background image

18        Maintaining the Boiler

Checking the Water System

1.  Verify all system components are correctly installed and 

operational.

2.  Check the cold fill pressure for the system. Verify it is correct 

(must be a minimum of 12 psi).

3.  Watch the system pressure as the boiler heats up (during 

testing) to ensure pressure does not rise too high.

Note

 

Ɣ

If the system contains glycol, test for proper 
concentration as recommended by manufacturer.

 

Ɣ

Excessive pressure rise indicates expansion tank 
sizing or performance problem.

4.  Inspect automatic air vents and air separators. Remove air vent 

caps and briefly press push valve to flush vent.

5.  Replace caps. Make sure vents do not leak. Replace any leaking 

vents.

Checking Expansion Tank

 

Ɣ

Expansion tanks provide space for water to move in and out as 
the heating system water expands due to temperature increase 
or contracts as the water cools.

 

Ɣ

Perform annual checks as recommended by manufacturer to 
ensure proper operation.

Checking the Pressure Relief Valves

Inspect the relief valve and lift the lever to verify flow. Before 
operating any relief valve, ensure that it is piped with its discharge 
in a safe area to avoid severe scald potential.

WARNING

Explosion Hazard

A dripping or leaking pressure relief valve must be replaced. 
Do not plug or remove the valve. Failure to follow these 
instructions can result in fire or explosion, and personal injury 
or death.

Note

Safety relief valves should be inspected 

at least once 

every three years

, by a licensed plumbing contractor 

or authorized inspection agency, to ensure that the 
product has not been affected by corrosive water 
conditions and to ensure that the valve and discharge 
line have not been altered or tampered with illegally.

WARNING

 

Ɣ

Certain naturally occurring conditions may corrode the 
valve or its components over time, rendering the valve 
inoperative. Such conditions are not detectable unless 
the valve and its components are physically removed and 
inspected. This inspection must only be conducted by a 
plumbing contractor or authorized inspection agency – not 
by the owner. Failure to re-inspect the boiler relief valve 
as directed could result in unsafe pressure buildup, which 
can result in severe personal injury, death, or substantial 
property damage.

 

Ɣ

Following installation, the valve lever must be operated 

at 

least once a year

 to ensure that waterways are clear. Certain 

naturally occurring mineral deposits may adhere to the valve, 
rendering it inoperative. When manually operating the lever, 
water will discharge and precautions must be taken to avoid 
contact with hot water and to avoid water damage. 

 

Ɣ

Before operating lever, check to see that a discharge line 
is connected to this valve directing the flow of hot water 
from the valve to a proper place of disposal. Otherwise 
severe personal injury may result. If no water flows, valve is 
inoperative. Shut down the boiler until a new relief valve has 
been installed.

After following the above warning directions, if the relief valve 
weeps or will not seat properly, replace the relief valve. Ensure 
that the reason for relief valve weeping is the valve and not over-
pressurization of the system due to expansion tank waterlogging 
or undersizing.

Inspecting the Ignition and Flame Detector Electrodes

1.  Remove the ignition and flame detector electrodes from the 

boiler heat exchanger.

2.  Remove any deposits accumulated on the ignition/flame 

detector electrode. If the electrodes cannot be cleaned 
satisfactorily, replace with new ones.

3.  Replace ignition/flame detector electrode, making sure gasket 

is in good condition and correctly positioned.

Checking the Ignition Ground Wiring 

1.  Check that the ground wire is in good condition and securely 

attached to the boiler casing.

2.  Check ground continuity of wiring using continuity meter.

3.  Replace ground wires if ground continuity is not satisfactory.

Summary of Contents for NBH Series

Page 1: ...our gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified...

Page 2: ...oiler On or Off 9 3 2 Adjusting the Temperature 9 3 3 Viewing Basic Information 10 3 4 Resetting the Boiler 11 4 Maintaining the Boiler 12 4 1 Cleaning the Boiler 12 4 2 Draining the Boiler 12 4 3 Cle...

Page 3: ...tment C Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas co...

Page 4: ...er using a lower temperature setting Do not leave children the elderly or disabled persons unsupervised Do not allow small children to play unsupervised in the bathroom Do not allow anyone to change t...

Page 5: ...ler in any other country will void the manufacturer s warranty Should overheating occur or the gas supply fail to shut off turn off the manual gas valve to the appliance WARNING Shut off the gas suppl...

Page 6: ...e temperature and if necessary initiates a safety heating cycle to prevent internal equipment damage due to freezing temperatures Short Circuit Protection Any short circuit occurring in the boiler s e...

Page 7: ...n Refer to the following table for detailed information a Space heating mode f S Supply water control Indicates space heating mode operation Indicates supply water control status b Error g R Return wa...

Page 8: ...ler s operation such as space heating and DHW supply temperatures Refer to the following table for detailed information k Diagnostics button n Up button For installers only Increases the temperature l...

Page 9: ...olute MIN to 149 F 65 C Absolute MAX You can adjust the temperature range in the parameter settings menu The boiler will retain your settings during a power outage WARNING Follow the instructions belo...

Page 10: ...ting the DHW Indirect Supply Temperature WARNING Before adjusting the water temperature read To prevent burns on page 4 carefully Water above 120 F can cause instant scalding severe burns or death To...

Page 11: ...Troubleshooting section of this manual or contact Technical Support at 1 800 519 8794 Display Description psi O R S R Boost interval time set by installer psi O R S R Space heating water pressure in...

Page 12: ...e resistant but it is not waterproof Keep it as dry as possible 4 2 Draining the Boiler You will need to drain the boiler before performing maintenance tasks such as to prevent the boiler from freezin...

Page 13: ...clean the air intake filter every 3 4 months To clean the air intake filter 1 Press the Power button on the front panel to turn off the boiler MODE 2 Disconnect the power supply to the boiler 3 Remov...

Page 14: ...of the boiler 6 Remove the filter from the plastic assembly Dust and rinse it with clean running water 7 Allow the filter to dry completely 8 Place the filter assembly back into the boiler and secure...

Page 15: ...ringdefect andtherefore Navienwillnotwarrant any damages due to freezing The installer is responsible for ensuring that there is sufficient make up air to avoid such a situation and the owner is respo...

Page 16: ...emove and clean space heating strainer Remove and clean inlet water filter 4 5 Maintenance Schedules Regular maintenance is required to operate the boiler safely Refer to the maintenance schedules bel...

Page 17: ...aminants listed in Installation Operation Manual If any of these are present in the boiler intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lines per the I...

Page 18: ...ring the valve inoperative Such conditions are not detectable unless the valve and its components are physically removed and inspected This inspection must only be conducted by a plumbing contractor o...

Page 19: ...iring making sure wires are in good condition and securely attached Checking the Control Settings 1 From the front panel enter the Diagnostics Mode and check all settings Adjust settings if necessary...

Page 20: ...llow the solution to circulate through the boiler Refer to the manufacturer s literature for information about the circulation time 10 Rinse the cleaning solution from the boiler a Remove the free end...

Page 21: ...the system in stand by Make sure the power is on and plugged into the outlet with the correct voltage Press the Power button and raise the setting temperature Make sure the boiler is turned on Is the...

Page 22: ...eration heating supply thermistor Auto reset E218 Abnormal operation heating return thermistor Alarm E271 Temperature differential limit Alarm E278 Abnormal operation system supply thermistor Alarm E2...

Page 23: ...at issue The replacement component or product will be warranted only for the unexpired portion of the applicable warranty period for the original component or Product The heat exchanger is covered by...

Page 24: ...tion for non recommended uses failure to follow or comply with the User s Operational Manual etc Improper maintenance including but not limited to scale buildup vent blockage failure to maintain etc M...

Page 25: ...Notes...

Page 26: ......

Page 27: ...tact a licensed professional for the affected system for example a plumber or electrician When you contact Technical Support please have the following information at hand Model number Serial number Da...

Reviews: