Installation
12
3.
Fit
the
vertical
condensate
pipe
and
secure
with
worm
drive
clip
The
condensate
pipe
can
be
attached
with
a
worm
drive
clip
to
a
22
mm
vertical
pipe.
Fit
a
‘U’
bend
condensate
drain
having
a
minimum
of
a
60mm
water
seal
or
a
HepvO
valve
to
the
building’s
foul
water
drainage
system
and
ensure
there
is
a
minimum
3
degree
fall
to
allow
condensate
drainage.
Both
left
hand
and
right
hand
condensate
drain
pipes
are
supplied
for
use
as
appropriate
depending
on
the
orientation
of
the
unit.
4
.
Go
to
Spigot
Installation
on
page
14.
Horizontal Discharge Condensate Installation
To
install
the
condensate
horizontal
discharge:
1.
For
horizontal
discharge,
remove
the
front
cover
and
locate
the
condensate
stub
at
the
front
of
the
unit.
2.
Remove
the
Black
Cap
from
end
of
condensate
stub
at
the
front
of
the
unit.