The velocity range is the maximum velocity that can be measured 
for a given timebase. The velocity register uses a 15-bit counter, 
which gives a maximum number of counts of 2

15

, or 32,768. So, the 

velocity range for a given timebase is calculated using the 
following formula:

where V

rng

 is the velocity range in counts per microsecond and T is 

the timebase in microseconds.

The velocity resolution is the velocity accuracy for a given 
timebase and is determined using the following formula:

where V

res

 is the velocity resolution in counts per millisecond and 

T is the timebase in microseconds.

Index Status Channel Operation

The FP-QUAD-510 includes four discrete input channels, channels 
12 through 15, which contain the status of the Index signal for axes 
0 through 3 respectively. This signal is latched to a 1 when the 
condition at the axis inputs is Phase A = 0, Phase B = 0, and 
Index = 1. This bit remains latched until it is read, at which point it 
is cleared automatically. 

Table 2.  

Velocity Ranges

Length of Timebase 

(in µs)

Velocity Range

(in counts/µs)

Velocity

Resolution

204.8

±160

4.883 counts/ms

409.6

±80

2.441 counts/ms

819.2

±40

1.221 counts/ms

1638.4

±20

610.4 counts/s

3276.8

±10

305.2 counts/s

6553.6

±5

152.6 counts/s

13107.2

±2.5

76.29 counts/s

26214.4

±1.25

38.15 counts/s

V

rng

32768

±

T

------------------

=

V

res

1000

T

------------

=

Summary of Contents for Quadrature Input Module FP-QUAD-510

Page 1: ...0 Features The FP QUAD 510 is a FieldPoint quadrature input module with the following features Four independent 32 bit position counters with individual Phase A Phase B and Index input terminals Veloc...

Page 2: ...n a FieldPoint terminal base FP TB xx unit Because of its hot plug and play operation you can install the FP QUAD 510 onto a powered terminal base without disturbing the operation of other modules or...

Page 3: ...ne driver Figure 2 shows the typical encoder wiring for differential signal input Figure 3 shows the typical encoder wiring for single ended signal input Power for a 5 V encoder is also provided for e...

Page 4: ...x signal must occur when both the Phase A and Phase B signals are low as shown in Figure 4 If the index polarity is inverted try reversing the Index and Index signals on differential encoders or using...

Page 5: ...nto a terminal base and apply power the green POWER indicator lights and the FP QUAD 510 informs the network module of its presence When the network module recognizes the FP QUAD 510 it sends initial...

Page 6: ...nsists of a comparator with current limited inputs to convert from a differential to a single ended signal The output of the comparator is used to drive an optoisolator When you apply a voltage above...

Page 7: ...f position the velocity for each axis The four velocity data registers channels 8 through 11 contain 16 bit velocity data for axes 0 through 3 respectively The data in each register represents the vel...

Page 8: ...per millisecond and T is the timebase in microseconds Index Status Channel Operation The FP QUAD 510 includes four discrete input channels channels 12 through 15 which contain the status of the Index...

Page 9: ...fault voltages of up to 2 500 Vrms In addition the FP QUAD 510 provides double insulation compliant with IEC 1010 1 for working common mode voltages of 250 Vrms Safety standards such as those publish...

Page 10: ...els as accessed through FieldPoint Explorer or other software Table 3 FP QUAD 510 Channel Operation Summary Channel No Channel Description Type Range 0 Axis 0 Position LSW Count Input 0 65535 1 Axis 1...

Page 11: ...C on each input Input bandwidth 250 kHz for each input Encoder frequency 1 million counts second Minimum input pulse width 2 s Isolation 2 500 Vrms Safety isolation working voltage 250 Vrms designed p...

Page 12: ...isolation installation category II EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 m Mechanical Dimensions Figure 7 shows the mechanical dimensions of the FP QUAD...

Reviews: