5
See the dimensional details below for the mounting hole positions.
Condensate
Drain
Condensate
Drain
On the unit housing.
Under the lid.
INSTALLATION
1. Position the MON-MEVH, taking into consideration the position of the rooms to be ventilated, the
exhaust position, the drainage position and the electrical services. Ensure there is adequate access for
installation and maintenance. Securely mount the MON-MEVH through the mounting brackets on the
casing using the appropriate anti-vibration mounts, screws, washers, rubber bushes etc.
2. Where the intake and exhaust ducts are to be connected to the MON-MEVH, remove the spigot caps, if
125mm ducting is being used. If 100mm ducting is being used, peel out the center of the cap with a
screwdriver as indicated and leave the cap surround in position. To connect ducting to the base intake,
use a suitable adaptor attached using the 4 holes provided.
3. Ducting passing through an unheated roof void should be insulated. Ducting runs should be as straight
as possible and intake ducting should slope downwards from Under the lid. Connect ducting to the MON-
MEVH spigots and to appropriate ceiling terminations.
4. Select the drain spigot required, remove the “Knockout” and connect a suitable drainage system.
WIRING
WARNING: THE MON-MEVH AND ANCILLARY CONTROL EQUIPMENT MUST BE
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR
MAINTENANCE.
THE MON-MEVH UNIT MUST BE EARTHED.
1. Connect mains supply as (
Fig. 1
).
2. Check that all connections have been made correctly. Ensure that all terminal screws and cable clamps
are securely fastened.
3. The cable entry must be made using a suitable grommet or cable gland.
4. After performing the following set-up instructions, switch the mains supply on and check the system is
operating correctly.
Fig 1
Switched Fused
Spur
1
9
E
E
5
7
8
N
3
4
2
1 Phase
Supply
(220-240V
50Hz).
E
N
L
~
3A