Air Handlers
There are LED indicators on the main board of the indoor unit, which are used to
display the operating status and malfunction information of the unit.
LED indicator
Color
Function
Power Indicator
Red
Indoor unit main board is powered on,
Power Indicator is on.
Running Indicator
Green
After detecting the indoor fan turn-on
signal, the running indicator light is on,
when detecting the indoor fan turning-off
signal, the running indicator light is off.
When detecting a system failure, the
running indicator light flashes.
Different running indicator flashing light means different system failure.
malfunction
Running Indicator status
Remark
Indoor Jumper cap failure
Light out 3S then flash
once
Flash means light on
0.5S then light out 0.5S
Indoor fan failure
Light out 3S then flash
twice
Indoor tube temperature
sensor failure
Light out 3S then flash
four times
Indoor air outlet
temperature sensor failure
Light out 3S then flash six
times
7 Maintenance and Care
Regular check, maintenance and care should be performed by professional
personnel, which will prolong the unit life span.
7.1 Drain Pipe
Regularly check if the drain pipe is clogged in order to drain condensate smoothly.
7.2 Notice before Seasonal Use
(1) Check if the inlet/outlet of the indoor unit is clogged.
(2) Check if the ground wire is earthed reliably.
(3) Check if the filter screen has been set soundly.
(4) Check if the unit is installed firmly. If there is something abnormal, please contact
the local appointed service center.
7.3 Maintenance after Seasonal Use
(1) Cut off main power supply of the unit.
(2) Clean filter screen of indoor units.
34
Summary of Contents for NPFX24A
Page 18: ...Air Handlers 13...
Page 19: ...Air Handlers 14...
Page 21: ...Air Handlers 16...
Page 25: ...Air Handlers 20...
Page 26: ...Air Handlers 21...
Page 27: ...Air Handlers 22...
Page 28: ...Air Handlers 23...
Page 29: ...Air Handlers 24...
Page 41: ......
Page 42: ......
Page 43: ......