Adjust the pilot screw to provide properly sized flame. Turn in a clockwise
direction to reduce the gas flow.
Inlet pressure can be checked by turning screw (A) counter-clockwise
until loosened and then placing pressure gauge tubing over the test
point. Gauge should read 7” (minimum 4.5”) water column for natural
gas or 13” (11” minimum) water column for propane. Check that main
burner is operating on “HI”.
Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5” water column for natural gas or 10” water
column for propane. Check that main burner is operating on “HI”.
AFTER TAKING PRESSURE READINGS, TIGHTEN SCREWS
FIRMLY TO SEAL. DO NOT OVER TORQUE.
LEAK TEST.
ADJUSTMENTS
PRESSURE ADJUSTMENT
PILOT
BURNER
FLAME MUST ENVELOP
UPPER 3/8” TO 1/2” OF
FLAME SENSOR
FLAME
SENSOR
ELECTRODE
It is important to periodically perform a visual check of the pilot and burner flames.
Compare them to the illustrations below.
VENTURI ADJUSTMENT
Air shutter adjustment must be done by a qualified
installer!
Air shutter opening has been factory set according to the chart
below:
Closing the air shutter will cause a more yellow flame, but can lead
to carboning. Opening the air shutter will cause a more blue flame,
but can cause flame lifting from the burner ports. The flame may
not appear yellow immediately; allow 15 to 30 minutes for the final
flame colour to be established.
Adjustment is required depending on fuel type, vent configuration
and altitude.
VENTURI
AIR SHUTTER
OPENING
ORIFICE
VENTURI ADJUSTMENT CHART
FUEL
BURNER
NG
1/8" (3.2mm)
P
3/16" (4.7mm)
FLAME CHARACTERISTICS
NOTE: If the intent is to use a portable propane bottle as the source of fuel for this appliance,
the bottle must be supported. A support (W655-0171) is available by your local Napoleon or
Continental dealer / distributor.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada • 1(866)820-8686
• www.napoleonfireplaces.com
W415-1832 / A / 04.13.18
MAXIMUM INPUT RATINGS
NG
P
40,000 BTU/h
40,000 BTU/h
Birch Log Set
BLKO36
Oak Log Set
OLKO36
:ROI6WHHO/WG1DSROHRQ5G%DUULH21/0<&DQDGD ID[ ZZZQDSROHRQILUHSODFHVFRP
ADJUSTMENTS
VENTURI ADJUSTMENT
Air shutter adjustment must be done by a quali
fi
ed
installer!
All models have air shutters that have been factory set open
according to the chart below:
Adjustment may be required depending on fuel type, vent
con
fi
guration and altitude.
Closing the air shutter will cause a more yellow
fl
ame, but
can lead to carboning. Opening the air shutter will cause a
more blue
fl
ame, but can cause
fl
ame lifting from the burner
ports. The
fl
ame may not appear yellow immediately; allow
15 to 30 minutes for the
fi
nal
fl
ame colour to be established.
NG
3
/
16
”
LP
1
/
4
”
Adjust the pilot screw to provide properly sized
fl
ame. Turn
in a clockwise direction to reduce gas
fl
ow.
Inlet pressure can be checked by turning screw (A) counter-
clockwise until loosened and then placing pressure gauge
tubing over the test point. Gauge should read 7” (minimum 4.5”)
water column for natural gas or 13” (11” minimum) water column
for propane. Check that main burner is operating on “HI”.
Outlet pressure can be checked the same as above using
screw (B). Gauge should read 3.5” water column for natural
gas or 10” water column for propane. Check that main burner
is operating on “HI”.
AFTER TAKING PRESSURE READINGS, TIGHTEN
SCREWS FIRMLY TO SEAL. DO NOT OVERTORQUE.
LEAK TEST
3/8” - 1/2”
FLAME MUST
ENVELOPE UPPER
3/8" TO 1/2" OF
THERMOCOUPLE &
THERMOPILE
It is important to
periodically perform
a visual check of the
pilot and burner
fl
ames.
Compare them to the
illustrations provided.
Maximum Input Ratings
NG
40,000 BTU/hr
LP
40,000 BTU/hr
PILOT
BURNER
THERMOCOUPLE
THERMOPILE
PILOT BURNER ADJUSTMENT
VENTURI
AIR SHUTTER
OPENING
ORIFICE
PIL
O
T
NOTE: If the intent is to use a portable
propane bottle as the source of fuel, the
bottle must be supported.
A support (W655-0171) is available by
your Napoleon or Continental dealer.
A
B