STEP 3    After Installing 

  Opening All the Valves 

 

 

  Operating the Boiler 

 

 

  Measuring the Inlet Gas Pressure 

 

 

 

  Installing the Front Cover 

 

 

  Ensure Maximum Water Flow 

 

After running the boiler for the first 10 minutes, turn it off and clean the cold water 
filter and the space heating return strainer to remove any trapped debris. 

 

  Final Check 

 

A trial run should be performed in accordance with the Installation checklist listed in 
the boiler’s Installation & Operation Manual.

 

Shut off the manual gas 
valve. 

Open 

Closed 

Remove the front cover 
by loosening the 4 screws. 

Loosen the screw indicated in the 
figure and connect a manometer to 
the pressure port. Reset the 
manometer to zero before use. 

Open 

Check the inlet gas pressure reading on the manometer. 

Re-open the manual gas 
valve and check for leaks. 

Open multiple fixtures 
that have high flow rates, 
such as bathtub and 
shower faucets, to ramp 
the boiler up to its 
maximum firing rate. 
 

Adjust the inlet gas pressure with 
gas regulator. 

Gas supply 

If not, 

NG : 3.5

~10.5

  WC 

LP    : 8.0

~13.5

  WC 

Recommended Gas Pressure Settings: 

Open a hot water 
faucet. The boiler 
should turn on and 
the gas in the gas 
supply line will be 
purged. 

Leave the faucet on until the boiler 
shuts down due to a lack of gas 
supply, and then turn off the hot 
water faucet. 

 

  CAUTION

 

The boiler cannot function properly without sufficient inlet gas pressure.   

Measuring the inlet gas pressure should be performed by a licensed professional only.

 

 

Power ON 

Adjust Temperatures 

 

View Basic Information 

Resetting the Boiler 

When the power is on, the water 
temperature of the space heating 
supply will appear with the water 
pressure on the front panel 
display in 5 second intervals. 

 

1.

 

Press the Mode button three 

times. “INFO” will appear on 

the display.   

2.

 

Press the + or – buttons to 

switch between the 

information types. 

If an error message appears, you 
can try resetting the boiler to 
resolve the problem.   

Note 

Space Heating Temperature   

DHW Temperature   

 

1.

 

Make sure that all hot 

water faucets are closed, 

and ensure that the 

internal circulator and any 

external circulating 

pumps are off. 

2.

 

Press the Mode button 

twice. The DHW mode 

icon turns on. 

3.

 

Press + (Up) or – (Down) 

buttons until the desired 

temperature appears on 

the display. 

Note 

1.

 

Press the Mode button 

once. The space heating 

icon turns on.   

2.

 

Press the + (Up) or – (Down) 

buttons until the desired 

temperature appears on 

the display. 

DHW temperature 
higher than 125

°

F can 

cause scalding. 

If resetting does not solve 
the problem, refer to the 
troubleshooting section of 
the User’s Information 
Manual or contact the 
service center. 
 

Closed 