Gas detection Control Unit 

 UCE1    

27/04/2021 

Gas detection systems for industrial environments 

1 of 4 

 

 

Sensigas

®

 

UCE1 

Gas detection control unit 

MED/3.54 (IEC 60092-504) certified 

 

Installation instructions

 

 

GENERAL 

The UCE1 control unit can be used to connect one detector (model 

URx13  or  URx20/21..)  to  create  gas  detection  systems  in 

environments  such  as  boiler  rooms,  workshops,  warehouses, 

laboratories  etc.;  the  incorporated  alarm  relay  can  be  used  to 

control  a  solenoid  valve  or  an  accessory  device  (siren,  flashing 

light, extractor, etc.). The installation of a gas or carbon monoxide 

detection  system  does  not  constitute  a  release  from  compliance 

with all regulations for the installation and use of gas devices and 

with the relative safety standards and legal provisions in force for 

this  kind  of  system.  Installation,  periodic  inspections  and 

maintenance  of  devices  and  systems  must  be  carried  out  by 

qualified service technicians. 

 

TECHNICAL SPECIFICATIONS 

UCE1 control unit (data URx20/21.. detectors in brackets) 

Power supply: 

12 Vac/dc 

 10% 

Consumption: 

about 160mA (320mA) with the detector only 

 

 

460mA  (620mA)  with  detector  and  failure 
output 

Connections: 

two terminals of 2.5 mm

2

 

Protection: 

Power input fuse 1A 5x20mm 

Inputs: 

one,  for  UGR13,  URP13,  URO13  detectors,  or 
URx20/21.. detectors (different types of gas) 

Detector connection: 

three terminals of 2.5 mm

2

 

C (-

12...24V); S (+4…20mA); A (+12...24V)

 

Max cable run length: 

50 m 

Diameter of the 3 wires: 

1.5 mm

2

 

Alarm output: 

1 relay with one contact SPDT 8A 250Vac 

Failure output: 

one open collector 12Vdc / 300mA max 

Output connections: 

three terminals of 2.5 mm

2

 for C-NC-NO relay 

 

 

two terminals of 2.5 mm

2

 for open collector 

Visual alarms: 

1 green LED: power on 

 

 

1 yellow LED: failure 

 

 

1 red LED: gas alarm 

Audible alarms: 

1 buzzer noise level > 60db at 1m 

“Reset/Test” button:

 

1 for alarm Reset and detector Test 

Enclosure: 

RAL7035 grey, self-extinguishing plastic house 

Dimensions and weight: 

105x90x58 mm (6 modules to standard  DIN 
43880), 185 g 

Mounting: 

Back panel Omega DIN rail (EN

 

50022)

 

Protection rating: 

IP20; IP40 when correctly installed in 

 

electric panel 

Room temperature: 

-

20…

+55°C 

Humidity 

90% RH (non condensing) 

 
 
         Conformity 

          0474 / xxxx (manufacturing year) 

 

 

CERTIFICATE n. MED327120CS 

MED Directive / Standards  MED 2014/90/EU / IEC 60092-504 
EMC Directive / Standards  EMC 2014/30/EU / EN50270 / EN 61326-1 

LVD Directive / Standards 

LV 2014/35/EU / EN60730-1 

Product Standard               EN60079-29-1 

 

URx13 (URx20/21..) detectors 

Power supply: 

from the UCE1 control unit 

Consumption: 

40 mA (200mA) 

Connections: 

three terminals of 2.5 mm

2

 

C (-

12...24V); S (+4…20mA); A (+12...24V)

 

URx13 models: 

Methane Gas 

URG13 

 

LPG 

URP13 

 

Carbon Monoxide 

URO13 

URx20/21.. models: 

Various gases, see dedicated data sheet 

Calibration: 

URG13:   10% LEL of Methane 

  URP13:  

12% LEL of LPG 

  URO13: 

200ppm of CO 

 

(URx20/21..: 20% LEL, 100ppm CO) 

Enclosure: 

self-extinguishing plastic 

Dimensions and weight: 

66x90x45 mm (depending on model),  65 g 

Mounting: 

wall-mounted using plastic screws and anchors 

Protection: 

IP44 (IP44, IP55 or IP65 depending on model) 

Room temperature: 

0

+50°C (-20

+50°C till -

40…

+70°C) 

Humidity: 

90% RH (non condensing) 

LVD Directives/Standards 

Not applicable 

EMC Directives/Standards 

EMC 2014/30/EU / EN50270 

 

Other features of URx20/21.. detectors 

See their technical features on dedicated data sheet.

 

 

INSTALLATION 

 

MOUNTING 

Ensure  correct  environmental  conditions  (See  Technical 

Specifications). 

 

UCE1 control unit 

To  guarantee  the  correct  protection  rating  for  the  device  it  must 

be  installed  in  an  electric  panel  manufactured  according  to  the 

laws  in  force  for  workplaces  and  that  can  also  house  the  power 

supply  system.  Mount  the  control  unit  on  a  rail  (to  DIN  EN 

50022),  using  accessories  for  standard  electric  panels.  It  can  be 

installed on a mounting plate or in DIN rail modules. 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

URx13 (URx20SW) detectors 

To  be  used  for  wall-mounting  (vertical),  attached  by  plastic 

screws and anchors. To install, insert a screwdriver in the recess 

at  the  bottom  of  the  enclosure  to  open  it;  avoid  damage  to  the 

sensor and do not touch the calibration devices.    The detectors 

must  be  correctly  positioned  for  the  system  to  operate  properly. 

For this purpose, the control units must be installed: 

-

 

in zones with constant natural air circulation 

-

 

in zones free of dust and dirt that could clog up the sensor and 
make it ineffective 

-

 

never  near  running  water,  exhaust  vents,  windows,  openings 

etc. 

-

 

at a suitable distance from the gas-fuelled equipment to avoid 

the  system  taking  inappropriate  action  due  to  possible 

functional loss. 

The  positioning  also  depends  on  the  type  of  gas  that  is  to  be 

detected, in particular: 

-

 

URG13:  Methane gas - high, about 20-30 cm from ceiling 

-

 

URP13:  LPG - low, about 20-30 cm from floor 

-

 

URO13:  CO - about 1.5 m from floor 

For new plants, the detector must be installed at the last possible 

moment  so  that  typical  worksite  activities  (particularly  welding, 

painting,  sealing  etc.),  do  not  damage  the  actual  detector 

(particularly the sensing element). 

 

URx20/21.. detectors 

See installation instructions on dedicated data sheet. 

 

ELECTRICAL CONNECTIONS 

Normal  electric  cables  can  be  used.  Still,  if  detectors  are  to  be 

installed  in  environments  with  high  exposure  to  EMI,  it  is 

advisable  to  use  shielded  cables.    The  detection  system  must 

always  be  operating,  so  power  switches  or  other  devices  that 

could  inadvertently  make  the  detector  inoperative  must  not  be 

used. Do not touch the sensing element and the electronic circuits 

for any reason whatsoever.  Tampering of any kind may cause the 

system to operate incorrectly. 

Ensure compliance with all current electric standards. 

 