![Napoleon LV50N2 Installation And Operating Instructions Manual Download Page 16](http://html1.mh-extra.com/html/napoleon/lv50n2/lv50n2_installation-and-operating-instructions-manual_4226536016.webp)
16
W415-1624 / D / 11.22.16
EN
EN
Simple venting configuration (only one 90° elbow)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED VERTI-
CAL RISE
IN INCHES
(METERS)V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H
T
The shaded area within the lines represents acceptable
values for H
T
and V
T
0
5
(1.5)
15
(4.6)
20 (6.1)
100 (2.54)
50 (1.27)
150 (3.81)
12.5
(3.8)
15 (0.381)
57 (1.44)
147 (3.734)
1
(0.3)
10
(3.1)
19.5
(5.9)
(H
T
) > (V
T
)
SINGLE-SIDED
Simple venting configuration (only one 90° elbow)
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED VERTI-
CAL RISE
IN INCHES
(METERS)V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)H
T
The shaded area within the lines represents acceptable
values for H
T
and V
T
0
5
(1.5)
15
(4.6)
20 (6.1)
100 (2.54)
50 (1.27)
150 (3.81)
12.5
(3.8)
33.25 (0.845)
57 (1.44)
147 (3.73)
1
(0.3)
10
(3.1)
19.5
(5.9)
SEE-THROUGH