Connect the positive lead of the isolated outputs power source to the V terminal of the
power connector plug and tighten the terminal screw to 0.2 N · m to 0.25 N · m (1.8 lb ·
in. to 2.2 lb · in.) of torque.

5.

Connect the negative lead of the isolated outputs power source to the C terminal of the
power connector plug and tighten the terminal screw to 0.2 N · m to 0.25 N · m
(1.8 lb · in. to 2.2 lb · in.) of torque.

6.

Install the power connector plug into ISO PWR IN on the front panel of the controller and
tighten the connector screws to 0.4 N · m (3.5 lb · in.) of torque.

7.

Turn on the external power source.

IC-3173 (IP67)

The following information applies to the IC-3173 (IP67).

Safety Information

Caution

 

The following paragraphs contain important safety information you must

follow when installing and operating the device.

Do not operate the device in a manner not specified in the documentation. Misuse of the
device may result in a hazard and may compromise the safety protection built into the device.
If the device is damaged, turn it off and do not use it until service-trained personnel can check
its safety. If necessary, return the device to National Instruments for repair.

Keep away from live circuits. Do not remove equipment covers or shields unless you are
trained to do so. If signal wires are connected to the device, hazardous voltages can exist even
when the equipment is turned off. To avoid a shock hazard, do not perform procedures
involving cover or shield removal unless you are qualified to do so. Disconnect all field power
prior to removing covers or shields.

Because of the danger of introducing additional hazards, do not install unauthorized parts or
modify the device. Use the device only with the chassis, modules, accessories, and cables
specified in the installation instructions. All covers and filler panels must be installed while
operating the device. All cabling must be suitably rated for outdoor use.

This is a Pollution Degree 3 device. Do not operate the device in an explosive atmosphere or
where flammable gases or fumes may be present. Operate the device only at or below the
pollution degree stated in the specifications. Pollution consists of any foreign matter—solid,
liquid, or gas—that may reduce dielectric strength or surface resistivity. The following is a
description of pollution degrees.

Pollution Degree 1—No pollution or only dry, nonconductive pollution occurs. The
pollution has no effect.

Pollution Degree 2—Normally only nonconductive pollution occurs. Occasionally,
nonconductive pollution becomes conductive because of condensation.

Pollution Degree 3—Conductive pollution or dry, nonconductive pollution occurs.
Nonconductive pollution becomes conductive because of condensation.

IC-317x Getting Started Guide

  | 

© National Instruments

  | 

7

Summary of Contents for IC-3171

Page 1: ...Compatibility Guidelines 8 Preparing the Environment 9 Configuring the Hardware 9 Connecting the System Power Supply 10 Connecting the Isolated Outputs Power Supply 11 Connecting the DisplayPort Conne...

Page 2: ...e specifications Pollution consists of any foreign matter solid liquid or gas that may reduce dielectric strength or surface resistivity The following is a description of pollution degrees Pollution D...

Page 3: ...10 ft A DC mains supply is a local DC electricity supply network in the infrastructure of a site or building Caution To ensure the specified EMC performance the length of cables connected to the video...

Page 4: ...Power over Ethernet PoE LED Indicators 4 Gigabit Ethernet Ports with PoE 5 44 pin Digital I O Connector 6 Isolated Power Input Connector 7 Chassis Grounding Screw 8 Reset Button not pictured 9 Power...

Page 5: ...Do not tighten or loosen the terminal screws on the power connector while the power is on 3 Connect the positive lead of the primary power source to the V1 terminal of the power connector plug and tig...

Page 6: ...isolated outputs power connector plug from the controller The following figure shows the V positive terminal screw and the C negative terminal screw which secure the wires in the screw terminals and...

Page 7: ...es are connected to the device hazardous voltages can exist even when the equipment is turned off To avoid a shock hazard do not perform procedures involving cover or shield removal unless you are qua...

Page 8: ...dential areas To minimize the potential for the product to cause interference to radio and television reception or to experience unacceptable performance degradation install and use this product in st...

Page 9: ...e Caution To ensure the specified EMC performance product installation requires either special considerations or user installed add on devices See the product installation instructions for further inf...

Page 10: ...ors 4 System Gigabit Ethernet Port 5 RS 232 RS 485 Serial Port 6 System Power Connector 7 Gigabit Ethernet Ports with PoE 8 17 pin Digital I O Ports 9 Chassis Grounding Screw 10 Isolated Power Input C...

Page 11: ...positive lead of another power supply to the V2 terminal and the negative lead to the other C terminal Caution The C terminals are internally connected to each other d Assemble the rest of the plug s...

Page 12: ...rimary power source to the C terminal inside the power connector plug c Assemble the rest of the plug sleeve Go to ni com info and enter Info Code 317xIP67Connector for instructions 3 Install the isol...

Page 13: ...ment computer is powered on and connected to the network 2 Connect one end of an Ethernet cable to the network port on the device 3 Connect the free end of the cable to an Ethernet switch or other net...

Page 14: ...ck Finish 7 Install custom software You do not need to install custom software if you installed a recommended software set a Expand the IC 317x under Remote Systems b Click the Software item below the...

Page 15: ...I cannot recover lost system passwords If you forget the password you must contact NI and reformat the controller Configuring the IC 317x for Windows The Windows version of the IC 317x ships preloaded...

Page 16: ...ured on another network and then moved to the current network Reconfigure the IC 317x for the current network Note Connect a monitor and keyboard to the IC 317x and press Enter to view the current con...

Page 17: ...ed as nati vi server NATI VI Server Used by Vision Builder AI to configure a remote target If your firewall is controlled remotely or you are unsure about configuring the firewall contact your network...

Page 18: ...he following errors RT only The IC 317x has not booted into NI Linux Real Time The controller either booted into an unsupported operating system was interrupted during the boot process or detected an...

Page 19: ...o email and phone assistance from NI Application Engineers Visit ni com services for NI Factory Installation Services repairs extended warranty and other services Visit ni com register to register you...

Page 20: ...legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain relevant...

Reviews: