring diagram Check that the fuses are intact and if necessa...

Page 17: ...hygiene practices After cleaning do not touch the surface of any elements that may come into contact with food Wash your hands thoroughly preferably using disinfectant before starting any hygiene ope...

Page 18: ...cabinet with a cloth dampened with a chlorine based detergent Check that there are no small insects Open the door and disconnect the machine form the power supply FIG 1 Clean the outside and inside of...

Page 19: ...ed detergents Completely remove the cooling unit FIG 3 thoroughly clean the internal base and make hygienic Remove all the dust from the fans and cooling unit condenser FIG 4 Clean and make hygienic t...

Reviews: