cFP-21xx Quick Start Guide

 

Caution

If you are using UL Recognized I\O modules with the Compact 

FieldPoint system, you must install the entire system in a suitably rated, 
UL Listed NEMA or IP enclosure.

Cabling Clearance

Cooling Outline 51 mm (2 in.) All Around

4 slots = 246 mm (9.68 in.)
8 slots = 441 mm (17.4 in.)

127 mm

(5.00 in.)

Min.

 165 mm

(6.50 in.)

Cabling

Clearance

4 slots = 246 mm (9.68 in.)
8 slots = 441 mm (17.4 in.)

Cooling Outline 51 mm (2 in.)

Cooling Outline 51 mm (2 in.)

Min.

 182 mm (7.18 in.)

106 mm (4.18 in.)

Summary of Contents for Compact FieldPoint Mounting Accessories...

Page 1: ...ontroller Mounting hardware DIN rail panel mount or rack mount accessory I O module s cFP BP x backplane connector blocks cables 11 30 VDC power supply Accessories Ethernet cable number 2 Phillips scr...

Page 2: ...PE ground terminal on the cFP BP x backplane to the system safety ground The backplane PE ground terminal has the following symbol stamped beside it Connect the backplane PE ground terminal to the sys...

Page 3: ...tall the entire system in a suitably rated UL Listed NEMA or IP enclosure Cabling Clearance Cooling Outline 51 mm 2 in All Around 4 slots 246 mm 9 68 in 8 slots 441 mm 17 4 in 127 mm 5 00 in Min 165 m...

Page 4: ...commends that you use one of the mounting systems described in this document If you decide to use a custom mounting solution make sure that the screws you use are short enough to fit in the holes in t...

Page 5: ...ten the panel mount plates to the back of the cFP BP x using a number 2 Phillips screwdriver and the 8 32 5 16 in countersink screws shipped with the kit Caution Do not use screws longer than 5 16 in...

Page 6: ...art Guide 6 ni com 104 78 mm 4 1 in 63 50 mm 2 5 in 22 23 mm 0 9 in 33 15 mm 1 3 in 129 54 mm 5 1 in 311 40 mm 12 3 in 387 60 mm 15 3 in 407 80 mm 16 1 in 127 00 mm 5 0 in 440 94 mm 17 4 in 260 mm 10...

Page 7: ...ane on a DIN Rail NI recommends DIN rail mounting for the cFP BP 4 only Use panel mounting or rack mounting for the cFP BP 8 The DIN rail mounting kit is NI part number 778614 01 1 Fasten the DIN rail...

Page 8: ...edge of the DIN rail into the deeper opening of the DIN rail clip 3 Press down firmly on the backplane to compress the spring until the clip locks in place on the DIN rail 4 Connect the PE ground ter...

Page 9: ...ck Start Guide Mounting the Backplane in a Standard 19 in Rack 1 Fasten the rack mount bracket to the back of the cFP BP x using the captive screws on the bracket 2 Bolt the rack mount accessory to a...

Page 10: ...P 21xx Quick Start Guide 10 ni com 3 Connect the PE ground terminal on the cFP BP x to safety ground Caution Disconnect power before removing the backplane from the DIN rail NA TIO NA L INS TR UM EN T...

Page 11: ...p with the NI logo at the top and align the captive screws on the controller with the holes on the backplane 3 Seat the card edge at the back of the controller in the card edge connector on the backpl...

Page 12: ...O module with the holes on the backplane 2 Press firmly to seat the I O module on the backplane 3 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive...

Page 13: ...accessories while power is applied to them 1 Wire field devices as described in the I O module and connector block operating instructions Caution Hazardousvoltage wiring should be performed by qualif...

Page 14: ...Caution To prevent data loss and to maintain the integrity of your Ethernet installation do not use a cable longer than 100 m If you are using a 100 Mbps Ethernet network National Instruments recommen...

Page 15: ...using a backup power supply connect the positive lead to V2 and the negative lead to one of the C terminals The cFP 21xx uses the power supply with the higher voltage level V2 is isolated from the oth...

Page 16: ...er about three seconds the STATUS LED begins flashing steadily The cFP 21xx is ready to be configured If you have already assigned an IP address to the cFP 21xx the STATUS LED turns off The total boot...

Page 17: ...the National Instruments FieldPoint Software CD into the CD ROM drive on your computer 4 Follow the onscreen instructions to complete the installation Note If the setup does not launch automatically s...

Page 18: ...ed in the installation instructions You must connect the protective earth PE ground terminal on the cFP 1808 to the system safety ground The backplane PE ground terminal has the following symbol stamp...

Page 19: ...u must insulate signal connections for the maximum voltage for which the Compact FieldPoint product is rated Do not exceed the maximum ratings for the product Do not install wiring while the product i...

Page 20: ...tlet for example 115 V for U S or 230 V for Europe Examples of Measurement Category II are measurements performed on household appliances portable tools and similar products Measurement Category III i...

Page 21: ...unless power has been switched off or the area is known to be nonhazardous Equipment must be used within its electrical and environmental ratings Refer to the Specifications section Refer to the prod...

Page 22: ...r information about the memory used by the LabVIEW Real Time Module and the operating system go to ni com info and enter rdfpec Serial Ports cFP 2100 One RS 232 serial port cFP 2110 Two RS 232 serial...

Page 23: ...und Continuous 100 Vrms Dielectric withstand 740 Vrms verified by 5 s test Power Requirement Power supply range 11 30 VDC Recommended power supply cFP BP 4 system 15 W cFP BP 8 system 20 W Power consu...

Page 24: ...he isolation voltage ratings must be lowered Pollution Degree 2 Shock and Vibration Operating vibration Random IEC 60068 2 64 10 500 Hz 5 grms Sinusoidal IEC 60068 2 6 10 500 Hz 5 g Operating shock IE...

Page 25: ...andards for electrical equipment for measurement control and laboratory use EN 61326 IEC 61326 Class A emissions Basic immunity EN 55011 CISPR 11 Group 1 Class A emissions AS NZS CISPR 11 Group 1 Clas...

Page 26: ...fication column Cabling The table below shows the standard Ethernet cable wiring connections for both normal and crossover cables Ethernet Cable Connector Pinouts Pin Connector 1 Connector 2 Normal Co...

Page 27: ...ted States contact your local branch office Australia 1800 300 800 Austria 43 662 457990 0 Belgium 32 0 2 757 0020 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 5050 9800 Czech Republic 420 2...

Page 28: ...n on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents co...