FP-TB-10 Operating Instructions
20
ni.com
Power Requirements
FP-TB-10 .......................................... 200 mW
Analog input modules
FP-AI-V50m, FP-AI-100m ........ 300 mW
FP-AI-C020, FP-AI-C420,
FP-AI-V1, FP-AI-V5,
FP-AI-V10, FP-AI-V5B,
FP-AI-V10B, FP-RTD-PT100,
FP-RTD-PT100-3,
FP-RTD-PT100-4,
FP-TC-J, FP-TC-K, FP-TC-T .... 375 mW max
Analog output modules
FP-AO-C020, FP-AO-C420,
FP-AO-C024............................... 1100 mW at max output
FP-AO-V5, FP-AO-V10,
FP-AO-V5B, FP-AO-V10B ....... 1100 mW at max output
Discrete input modules
FP-DI-DC, FP-DI-AC120,
FP-DI-AC240 ............................. 60 mW
Discrete output modules
FP-DO-DC60, FP-DO-DC200,
FP-DO-AC120,
FP-DO-AC240............................ 70 mW
Table 4.
Discrete Output Characteristics
FP-DO-
DC60
FP-DO-
DC200
FP-DO-
AC120
FP-DO-
AC240
Voltage
range
3 to 60 VDC
4 to 200 VDC
24 to 140 VAC
25 to 70 Hz
24 to 280 VAC
25 to 70 Hz
Voltage
drop
1.3 V at 0.75 A
1.75 V at 1.0 A
1.0 V at 0.5 A
1.0 V at 0.5 A
Current
rating
(per
channel)
0.75 A at 25 °C
0.50 A at 40 °C
0.30 A at 60 °C
0.40 A at 25 °C
0.20 A at 40 °C
0.10 A at 60 °C
0.75 A at 25 °C
0.50 A at 40 °C
0.30 A at 60 °C
0.75 A at 25 °C
0.50 A at 40 °C
0.30 A at 60 °C
Max
leakage
1.5 mA
0.01 mA
2 mA rms
4 mA rms
Max
output
delay
0.06 ms
0.75 ms
1/2 cycle
1/2 cycle