15
FP-1300 Quick Start Guide
©
National Instruments Corporation
FP-1300 LED Indications
LED
POWER
MODULE STATUS
CAN STATUS
Solid Green
Power is applied
to the FP-1300.
The FP-1300
is operating
normally.
The CAN bus
is operating
normally.
Flashing Green
—
I/O data has
stopped because
the FP-1300 is
communicating
with the config-
uration utility.
—
Solid Red
—
The FP-1300 has
had an unrecov-
erable fault. Cycle
the power.
There is an error on
the CAN bus and
the CAN
communication has
stopped.
Flashing Red
—
The FP-1300 has
had a recoverable
fault. Try using the
FP-1300
configuration
utility to resolve
the issue.
There is a mes-
sage overflow on
the FP-1300 CAN
controller. In the
configuration
utility, select
Reset»Cycle
Power.
N
N
N
NO
O
O
OTT
T
TEE
E
E
Refer to the
FP-1300 User Manual for more information on the FP-1300 LED