Installation Guide for NHPA Split-System Heat Pumps
16
SPECIFICATIONS CHART - 3000 SERIES
MODEL NO.
NHPA-418
NHPA-424
DIMENSIONS
24 1/8”
32”
18 1/2”
3/8”
3/4”
24 1/8”
32”
18 1/2”
3/8”
3/4”
Width
Height
Length
Liquid Valve
Vapor Valve
NOMINAL COOLING
CAPACITY
18,200
22,200
NOMINAL HEATING
CAPACITY
16,100
19,000
ELECTRICAL
208/230
60
1
12
13.78
20
208/230
60
1
10
16.8
25
Volts
Hertz
Phase
Min. AWG Wire
Min. Cir. Ampacity
Max. Fuse
COMPRESSOR
9.0
56.3
10.9
62.9
RLA (Amps)
LRA (Amps)
FAN MOTOR
0.25
1500
1.4
0.25
1500
1.4
HP
RPM
Amps (Full Load)
COIL
3.77
16
3.77
16
Face Area
FPI
Service
Clearance 30
"
DIMENSIONAL DRAWING FOR 3000 SERIES
5 5/8"
3 3/4"
23 7/8"
1 5/16"
3 1/16"
8 9/16"
12 7/8"
17 1/4"
21 5/8"
1"
1 1/8"
7/8" (2)
1 1/2" (2)
1 1/16"
8 1/2"
1 1/2"
32"
18 7/16"
3 3/8"
1 1/8"
1"
1 5/16"
1 9/16"
3000 SERIES HEAT PUMP