Capacitance

0.2 µF maximum

Special Conditions for Hazardous Locations Use in Europe and

Internationally

The NI-9403 has been evaluated as Ex nA IIC T4 Gc equipment under

DEMKO 07ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI-9403 is marked

 II 3G and is suitable for use in Zone 2 hazardous locations, in ambient

temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9403 in Gas Group IIC

hazardous locations, you must use the device in an NI chassis that has been

evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.

Caution

 Transient protection shall be provided that is set at a level not

exceeding 140% of the peak rated voltage value of 85 V at the supply

terminals to the equipment.

Caution

 The system shall only be used in an area of not more than

Pollution Degree 2, as defined in IEC/EN 60664-1.

Caution

 The system shall be mounted in an ATEX/IECEx-certified

enclosure with a minimum ingress protection rating of at least IP54 as

defined in IEC/EN 60079-15.

Caution

 The enclosure must have a door or cover accessible only by the

use of a tool.

Electromagnetic Compatibility Guidelines

This product was tested and complies with the regulatory requirements and limits

for electromagnetic compatibility (EMC) stated in the product specifications. These

requirements and limits provide reasonable protection against harmful interference

when the product is operated in the intended operational electromagnetic

environment.

© National Instruments

5

NI-9403 Getting Started

Summary of Contents for NI 9403

Page 1: ...NI 9403 Getting Started 2022 07 06...

Page 2: ...ons 4 Electromagnetic Compatibility Guidelines 5 Special Conditions for Marine Applications 6 Preparing the Environment 6 Connecting the NI 9403 7 Connecting Digital Devices to the NI 9403 7 Overcurre...

Page 3: ...atings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user documentation Using the product in a manner not specified can damage the product and compromise...

Page 4: ...tentially explosive environment Not following these guidelines may result in serious injury or death Caution Do not disconnect I O side wires or connectors unless power has been switched off or the ar...

Page 5: ...ated voltage value of 85 V at the supply terminals to the equipment Caution The system shall only be used in an area of not more than Pollution Degree 2 as defined in IEC EN 60664 1 Caution The system...

Page 6: ...s Some products are approved for marine shipboard applications To verify marine approval certification for a product visit ni com product certifications search by model number and click the appropriat...

Page 7: ...DIO15 RSVD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Signal Name Description DIO Each channel includes a DIO pin to which you can connect a...

Page 8: ...dule sets all the DIO channels to high impedance for approximately 280 ms When the channels are in an overcurrent state the NI 9403 can accept new line direction configuration and output state data bu...

Page 9: ...ion downloads and troubleshooting and application development self help such as tutorials and examples Visit ni com services to learn about NI service offerings such as calibration options repair and...

Reviews: