background image

27

Installation Guide for Comfort Pack (CPG) Units

Figure 6B

Secondary Air Shield Assembly 

w/ End Cap Removed

Upper Burner Brackets

Burner Assembly

Retaining Track

Lower Burner Bracket

(one on each end) - 

Place in the retaining track on the 

secondary air shield assembly.

Burner Orifice

Burner orifice only needs to be replaced when a change in 

gas is made. When ordering a replacement orifice, give BTUH 

content and specific gravity of gas, as well as the model and 

serial number of the unit. To prevent dropping the orifice into 

the burner housing, block the venturi with something the size of 

a credit card when removing the burner orifice. Be careful not to 

damage the venturi tube and/or the bracket.

Ignition System

Igniter

 - Refer to Figure 6A and locate the igniter. Disconnect 

the wire; remove the screw and the igniter. Clean the igniter 

assembly with an emery cloth. Spark gap must be maintained to 

1/8" (See Figure 7) below.

Flame Sensor

 - Refer to Figure 6A and locate the flame sensor. 

Disconnect the wire; remove the screw and the flame sensor. 

Clean with an emery cloth.

Figure 7

DUE TO HIGH VOLTAGE ON THE SPARk WIRE 

AND ELECTRODE, DO NOT TOUCH WHEN 

ENERGIzED. SEE HAzARD LEVELS, PAGE 5. 

!

CAUTIoN

DSI Integrated Control Module

 - The module monitors the 

operation of the heater including ignition. The only replaceable 

component is the 3 amp fuse. If the fuse is blown, the problem is 

most likely an external overload. Correct the problem and replace 

the fuse. Do not attempt to disassemble the control module. 

However, each heating season check the lead wires for insulation 

deterioration and good connections. 

Proper operation of the direct spark ignition system requires 

a minimum flame signal of 1.0 microamps as measured by a 

microammeter. 

For further information and check out procedure on the direct 

spark ignition system, refer to the circuit board manufacturer’s 

instructions supplied with the heater.

Venter Motor and Wheel Assembly

Remove dirt and grease from the motor casing. Venter motor 

bearings are permanently lubricated. The DSI Integrated Control 

Module controls and monitors operation of the venter motor. If 

the contacts fail to close the venter motor will not run. If the 

contacts fail to open, the venter motor will not shut off, preventing 

the combustion air pressure switch from opening.

Follow these instructions for replacement of the venter motor 

and wheel assembly. Keep all hardware removed to be used in 

reassembling and installing the replacement parts. 

1. Turn off the gas and disconnect the electric power. 

2. Open the burner/control compartment access panel. 

3.  Disconnect the three venter motor wires at their terminal block 

connections. 

4.  Holding the motor, remove the three screws that attach the 

venter motor mounting plate to the venter housing. Remove 

the motor and wheel assembly from the heater. 

5.  Re-assemble with the replacement venter motor and wheel 

assembly. 

6. Follow the wiring diagram to connect the venter wires.

7.  Restore power to the heater and turn on the gas. Light, 

following the instructions plate. Check for proper operation. 

Replace the access panel.

Summary of Contents for CPG41228-U

Page 1: ...nance To ensure long life and satisfactory performance a heater that is operated under normal conditions should be inspected and cleaned at the start of each heating season If the heater is operating...

Page 2: ...h end Loosen burner assembly by removing only the two screws indicated Burner Assembly Secondary Air Shield End Cap Remove secondary air shield end cap by removing four screws indicated Remove screw o...

Page 3: ...he fuse Do not attempt to disassemble the control module However each heating season check the lead wires for insulation deterioration and good connections Proper operation of the direct spark ignitio...

Page 4: ...pect the burner control compartment for signs of excessive heat and burned wiring If the compartment appears normal reset by depressing the red button on the switch 15 to 20 minutes are required for t...

Page 5: ...tions to Slide Out the Furnace After removing front panels 1 Remove the 4 screws indicated at the right Gas Line Power Cord 2 Remove the patch plate Gas Line Power Cord Front Furnace Baffle 3 Remove 2...

Page 6: ...insulation when pulling the heat exchanger furnace assembly forward 4 Unplug 2 molex plugs before sliding out the heat exchanger furnace assembly Lift Pull Forward Power Cord 6 With your right hand re...

Page 7: ...U 2 5 27 000 9 2 64 000 51 200 360 Electrical Data Models Voltage Compressor Outdoor Fan Motor Indoor Blower Motor Total Amps Minimum Circuit Amps Maximum Overcurrent Protector RLA LRA HP FLA LRA HP...

Page 8: ...F Nominal 45 F to 60 F 38MBTU 52 5 F Nominal 45 F to 60 F 51MBTU 55 F Nominal 45 F to 65 F 64MBTU 67 F Nominal 60 F to 80 F In order to calculate CFM use the formula CFM BTU Output 1 08 x Temp Rise S...

Page 9: ...0 59 3 328 63 2 Comfort Pack Gas CFM and Temperature Rise 38 000 BTU Input UNIT SIZE COLOR SPEED 1 w c TD 2 w c TD 3 w c TD 4 w c TD 5 w c TD CPG41238 Red 1 780 36 1 770 36 6 760 37 0 725 38 8 680 41...

Page 10: ...nge 5 410 92 1 320 118 1 225 167 9 Comfort Pack Gas CFM and Temperature Rise 64 000 BTU Input UNIT SIZE COLOR SPEED 1 w c TD 2 w c TD 3 w c TD 4 w c TD 5 w c TD CPG41864 Red 1 780 60 8 770 61 6 760 62...

Page 11: ...range 5 415 325 225 X X CPG418 Red 1 780 770 760 725 680 Yellow 2 715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 550 500 430 340 240 Orange 5 415 325 225 X X CPG424 Red 1 850 833 815 803 790 Y...

Page 12: ...36 Installation Guide for Comfort Pack CPG Units...

Page 13: ...37 Installation Guide for Comfort Pack CPG Units REVISION 3...

Page 14: ...38 Installation Guide for Comfort Pack CPG Units...

Page 15: ...Set thermostat at lowest setting 2 Turn on manual gas valve 3 Turn on power to unit 4 Set thermostat at desired setting 5 Thermostat calls for heat energizing the venter motor 6 Venter pressure switc...

Page 16: ...ain power Replace combustion air proving switch 6 7 a If 24 volt is measured at the valve connections and valve remains closes replace valve b Check and tighten all wiring connections 8 a Check and ti...

Page 17: ...678 All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All All 28 Mbh 38 Mbh 51 Mbh 64 Mbh All All All All 38 Mbh 38 Mbh 51 Mbh...

Page 18: ...or Coil Outdoor Coil Compressor Low Pressure Switch High Pressure Switch Dual Run Capacitor 40 5 TXV 14256641 14208304 14208383 14210248 14265026 14265029 14225372 14275103 30 30 30 30 30 30 30 30 CHA...

Page 19: ...ding between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding OHM...

Page 20: ...the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular purp...

Page 21: ...shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to Nati...

Reviews: