background image

Figure 4

Figure 5

Figure 7

 

X mm

Unprotected ceiling 

1200

Single-layer, 
light protection  

900

Figure 6

4. If the wall is a masonry wall, a 50 mm 
ventilation gap between the vertical sides of 
the sauna woodburning stove and the wall is 
sufficient. (Figure 4)

Measurement A is applied to wooden surfaces 
in accordance with the thermal protection 
method applied:

- no thermal protection: 500 mm
- single-layer, light thermal protection: 250 mm
- double, light thermal protection: 125 mm

5. 55 mm thick masonry which is open at 
the edges and detached from the protected 
surface by at least 30 mm also constitutes 
single-layer, light thermal protection. Double 
light thermal protection constitutes 110 mm 
thick masonry detached from the protected 
surface as above. (Figure 5)

Thermal protection of the ceiling:

When the distance from the upper surface 
of the sauna woodburning stove is at least 
1,200 mm no ceiling protection is needed. If 
the safety distance is less than 1,200 mm, the 
thermal protection method for the ceiling is 
chosen from sections 1-3. (Figure 6)

Thermal protection of the floor in front of the 
sauna woodburning stove:

A floor consisting of combustible material must 
be protected with a metal sheet extending 100 
mm to each side of the woodburning stove fire 
door and 400 mm to its front. (Figure 7)

Reviews: