6V&12V Serials

15

16

The 6V & 12V batteries require ventilation, drying, and avoid direct sunlight. The batteries experience 
self-discharge in open circuit state, the result is that open circuit voltage decreases, and the capacity 
also  decreases.  The  self-discharge  rate  is  related  with  ambient  temperature.  The  self-discharge 
rate is smaller when the ambient temperature is lower, otherwise is larger. If the open circuit voltage 
is lower than 2.10V/cell, or storage period reach 6 months shown in following table, the batteries 
should be recharged to avoid damage caused by self-discharge.

Storage

It’s suggested to record the storage time in the periodic maintenance record and record the time when 

another necessary supplemental charge should be made. The quality certificates and packages of 

6V & 12V series batteries record the latest charge time of the batteries, next charge time can be 
calculated according to this charge time.

Above 30°C

Below 30°C

3 months

6 months

Storage temperature

Max. Storage period

Proper maintenance will prolong the life of a battery and will aid in assuring that it is capable of 
satisfying its design requirements. A good battery maintenance program will serve as a valuable aid 
in determining the need for battery replacement. The users must consider their particular application 
and reliability needs if maintenance procedures, other than those recommended in this document, 
are used. Battery maintenance should be performed by personnel knowledgeable of batteries and 
the safety precautions involved.

General

Inspection

Maintenance
Chapter 

Four/04

Monthly Maintenance

■ 

Keep the battery-room clean.

■ 

Measure and record the ambient temperature of the battery-room.

■ 

Check each battery’s cleanness; check damage and overheating trace of the terminal, container 

   and lid.

■ 

Measure and record the total voltage and floating current of the battery system.

Yearly Maintenance

■ 

Repeat quarterly maintenance and inspection.

■ 

Check whether connectors are loose or not every year.

■ 

Make a discharge test to check with exact load every year, discharging 30-40% of rated capacity. 

Make an 80%DOD capacity test every year after three years’ operation.

Special inspections

If the battery has experienced an abnormal condition (such as a severe discharge, overcharge, or 
extreme high ambient temperature), an inspection should be made to assure that the battery has not 
been damaged. Include the requirements for the yearly inspection.

Quarterly Maintenance

■ 

Repeat monthly inspection.

■ 

Measure and record floating voltage of every on-line battery. If more than two cells’ voltage is 

  less than 2.18Vpc after temperature compensation, the batteries need to be equalization charged.

Summary of Contents for 6V Series

Page 1: ...VALVE REGULATED SEALED LEAD ACID BATTERY NARADA POWER SOURCE CO LTD Email intl narada biz Website en naradapower com OPERATION MANUAL Version V1 0 6V 12V Series ...

Page 2: ...0 Product Features Main application Working principle Discharge performance Charge performance General Inspection Corrective actions Annex1 Annex2 Parameter settings Operation condition Capacity and influence factors Lifetime and influence factors Storage 4 4 5 6 6 16 16 17 18 19 10 11 12 14 15 01 02 notes two one Four three ...

Page 3: ...uthorized by the manufacturer To replace the battery or maintenance equipment please call the after sales service hotline for information of the nearest service center Please check the local regulations on the correct way of battery disposal or send the battery to the authorized service center for replacement Battery replacement should be operated or supervised by engineers who are experienced and...

Page 4: ...aled structure Figure 2 2 is the battery charging characteristics curve of 6V 12V series battery with constant voltage and limited current 0 1C10 A current voltage limit 2 35V cell fully discharged battery charges for 24 hours and the charge power up to 105 The dotted line is the 50 charge curve Pb PbO2 2H2SO4 2PbSO4 2H2O Discharge Charge 2Pb O2 2PbO PbO H2SO4 PbSO4 H2O Discharge performance techn...

Page 5: ...ch series of batteries is shown in Table 2 2 Similarly the average charging voltage needs to be adjusted with the ambient temperature and the temperature compensation coefficient of the battery charging voltage is 5 mV C cell Table 2 1 Floating Voltage of Each Series 25 C Table 2 2 Equalization charging Voltage of Each Series 25 C Table 2 3 Temperature and voltage setting MP MPG Acme AcmeG GP GPG ...

Page 6: ...e batteries will be rejected if the situation is serious Battery recharge method Step 1 Connect the batteries in series and ensure that the bolts and screws are fastened Step 2 Connect the positive and negative poles of the battery to the positive and negative poles of the charging device Step 3 Turn on the charging power supply set the charging current limit value and charging voltage value accor...

Page 7: ... 25 C 15 C 25 C 15 C 35 C 15 C 35 C 15 C 35 C Operation status Operation status Optimum temperature Optimum temperature Temperature range Temperature range Capacity and influence factors The capacity can be expressed in Rated Capacity or Actual Capacity The Actual Capacity is the product of discharge current A and discharge time h The usual unit of capacity is ampere hour shortened as Ah The Influ...

Page 8: ...The capacity will decrease under lower temperature as Fig 3 1 Battery life is the battery operation life it is influenced by many factors The factors are charge mode discharge mode ambient Temperature and so on Lifetime and influence factors Floating voltage Equalization voltage 0 25C10 A The Equalization charge time is 24h 1 80V cell per block at 10h rate 15 25 C 1 The charge voltage is too high ...

Page 9: ...or battery replacement The users must consider their particular application and reliability needs if maintenance procedures other than those recommended in this document are used Battery maintenance should be performed by personnel knowledgeable of batteries and the safety precautions involved General Inspection Maintenance Chapter Four 04 Monthly Maintenance Keep the battery room clean Measure an...

Page 10: ...igated Routine The following items indicate conditions that if allowed to persist for extended periods can reduce battery life They do not necessarily indicate a loss of capacity Therefore the corrective action may be accomplished before the next quarterly inspection provided that the battery condition is monitored at regular intervals a If any cell unit voltage is below its respective critical mi...

Page 11: ...ing VRLA batteries Digital multimeter Wrenches insulated Adjustable wrench insulated Torque wrench Rubber gloves Full set of masks Plastic apron Portable eyedrops Fire extinguishers C grade The following equipment is optional according to the type of maintenance Resistance tester Charger and discharger special for storage battery portable ...

Page 12: ...6V 12V Serials ...

Page 13: ...1 56975955 Website en naradapower com E mail intl narada biz Block 9 Khaki Bukit Road 1 02 10 Eunos Technolink Singapore 415938 Tel 65 6848 1191 Fax 65 6749 3498 Website www narada ap com Email sales narada ap com Spectrum House Dunstable Road Redbourn St Albans Herts Al3 7PR Tel 44 0 845 612 2031 Fax 44 0 845 612 2031 E mail sales naradaeurope com After sale Services ...

Reviews: