GV30N TROUBLESHOOTING MANUAL
RESPONDING TO ALARMS
PAGE 4.1.12
VERSION 0.1 2014-11-01
Controller: High SWR Output Network
(amber)
This alarm occurs if the transmitter's average reflected power exceeds the
high SWR threshold (840 W). The GV30N takes no action on this alarm.
Inspect the antenna and transmission line system for damage or de-tuning.
Controller: High SWR
Shutdown
Output Network (red) This alarm occurs if the transmitter tries to reduce the forward power below
a level that is equivalent to a 3:1 VSWR (user-configurable) at the SWR
Foldback threshold due to a gradually degrading load match. This alarm
causes the transmitter to latch off. Inspect the antenna and transmission
line system for damage or de-tuning.
Controller: High
Temperature
Summary
-
Not displayed in AUI or UI status. Configurable as a remote output.This
alarms occurs if there are high temperature related alarms occurring. Check
for specific temperature related alarms and troubleshoot accordingly.
Controller: Local UI
Failure (UI Failure)
Exciter (red)
This alarm occurs if there is a fault with the LCD user interface (UI),
preventing it from being used to control the transmitter. The transmitter will
automatically switch to remote control mode to allow use of the AUI or
digital I/O.
Controller: Low AC
Operation
Power Supply (red)
This alarm occurs if the ac input voltage is less than 175 V ac, but greater
than 90 V ac. Transmitter RF output power will be limited to approximately
33% of maximum power or to the current setpoint, whichever is less.
Controller: Low
Battery
Exciter (amber)
This alarm occurs if the backup battery voltage falls below an acceptable
level (2.7 V). The GV30N takes no action on this alarm. Use a digital
multimeter to measure the battery voltage (with ac power on). If the battery
voltage is low, replace the battery. If battery voltage is OK, cycle ac power
(off, then on). If the alarm does not clear, check the controller PWB (A4A2).
Controller: Low
Battery/Memory
Summary
Power Supply (red)
Not displayed in AUI or UI status. Configurable as a remote output.This
alarms occurs if there is a specific battery or memory related alarm present.
Check for specific alarms and troubleshoot accordingly.
Controller: Low
Efficiency
Output network
(amber)
This alarm occurs in conjunction with the Combiner Match alarm to indicate
that the transmitter is exhibiting low dc-RF efficiency.
Controller: Low
Forward Power (Low
Fwd Power)
Output Network
(amber)
This alarm occurs if the transmitter’s average forward power is below the
low forward power threshold (defaulted to 50% of the setpoint and is user
adjustable). Check for associated alarms and follow the associated
troubleshooting procedure, if applicable.
Controller: Low RF
Drive
Exciter (red)
This alarm occurs if the RF drive power from the exciter is less than the low
threshold (70% of the setpoint). Ths may be the result of a calibration
problem with either the exciter or the transmitter RF drive sample. Check all
connections to the exciter. Check the RF drive connection between the
exciter RF output and the RF drive splitter input.
Device and
Alarm Name
(AUI, UI)
Controller Front
Panel LED (color)
Description and Troubleshooting Action
Summary of Contents for GV30N
Page 2: ......
Page 4: ......
Page 8: ...GV30N TROUBLESHOOTING MANUAL PAGE 4 VIII VERSION 0 1 2014 11 01...
Page 92: ...GV30N TROUBLESHOOTING MANUAL PARTS LISTS PAGE 4 2 10 VERSION 0 1 2014 11 01...
Page 318: ...VERSION 0 1 2014 11 01 SD 32 Figure SD 32 NAE107A or NAE107A 01 Exciter...
Page 327: ...VERSION 0 1 2014 11 01 SD 41 Figure SD 41 NAFP109B Output Power Probe and Sample PWBs...
Page 337: ...GV30N TROUBLESHOOTING MANUAL MECHANICAL DRAWINGS PAGE 4 5 4 VERSION 0 1 2014 11 01...
Page 351: ...VERSION 0 1 2014 11 01 MD 14 Figure MD 14 NAPA31C Power Amplifier PWB Q1...
Page 363: ...GV30N TROUBLESHOOTING MANUAL LIST OF TERMS PAGE 4 6 2 VERSION 0 1 2014 11 01...
Page 364: ......