![National Instruments CompactRIO cRIO-9263 Operating Instructions Manual Download Page 15](http://html1.mh-extra.com/html/national-instruments/compactrio-crio-9263/compactrio-crio-9263_operating-instructions-manual_709161015.webp)
©
National Instruments Corp.
15
cRIO-9263 Operating Instructions
limited-energy parts of equipment, circuits powered by regulated
low-voltage sources, and electronics.
Isolation
Channel-to-channel .................... No isolation between
channels
Channel-to-earth ground
Withstand ............................. 2,300 V
rms
, 1 minute max
Continuous ........................... 250 V
rms
,
Installation Category II
Installation Category II is for measurements performed on circuits
directly connected to the electrical distribution system. This
category refers to local-level electrical distribution, such as that
provided by a standard wall outlet (for example, 115 V for U.S. or
230 V for Europe).