Operation manual V 3.2 for AcmeG series 

- 19 - 

4. Charging Request 

4.1

 Equalization Charging 

Equalization charging should be carried out in the following situation: 

a. There are more than two batteries which voltage is under 13.0V in one group. 

b. More than three months after floating operation. 

Equalization charging is recommended as follows:   

Charge  the  battery  group  with  constant  current  not  exceeding  0.1C

10

A  till  the 

average  voltage  increases  to  14.1V/block(25º

C)

then  change  into  constant 

voltage  of  14.1V/block  charging.  The  equalization  charging  time  should  be  24 

hours.   

4.2

 Battery Charging 

Battery Charging should be carried out in the following situation: 

a.

 

The batteries should be recharged in time after discharge. 

b.

 

After battery system is installed. 

c.

 

Battery  storage  period  exceeding  three  months  or  open  circuit  voltage  lower 

than 12.6V/block. 

Battery charging is recommended as follows:   

The batteries should first be charged on the constant current of 0.10C

10

A till the 

average  voltage  of  the  batteries  increases  to  14.1V,  then  the  batteries  should  be 

charged with constant voltage of 14.1V till the charging has completed. 

 

On some occasions, the batteries have to be fully charged immediately, then fast 

charging  could  be  adopted.  The  value  of  limit  current  should  not  be  larger  than 

0.2C

10

A, and the charge voltage should be 14.1V/block(25º

C). 

 

We  can  determine  if  the  batteries  are  fully  charged  by  one  of  following  two 

conditions: 

a. After charging 18

24hours. The charging time will be lesser if it is not deep 

discharged.  For  example  at  20%  DOD  (refer  to  Table  2-1  for  the  Depth  of 

Discharge vs Charging Time), the charging time can be shorten to 10 hours. 

b.  Under  the  condition  of  constant  voltage,  the  value  of  charge  current  has  no 

variation for continuously three hours. 

 

5. Storage 

All  gel  batteries  experience  self-discharge  in  open  circuit.  The  result  is  that  the 

voltage of open circuit is decreased, and the capacity also decreases. Please note the 

Summary of Contents for ACMEG AG12V100A

Page 1: ...Polymer Gel Standby Battery Front Access Design OPERATION MANUAL Version 3 2 NARADA POWER SOURCE CO LTD Website www naradapower com...

Page 2: ...al Characteristics 7 1 Charge Performance Curve 7 2 Internal Resistance and Short Circuit Current 7 3 Discharge data with constant current constant power 9 Chapter Three Operation and Maintenance 15 1...

Page 3: ...ter Please check the local regulations on the correct way of dealing with battery disposal or send the battery to the authorized service center for replacement Battery replacement should be operated o...

Page 4: ...ion design with excellent heat dispersing capability Both positive and negative posts are along one side of the battery giving ease of monitoring and maintenance Flexible connectors that can fit accor...

Page 5: ...0 395 108 287 31 0 AG12V125F 12 125 558 125 270 46 0 AG12V150S 12 150 550 125 283 48 0 AG12V155F 12 155 558 125 270 52 5 AG12V170S 12 170 550 125 283 51 5 AG12V180 12 180 558 125 316 60 5 AG12V190 12...

Page 6: ...Operation manual V3 2 for AcmeG series 6 AG12V180 AG12V190 AG12V200 AG12V100S AG12V150S AG12V170S AG12V190S 558 21 99 316 12 45 125 4 93...

Page 7: ...C 2 Internal Resistance and Short Circuit Current The internal resistance of the battery is a dynamic nonlinear parameter that varies continuously with the temperature and discharge state The internal...

Page 8: ...ent A AG12V50F 8 94 1500 AG12V85F 6 52 1897 AG12V100F 6 36 1989 AG12V100S 5 52 2318 AG12V100A 6 59 1909 AG12V125F 5 76 2226 AG12V150S 5 19 2450 AG12V155F 4 30 2814 AG12V170S 4 65 2758 AG12V180 3 85 32...

Page 9: ...5 97 4 91 4 17 2 71 2 28 AG12V85F 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h 1 60V cell 305 6 164 2 99 9 72 2 58 4 33 5 24 3 19 1 16 1 13 8 10 6 8 75 7 40 4 64 3 87 1 67V cell 287 0 1...

Page 10: ...1 9 128 2 94 6 76 1 43 1 31 4 25 8 22 6 19 4 15 2 12 5 10 76 6 73 5 64 1 80V cell 314 2 188 3 122 5 90 7 74 1 42 8 31 2 25 7 22 1 19 1 15 1 12 4 10 67 6 66 5 63 1 83V cell 299 4 172 4 120 2 87 7 70 8...

Page 11: ...32 8 27 3 22 2 18 0 15 5 9 52 8 04 1 85V cell 337 7 240 2 170 9 131 7 113 6 66 0 48 2 39 0 32 3 27 0 21 9 17 9 15 4 9 52 7 99 AG12V100A 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h 1 6...

Page 12: ...9 286 4 178 9 134 4 109 3 63 2 46 2 36 6 30 8 26 6 20 6 16 9 14 24 9 15 7 64 1 67V cell 492 4 281 3 177 2 133 5 108 4 63 1 45 6 36 5 30 8 26 4 20 5 16 8 14 24 9 07 7 64 1 70V cell 489 8 278 0 177 2 13...

Page 13: ...534 6 322 1 229 4 169 5 137 5 82 5 58 9 49 4 42 7 36 9 29 3 24 2 20 47 13 60 11 34 1 85V cell 499 6 314 2 212 5 162 8 133 0 79 8 57 3 48 8 41 7 36 2 28 4 23 9 20 21 13 35 11 25 AG12V155F 5min 15min 3...

Page 14: ...8 38 8 33 4 19 7 17 2 AG12V100A 5min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 12h 20h 24h 1 60V cell 601 0 339 3 211 9 159 2 129 5 74 3 54 3 43 0 36 3 31 3 24 2 19 92 16 73 10 76 8 98 1 67V cell 578...

Page 15: ...h 2 2 Factors that influence the Actual Capacity Actual capacity is mainly related to the battery s construction manufacturing process and operational environment During operation the factors that inf...

Page 16: ...data such as capacity life and floating voltage are measured with temperature between 20 C 25 C as a standard The capacity of the battery will decrease with lower temperature as shown in Fig 3 1 belo...

Page 17: ...current will get larger and increase the grid eroding speed thus reducing the service life of the battery When the floating voltage is too low the battery will not be able to maintain its fully charg...

Page 18: ...k 5 2 45 14 7 10 2 425 14 55 15 2 40 14 4 20 2 375 14 25 25 2 35 13 95 30 2 325 14 25 35 2 30 14 10 40 2 275 13 65 Note If ambient temperature below 5 or above 40 temperature compensate is no longer g...

Page 19: ...mended as follows The batteries should first be charged on the constant current of 0 10C10A till the average voltage of the batteries increases to 14 1V then the batteries should be charged with const...

Page 20: ...by self discharge the batteries should be recharged as storage period shown in following table The equalization charge method should be adopted Storage temperature Max Storage period Above 30 3 months...

Page 21: ...e battery If there is more than one battery with voltage of less than 13 1V after temperature adjustment the batteries have to go through equalization charged If the problem persists after adopting th...

Page 22: ...ome cases 9 6V The battery will stop discharging when it reaches a certain voltage If the end voltage is too low it will be difficult to recharge the battery and decrease the charging efficiency thus...

Page 23: ...nnex 1 VRLA Battery Regular Maintenance Record Type Place Status Number of battery Total Voltage V Current A Temperature No Voltage V No Voltage V 1 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21 10 22 11...

Page 24: ...Operation manual V 3 2 for AcmeG series 24...

Reviews: