![Nautel NV5 Troubleshooting Manual Download Page 15](http://html2.mh-extra.com/html/nautel/nv5/nv5_troubleshooting-manual_3541567015.webp)
NV5/NV3.5 Troubleshooting Manual
Responding to alarms
Issue 3.2 2014-12-10
Page 1-7
Table 1.1: Troubleshooting Alarms
Alarm (with Prefix)
Description and Troubleshooting Action
Controller: +12V
Supply A (or B) Fault
This alarm occurs if the +12 V supply from SBC/AUI power supply A
(U1) or B (U2) is outside its acceptable voltage range (b10.8
and +13.2 V). Use a digital multimeter to measure between
+V
and
-V
of the s12 V supply’s output voltage. If necessary, replace the
+12 V supply (see
“+12 V Power Supply Replacement” on page 1-
). If the alarm persists after replacing the supply, suspect the
control/interface PWB (A1).
Controller: +15V
Supply A (or B) Fault
This alarm occurs if the +15 V supply from LVPS module A (U3) or B
(U4) is outside its acceptable voltage range (b13.5 and
+16.5 V). Use a digital multimeter to measure between
V2
and
COM
of the suspect LVPS output voltage. If necessary, replace the LVPS
(see
“LVPS Replacement” on page 1-40
). If the alarm persists after
replacing the supply, suspect the control/interface PWB (A1).
Controller: -15V
Supply A (or B) Fault
This alarm occurs if the +15 V supply from LVPS module A (U3) or B
(U4) is outside its acceptable voltage range (between -13.5 and
-16.5 V). Use a digital multimeter to measure between
V3
and
COM
of
the suspect LVPS output voltage. If necessary, replace the LVPS (see
“LVPS Replacement” on page 1-40
). If the alarm persists after
replacing the supply, suspect the control/interface PWB (A1).
Controller: +5V
Supply A (or B) Fault
This alarm occurs if the +5 V supply from LVPS module A (U3) or B
(U4) is outside its acceptable voltage range (b4.95 and
+6.05 V). Use a digital multimeter to measure between
V1
and
COM
of
the suspect LVPS output voltage. If necessary, replace the LVPS (see
“LVPS Replacement” on page 1-40
). If the alarm persists after
replacing the supply, suspect the control/interface PWB (A1).
Controller: Active
Exciter Fail
This alarm occurs when a system inhibiting fault has occurred within
the active exciter. The transmitter will be latched off (or changeover to
the standby exciter, if applicable). Check for associated Exciter
prefixed alarm(s) that may have caused the failure and refer to their
troubleshooting action.
Controller: Active
Exciter Not
Responding
This alarm occurs if the active exciter is not responding to serial
messages. Check the integrity of the cable between the exciter’s
TX
LINK
connector and J5 or J6 (as applicable) of the control/interface
PWB. If the connection is secure, the problem is likely exciter related.
Check for associated Exciter prefixed alarm(s) that may have caused
the failure and refer to their troubleshooting action.
Summary of Contents for NV5
Page 2: ......
Page 4: ......
Page 8: ...NV5 NV3 5 Troubleshooting Manual Page viii Issue 3 2 2014 12 10...
Page 168: ...NV5 NV3 5 Troubleshooting Manual Wiring connector lists Page 4 16 Issue 3 2 2014 12 10...
Page 174: ...NV5 NV3 5 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 3 2 2014 12 10...
Page 196: ...Issue 3 2 2014 12 10 SD 20 Figure SD 20 Power Amplifier Pallet CD2011B...
Page 212: ...Issue 3 2 2014 12 10 MD 6 Figure MD 6 NAI17 RF Drive Splitter Changeover Assembly A2 A1...
Page 213: ...Issue 3 2 2014 12 10 MD 7 Figure MD 7 Ac Distribution Assembly 206 5150 01...
Page 217: ...Issue 3 2 2014 12 10 MD 11 Figure MD 11 NAL09A 2 Input Reject Load Assembly A1...
Page 227: ......