![National Instruments SCC-DO01 User Manual Download Page 7](http://html1.mh-extra.com/html/national-instruments/scc-do01/scc-do01_user-manual_3704611007.webp)
SCC-DO01 Isolated Digital Output Module User Guide
6
ni.com
Specifications
These specifications are typical at 25 °C unless otherwise stated.
Output Characteristics
Compatibility ..........................................TTL-compatible
Number of channels................................1
Supply voltage range ..............................5 to 24 VDC
Digital logic levels
Configuration 1 (refer to Figure 1)
Configuration 2 (refer to Figure 2)
Maximum continuous load current (
I
O
)
Configuration 1................................86 mA
Configuration 2................................120 mA
Minimum load resistance (at
V
SS
=
24 V)
R
LOAD1
..............................................196
Ω
R
LOAD2
..............................................184
Ω
Logic Level
Output Voltage Level
between V
OUT
and V
COM
Low (
I
O1
= 0 mA)
0 V
High (
I
O1
= 25 mA)
22 VDC at
V
SS
= 24 V
3 VDC at
V
SS
= 5 V
Logic Level
Output Voltage Level
between V
OUT
and V
COM
Low (
I
O2
= 25 mA)
0.4 V
High (
I
O2
= 0 mA)
V
SS
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com