![National Instruments SCC-A10 User Manual Download Page 4](http://html1.mh-extra.com/html/national-instruments/scc-a10/scc-a10_user-manual_3693995004.webp)
SCC-A10 Voltage Attenuator Module User Guide
4
ni.com
Connecting the Input Signals
Note
The signal names have changed. Refer to
ni.com/info
and enter
rdtntg
to
confirm the signal names.
Each screw terminal is labeled by pin number <1..4>. Pins 1 and 2 form
a differential channel routed to E Series DAQ device channel
X
+
8, and
pins 3 and 4 form a second differential channel routed to E Series DAQ
device channel
X
. The value of
X
is determined by the number of the
SC-2345 socket where you plug in the module, J(
X
+
1) or J(
X
+
9).
The signal source can be floating or ground-referenced. Floating signal
sources do not require bias resistors to ground with the SCC-A10. Figure 1
shows the SCC-A10 signal connections.
Figure 1.
SCC-A10 Signal Connections
For information about how to configure the SCC-A10 module using
NI-DAQmx, refer to the
SCC Quick Start Guide
.
Signal
Source
AI (
X
)
AI SENSE
AI (
X
+8)
SCC-A10
+
–
E Series DAQ Device
Overvoltage
Protection
Overvoltage
Protection
+
–
+
–
Overvoltage
Protection
Overvoltage
Protection
+
–
Signal source may be floating or ground-referenced.
1
3
4
2
AI GND