Isolation and Safety Guidelines

Caution

Read the following information before 

attempting to connect the [c]FP-AI-112 to any circuits 
that may contain hazardous voltages.

This section describes the isolation of the [c]FP-AI-112 and its 
compliance with international safety standards. The field wiring 
connections are isolated from the backplane and the inter-module 
communication bus. The isolation barriers in the module provide 
250 V

rms

 Installation Category II continuous isolation, verified by 

2,300 V

rms

, 1 minute dielectric withstand test. The [c]FP-AI-112 

provides 

double insulation

 (compliant with IEC 61010-1) for 

working voltages of 250 V

rms

1

. Safety standards (such as those 

published by UL and IEC) require the use of double insulation 
between hazardous voltages and any human-accessible parts or 
circuits.

Never

 try to use any isolation product between human-accessible 

parts (such as DIN rails or monitoring stations) and circuits that 
can be at hazardous potentials under normal conditions, unless the 
product is specifically designed for such an application, as is the 
[c]FP-AI-112.

Even though the [c]FP-AI-112 is designed to handle applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system:

There is no isolation between channels on the [c]FP-AI-112. 
If a hazardous voltage is present on any channel, all channels 
are considered hazardous. Make sure that all other devices and 
circuits connected to the module are properly insulated from 
human contact.

Do 

not

 share the external supply voltages (the V and C 

terminals) with other devices (including other FieldPoint 
devices), unless those devices are isolated from human contact.

For Compact FieldPoint, you 

must

 connect the protective earth 

(PE) ground terminal on the cFP-BP-

x

 backplane to the system 

safety ground. The backplane PE ground terminal has the 
following symbol stamped beside it: 

. Connect the 

backplane PE ground terminal to the system safety ground 

1  

Working voltage

 is defined as the signal voltage plus the common-mode voltage. 

Common-mode voltage

 is the voltage of the module with respect to ground.

Summary of Contents for FieldPoint FP-AI-112

Page 1: ...c FP AI 112 is a FieldPoint analog input module with the following features 16 analog voltage input channels Eight voltage input ranges 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V 16 bit resoluti...

Page 2: ...lace Figure 1 Installing the FP AI 112 Installing the cFP AI 112 The cFP AI 112 mounts on a Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP AI 112...

Page 3: ...ions for each of the 16 input channels and for an optional external power supply to power field devices The cFP CB x connector block provides the same connections Each channel has one input terminal V...

Page 4: ...ternal power supply and the V terminals The wiring diagrams in this document show fuses where appropriate Table 1 lists the terminal assignments for the signals associated with each channel The termin...

Page 5: ...tage source without an external power supply to one channel of the c FP AI 112 Figure 3 Voltage Source without External Power Supply Figure 4 shows how to connect a voltage source with an external pow...

Page 6: ...able for each channel The filters on the c FP AI 112 input channels are comb filters that provide notches of rejection at multiples or harmonics of a fundamental frequency You can select a fundamental...

Page 7: ...nd 5 V The update rate does not affect the rate at which the network module reads the data Set up your application so that the update rate is faster than the rate at which the network module polls the...

Page 8: ...uits that can be at hazardous potentials under normal conditions unless the product is specifically designed for such an application as is the c FP AI 112 Even though the c FP AI 112 is designed to ha...

Page 9: ...most cases Occasionally however a temporary conductivity caused by condensation must be expected Do not operate FieldPoint products in an explosive atmosphere or where there may be flammable gases or...

Page 10: ...at 500 Hz 60 mV 65 mV 3 V 25 V 300 mV 325 mV 16 V 100 V 1 V 1 04 V 40 V 300 V 5 V 5 2 V 190 V 1500 V 10 V 10 4 V 380 V 3000 V 0 1 V 0 1 04 V 20 V 300 V 0 5 V 0 5 2 V 95 V 1500 V 0 10 V 0 10 4 V 190 V...

Page 11: ...anted Accuracy at 15 to 35 C of Reading of Full Scale 60 mV 0 03 0 05 0 05 0 3 300 mV 0 03 0 015 0 05 0 1 1 V 0 03 0 008 0 05 0 04 5 V 0 03 0 005 0 05 0 02 10 V 0 03 0 005 0 05 0 02 0 1 V 0 03 0 005 0...

Page 12: ...ontinuous 250 Vrms Installation Category II Dielectric withstand 2 300 Vrms 1 minute Channel to channel isolation None Environmental FieldPoint modules are intended for indoor use only For outdoor use...

Page 13: ...s product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement control and laboratory use IEC 61010 1 EN 61010 1 UL 61010 1 CAN CSA C22 2...

Page 14: ...mpliance information To obtain the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column Mechanical Dimensio...

Page 15: ...ephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Brazil 55 11 3262 3599 Canada Calgary 403 274 9391...

Page 16: ...com are trademarks of National Instruments Corporation Product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments...

Reviews: