Adjust the pilot screw to provide properly sized fl ame.  Turn 
in a clockwise direction to reduce the gas fl ow.

Inlet pressure can be checked by turning screw (A) counter-
clockwise until loosened and then placing pressure gauge 
tubing over the test point. Gauge should read 7” (minimum 
4.5”) water column for natural gas or 13” (11” minimum) 
water column for propane. Check that main burner is 
operating on “HI”.

Outlet pressure can be checked the same as above using 
screw (B). Gauge should read 3.5” water column for natural 
gas or 10” water column for propane. Check that main burner 
is operating on “HI”.

AFTER TAKING PRESSURE READINGS, TIGHTEN 
SCREWS FIRMLY TO SEAL. DO NOT OVER TORQUE.

LEAK TEST

 

ADJUSTMENTS

VENTURI ADJUSTMENT

Air shutter adjustment must be done by a 

qualifi ed installer!

Air shutters have been factory set open according to the 
chart below:  
These setting are for (maximum) horizontal termination.

Closing the air shutter will cause a more yellow fl ame, 
but can lead to carboning.  Opening the air shutter will 
cause a more blue fl ame, but can cause fl ame lifting 
from the burner ports.  The fl ame may not appear yellow 
immediately; allow 15 to 30 minutes for the fi nal fl ame 
colour to be established. 

Adjustment may be required depending on fuel type, vent 
confi guration and altitude.

FLAME CHARACTERISTICS

PRESSURE ADJUSTMENT

Maximum Input Ratings:

  

NG 

P  

 

Top Vent 

35,000 BTU/hr 

31,500 BTU/hr

 

Rear Vent 

21,000 BTU/hr 

21,000 BTU/hr

A

B

PILOT SCREW

P

NG

5/16” (7.9mm)

3/8” (9.5mm)

PILOT 

BURNER

FLAME MUST ENVELOP 
UPPER 3/8” TO 1/2” OF
FLAME SENSOR 

FLAME

SENSOR

ELECTRODE

It’s important to periodically perform a visual check of the 
pilot and burner fl ames. 
Compare them to the illustrations provided. 

VENTURI

AIR SHUTTER 
OPENING

ORIFICE

W415-0955 / A / 11.09.16