Troubleshooting the sbRIO-9627
The sbRIO-9627 is Not Communicating with the
Network
•
Ensure that the Ethernet connections between the sbRIO-9627 and the host computer and
the Ethernet connections between the host computer and the router are secure.
•
Ensure that you have the correct version of NI CompactRIO Device Drivers installed on
the host computer. Visit
and enter the Info Code
softwareversion
for the
minimum supported versions of LabVIEW and NI CompactRIO Device Drivers.
Tip
If you have recently upgraded LabVIEW, you must reinstall NI
CompactRIO Device Drivers.
•
Temporarily disable any network firewalls or other security software.
Configure the IP and other network settings by completing the following steps.
1. Use a standard Category 5 (CAT-5) or better shielded, twisted-pair Ethernet cable to
connect the sbRIO-9627 Ethernet port to a host computer. The sbRIO-9627 attempts to
initiate a DHCP network connection at powerup.
2. In MAX, expand your system under Remote Systems and select
Troubleshoot Remote
System Discovery
.
System Reset
The following figure shows the reset behavior of the sbRIO-9627.
Figure 3.
Reset Button Behavior
Press and hold RESET button for
≥
5 s
Press and hold RESET button for
<
5 s
Run Mode
Safe Mode
Press and hold RESET button for
<
5 s
Press and hold RESET button for
≥
5 s
Press and hold
RESET button for
≥
5 s
Press and hold
RESET button for
<
5 s
• Console Out enabled
• Network settings reset
• RT Startup App disabled
• FPGA Startup App disabled
• Console Out enabled
• RT Startup App disabled
• FPGA Startup App disabled
Safe Mode
8
|
ni.com
|
NI sbRIO-9627 Getting Started Guide