16
FP-1300 Quick Start Guide
ni.com
FP-1300 Specifications
Installation
Terminal wiring. . . . . . . . . . . . . . . . . . . 16–26 AWG copper conductor wire with 7 mm
(0.275 in.) strip length
Torque for screw terminals . . . . . . . . . . 0.5–0.6 N
·
m (4.4–5.3 lb
·
in.)
Network
Network interface. . . . . . . . . . . . . . . . . CAN
Compatibility . . . . . . . . . . . . . . . . . . . . ISO 11898
Communication rates . . . . . . . . . . . . . . Up to 1 Mbps
Maximum cabling distance
at 1 Mbps . . . . . . . . . . . . . . . . . . See ISO 11898-2
CAN bus power supply range . . . . . . . . 10 to 30 VDC
CAN bus power consumption
Typical. . . . . . . . . . . . . . . . . . . . . 0.72 W (30 mA at 24 VDC)
Maximum . . . . . . . . . . . . . . . . . . 3 W
CAN bus isolation. . . . . . . . . . . . . . . . . 250 V
rms
operational, 2,500 V
rms
breakdown
FieldPoint bank power supply range . . . 11 to 30 VDC
FieldPoint bank power consumption . . . 1 W + 1.1 (Total power consumption of all I/O modules)
Maximum terminal bases per bank. . . . 9
Maximum number of banks . . . . . . . . . Determined by network topology
Weight . . . . . . . . . . . . . . . . . . . . . . . . . 254 g (8.96 oz)
Isolation Voltage
For isolation voltage ratings, refer to the I/O module specifications and labels.
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, FieldPoint modules must
be mounted inside a sealed enclosure.
Operating temperature . . . . . . . . . . . . . –40 to 70 °C
Storage temperature. . . . . . . . . . . . . . . –55 to 85 °C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . 10 to 90% RH, noncondensing