Caution
Ensure that hazardous voltage wiring is performed only by
qualified personnel adhering to local electrical standards.
Caution
Do not mix hazardous voltage circuits and human-accessible
circuits on the same module.
Caution
Ensure that devices and circuits connected to the module are
properly insulated from human contact.
Note
When module terminals are hazardous voltage LIVE (>42.4 V
pk
/
60 V DC), you must ensure that devices and circuits connected to the
module are properly insulated from human contact. You must use the
NI-9940 connector backshell kit with the NI-9264 with spring terminal to
ensure that the terminals are not accessible.
NI-9264 with Spring Terminal (Black Connector) Safety Voltages
Connect only voltages that are within the following limits.
Isolation
Channel-to-channel
None
Channel-to-earth ground
Continuous
250 V RMS, Measurement Category II
Withstand
2,300 V RMS, verified by a 5 s dielectric withstand test
NI 9264 with DSUB Safety Voltages
Isolation
Channel-to-channel
None
Channel-to-earth ground
ni.com
4
NI-9264 Getting Started