Chapter 2
Installation and Configuration
2-18
ni.com
•
Switch 3—
Disable Startup VI
: Set this switch to ON to prevent
VIs from automatically running at startup if the controller becomes
inaccessible because of a startup VI.
•
Switch 4—
Reset IP Address
: Set this switch to ON to reset the
IP address and other TCP/IP settings to their factory defaults. Use this
switch if moving the controller to a different subnet or if the current
TCP/IP settings are valid.
Note
By default, the target will automatically attempt to connect to the network using
DHCP. If the target is unable to initiate a DHCP connection, the target connects to the
network with a link-local IP address or
169.254.x.x
.
Figure 2-4 shows the location of the LabVIEW RT configuration switches.
The switches are shown in the OFF position.
Figure 2-4.
LabVIEW RT Configuration Switches
1
S
witch 1—Boot L
ab
VIEW RT
2
S
witch 2—Boot
Sa
fe Mode
3
S
witch
3
—Di
sab
le
S
t
a
rt
u
p VI
4
S
witch 4—Re
s
et IP Addre
ss
3
2
1
4