Ground-To-Neutral Specifications{ XE "Conductor:Specifications,
ground-to-neutral" \t "
See
" }{ XE "Voltage:Ground-to-neutral" }
With circuit power turned off, the resistance between the circuit neutral conductor
{
XE
"Conductor:Neutral"
}{
XE "Neutral conductor" \t "
See
Conductor, neutral"
}
and the isolated
ground conductor must be less than 2.1 ohms.
With circuit power on and all 5000
i
system components unplugged, the voltage between the
circuit neutral conductor and the isolated ground conductor must be less than 0.6 VAC.
Chapter 2. Scanner Installation
Page 13