Navien NCB-240 Quick Installation Manual Download Page 2

 

   

 

  Gas Piping Connections 

 

 

 

  Water Piping Connections 

 

 

 

  Condensate Drain Connection 

 
A condensate drain pipe must be connected to the 1/2” condensate outlet fitting at 
the bottom of the unit and water must be poured into the exhaust connection to fill 
the condensate trap. 

 

The end of the 1/2

  (NPT) plastic piping should drain into a laundry tub or into a floor 

drain. 

 

 

Do not submerge the end of the 
pipe in water. 

 
 
 
 

Note 

Syphon 

Condensate Outlet 

Water 

Floor drain 

The boiler is recommended to be the first 
appliance to be connected to the gas supply 
line. 

Gas meter

s capacity 

  Total gas capacity of connected appliances 

Gas supply 

Gas 

Regulator 

Bottom View 

Gas Inlet Adapter 

Gas Supply Line 

Example: 

Gas meter 

425 CFH 

 

Boiler 

195 CFH 

Furnace 

58.8 CFH 

Domestic gas stove 

63.7CFH 

* 1 CFH=1,020 Btuh 

 

 

1/2" rigid pipe can be used; refer to the sizing tables in the Installation & 
Operation Manual for limitations. Avoid using 1/2" corrugated connectors 

or tubing as noise may occur. 

Built-in Water Fill Connection 

Navien NCB boiler is equipped with 
an auto-feeding water connection 
and motorized feeding valve. 
Therefore, installation of additional 
system water fill connection is not 
necessary in most cases. 

Note 

Backflow 
Preventer 

Make-up 
Water 

External Water Fill Connection 

 

Heating 
Supply 

Expansion Tank 

Circulator 

Pressure Relief Valve 

Air Separator 

Warning 

Water Piping Connections 

Space Heating System 

DHW System 

Install the included 3/4 in, maximum 30 
psi pressure relief valve on the space 
heating supply. 
   
An ASME approved HV pressure relief 
valve for space heating system is 
supplied with the boiler. 

The DHW pressure relief valve is 
not supplied, but is required.   
 

Install an approved 3/4 in, 
maximum 150 psi pressure relief 
valve on the hot water outlet. 

Space 
Heating 
Return 

Space 
Heating 
Supply 

Pressure Relief 
Valve 

Pressure 
Relief 
Valve 

Cold Water 

Supply 

DHW 
Supply 

Space 
Heating 
Supply 

Space 
Heating 
Return 

DHW 
Supply 

Cold 

Water 

Inlet 

 

Built-in   

Water Feeder 

Connection 

 

Flow Restrictor (for DHW system) 

Flow Rate (GPM) and Water Pressure (psi)

 

Orange 

Yellow 

Blue 

The boiler has a built-in flow restrictor at 
the cold water inlet adapter to limit the 
overall DHW flow. Three additional flow 
restrictors are provided for different flow 
rates. 

Refer to the following graph and install 
an appropriate restrictor for your DHW 
system. See the Installation & Operation 
Manual (page 21, 22) for detailed 
procedures.   
 

Flow Restrictors (Orange, Yellow, and Blue) 

Ensure that the Air Vent Cap is removed 
before filling the system. 
System will not be properly filled 
without the air vent cap removed. Air in 
the system may cause malfunctions 
and system overheating.       

Make-up 
Water 

Direct to the 

external drain 

To the drain via 

a neutralizer 

External drain 

To the laundry 

tub 

To the laundry tub 

via a condensate pump 

System Fill Connection 

The Navien NCB boilers 
have a built-in air vent 
on top of the internal 
circulator to purge air 
from the boiler system. 

Air Vent Cap 

Before filling the boiler, remove the air vent cap to 
allow the system to fill properly. Replace the cap 
when the system is full. 

 

Heating 
Return 