8
Fig.2-1 Discharge characteristic curve
2. Charge Curve
Fig.2-2 Recharge characteristics of 12REXC battery with current of 0.1C
10
A and limit
voltage of 2.30V/cell (25
℃
). The 100% DOD battery can be recharged 105% of
capacity after charging for 24 hours. Imaginary line is the recharge curve of 50%DOD.
Charge curve 25
(
℃
)
14.1
13.5
12.9
12.3
100% discharge
50% discharge
0
24
4
16
12
20
8
C
ha
rg
e
ca
pa
ci
ty
(%
)
C
ha
rg
e
cu
rr
en
t(C
A)
C
ha
rg
e
vo
lta
ge
(V
)
Charge current
Charge capacity
Charge voltage
Time ( h )
Fig.2-2 Charge characteristic curve
3. Internal Resistance and Short-Circuit Current
The internal resistance of the battery is a dynamic nonlinear parameter that is
continuously changed along with the temperature and discharge state. The internal
resistance is the lowest when battery is fully charged. The table 2-3 shows the internal
resistance and short circuit current of 12REXC battery in fully charged state according
to the IEC60896 standard. Pay attention to the battery to short-circuit causes the
battery voltage to reduce to 0V, and will cause the battery internal component
damaged.
Table 2-3 Referenced Internal Resistance and Short Current
Battery Type
Internal Resistance
(mΩ)
Short Current (A)
12REXC70
9.79
1291
12REXC200
3.83
3274
6REXC300
1.35
4619