Caution
The system must be installed in an enclosure
certified for the intended hazardous (classified)
location, having a tool secured cover/door, where a
minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use
in Europe and Internationally
The NI 9236 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO 07 ATEX 0626664X and is IECEx UL 14.0089X
certified. Each NI 9236 is marked II 3G and is suitable for use
in Zone 2 hazardous locations, in ambient temperatures of -40 °C
≤ Ta ≤ 70 °C. If you are using the NI 9236 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that
has been evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or
Ex nL IIC T4 equipment.
Caution
Transient protection shall be provided that is
set at a level not exceeding 140% of the peak rated
voltage value of 85 V at the supply terminals to the
equipment.
Caution
The system shall only be used in an area of
not more than Pollution Degree 2, as defined in
IEC/EN 60664-1.