3.4  EMPLACEMENTS ET DÉGAGEMENTS MINIMAUX DE LA TERMINAISON

INSTALLATION

CANADA

É.-U.

A

12” (304.8mm)

12” (304.8mm) Dégagement au-dessus du sol, d’une véranda, d’une terrasse en bois ou d’un balcon.

B

12” 

(304.8mm) 

Δ

9” (228.6mm)

Δ

Dégagement des fenêtres ou des portes qui ouvrent.

C

12” (304.8mm)*

12” 

(304.8mm)*

Dégagement des fenêtres fermées en permanence.

D

18” (457.2mm)**

18” 

(457.2mm)**

Dégagement vertical d’un sof

fi

 te ventilé situé au-dessus de la terminaison si la distance

horizontale est de moins de 2’ (0,6m) de la ligne médiane de la terminaison.

E

18” (457.2mm)**

18” 

(457.2mm)**

Dégagement d’un sof

fi

 te non ventilé.

F

0” (0mm)

0” (0mm)

Dégagement des murs faisant coin extérieur.

G

0” (0mm)***

0” (0mm)***

Dégagement des murs extérieurs 

in

combustibles faisant coin intérieur ou aux obstructions

in

combustibles (cheminée, etc.).

2” (50.8mm)***

2” (50.8mm)***

Dégagement des murs extérieurs combustibles faisant coin intérieur ou aux obstructions
combustibles (habillage extérieur, etc.).

H

3’ (0.9m)

3’ (0.9m)****

Dégagement horizontal de chaque côté depuis la ligne verticale tirée du centre d’un
ensemble de régulateur/compteur pour une distance verticale maximale de 15’  (4,6m).

I

3’ (0.9m)

3’ (0.9m) ****

Dégagement de l’évent du régulateur

J

12” (304.8mm)

9” (228.6mm)

Dégagement d’une prise d’air de ventilation non mécanique de la maison ou d’une prise
d’air de combustion de tout autre appareil.

K

6’ (1.8m)

3’ (0.9m) †

Dégagement d’une prise d’air mécanique.

L

7’ (2.1m) ‡

7’ (2.1m) ****

Dégagement au-dessus d’un trottoir ou d’une entrée pavée situés sur une propriété
publique.

M

12” (304.8mm)††

12” 

(304.8mm)****

Dégagement sous une véranda, une terrasse en bois ou un balcon.

N

16” (406.4mm)

16” (406.4mm) Dégagement au-dessus du toit.

O

2’ (0.6m)†*

2’ (0.6m)†*

Dégagement des murs adjacents, incluant les maisons voisines.

P

8’ (2.4m)

8’ (2.4m)

Le toit doit être incombustible et sans ouvertures.

Q

3’ (0.9m)

3’ (0.9m)

Voir le tableau pour les dimensions d’un mur plus large

R

6’ (1.8m)

6’ (1.8m)

Voir le tableau pour les dimensions d’un mur plus profond. La terminaison ne doit pas être 
installée sur quelconque mur ayant une ouverture entre la terminaison et le côté ouvert de 
la structure.

Δ

Pour les structures comportant trois murs et un toit, la terminaison doit être située à plus de 6 pieds (1,8m) sous une fenêtre s’ouvrant sur un plan horizontal. 

*

Recommandé a

fi

 n de prévenir la formation de buée dans les fenêtres et les cassures thermiques.

**

Il est recommandé d’utiliser un protecteur de chaleur et de maximiser la distance au sof

fi

 te de plastique.

***

L’ensemble périscopique requiert un dégagement minimal de 18 pouces (457,2mm) d’un mur extérieur faisant coin intérieur.

****

Ceci est une distance recommandée. Véri

fi

 ez les codes locaux pour connaître les contraintes additionnelles.

Trois pieds au-dessus si la distance horizontale est de moins de 10 pieds (3,1m).

Une terminaison d’évacuation ne doit pas être installée à un endroit où elle pourrait causer une formation dangereuse de givre ou de glace sur les surfaces d’une propriété 
adjacente.

††

Permis seulement si la véranda ou la terrasse en bois sont complètement ouverts sur un minimum de deux côtés sous le plancher.

†*

Recommandé a

fi

 n d’éviter la recirculation des produits d’échappement. Véri

fi

 ez les codes locaux pour connaître les contraintes additionnelles.

12.6C

NOTE : Les dégagements sont en conformité avec les codes d’installation locaux et les exigences du fournisseur de gaz.

R

Q

M

G

P

APPLICATIONS POUR BALCON COUVERT

Q

MIN

R

MAX

MAX

R

= 3 pieds

(0,9m)

= 2 x 

”SLHGV

(4,6m)

Q

RÉELLE

FR

W415-1333 / 06.26.14

 65

Summary of Contents for Castlemore GDS26N

Page 1: ...o not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department I...

Page 2: ...5 4 1 4 HORIZONTAL AIR TERMINAL INSTALLATION 25 4 1 5 EXTENDED HORIZONTAL AND CORNER TERMINAL INSTALLATION 26 4 1 6 VERTICAL AIR TERMINAL INSTALLATION 27 4 2 MOBILE HOME INSTALLATION 28 4 3 GAS INSTAL...

Page 3: ...REMOVAL section Rating Plate see RATING PLATE INFORMATION section Top vent see REAR VENT CONVERSION section Venting see VENTING section Blower see OPTIONAL BLOWER INSTALLATION section SAFETY BARRIER W...

Page 4: ...no circumstances should this appliance be modified This appliance must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance Do not use this appliance if any part has...

Page 5: ...stallation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT WITH THE GLASS DOOR OP...

Page 6: ...flow in the room where the appliance is to be located should be considered If possible you should choose a location where the vent will pass through the house without cutting a floor or roof joist If...

Page 7: ...DU SYSTEME DE PRISE D AIR DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES SERIAL NUMBER NO DESERIE 0 4500ft 25 000 BTU h 20 000 BTU h 61 3 CDVS26N GDS26P CDVS26P WOLF STEEL LTD 24 NAPOLEON ROAD BARRI...

Page 8: ...REQUIRED AT THE START MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED THESE SPACERS MUST NOT BE REMOVED 3 1 VENTING LENGTHS AND COMPONENTS Use only Wolf Steel Simpson Dura Vent Selkirk D...

Page 9: ...ting systems must not be combined Different venting manufacturers components must not be combined These vent kits allow for either horizontal or vertical venting of the appliance The maximum allowable...

Page 10: ...W415 1333 06 25 14 10 EN 29 1 8 740mm 20 508mm MAXIMUM See VENTING section 16 406mm MINIMUM 40 FT 12m MAXIMUM 3 FT 1m MINIMUM 29 1 8 740mm MINIMUM PLUS RISE...

Page 11: ...m for a fireplace and 8 2 4m for a stove 9 4A 3 3 SPECIAL VENT INSTALLATIONS 3 3 1 PERISCOPE TERMINATION 20 508mm MAXIMUM 6 RISE MINIMUM 3 3 2 CORNER TERMINATION The maximum vent length for a corner i...

Page 12: ...304 8mm 12 304 8mm Clearance under a veranda porch deck or balcony N 16 406 4mm 16 406 4mm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8...

Page 13: ...n Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizontal run Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizon...

Page 14: ...3 4m H1 2 5 FT 0 8m H2 2 FT 0 6m HR H1 H2 2 5 FT 0 8m 2 FT 0 6m 4 5 FT 1 4m HO 03 three 90 elbows 90 03 270 90 5 4 FT 1 7m HT HR HO 4 5 FT 1 4m 5 4 FT 1 6m 9 9 FT 3m HT VT 9 9 FT 3m 11 FT 3 4m 20 9 F...

Page 15: ...ce both formulas are met this vent configuration is acceptable 0 5 1 5 15 4 6 20 6 1 100 2540 50 1270 150 3810 12 5 3 8 19 1 2 495 3 57 1447 8 147 3733 8 2 0 6 The shaded area within the lines represe...

Page 16: ...within the lines represents acceptable values for HT and HT HT VT 16 3A For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 1...

Page 17: ...3_2B For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT VT 24 75 feet 7 5m Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4FT 1 2m 1...

Page 18: ...vent configurations requiring one or more 90 elbows top exit or one or more 90 elbows rear exit the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 5 FT 1 5m V2 6 FT...

Page 19: ...mulas apply Formula 1 HT 3 VT Formula 2 HT VT 40 feet 12 2m Example V1 2 FT 0 6m V2 1 FT 0 3m V3 1 5 FT 0 5m VT V1 V2 V3 2FT 0 6m 1FT 0 3m 1 5FT 0 5m 4 5 FT 1 4m H1 6 FT 1 8m H2 2 FT 0 6m HR H1 H2 6FT...

Page 20: ...1FT 0 3m 1FT 0 3m 10 75FT 3 3m 12 75FT 3 9m HO 03 four 90 elbows one 45 elbow 90 03 360 45 90 6 75 FT 2 1m HT HR HO 12 75FT 3 9m 6 75FT 2 1m 19 5 FT 5 9m HT VT 19 5FT 5 9m 6 5FT 2m 26 FT 7 9m Formula...

Page 21: ...OTE A vent adaptor will be required directly off the appliance Follow vent manufacturer s installation instructions Different manufacturer s venting components must not be combined Once the preferred...

Page 22: ...op of the appliance Before replacing the rear shield slide the vent pipe through the rear shield a few inches secure 4 102mm and 7 178mm to the collars Slide the rear shield along the vent pipe and re...

Page 23: ...ASPHYXIATION IMPROPER SUPPORT OF THE ENTIRE VENTING SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE USE VENT RUN SUPPORTS AND CONNECT VENT SECTIONS PER INSTALLATION INSTRUCTIONS RISK OF FIRE DO NOT ALLOW LO...

Page 24: ...rom your authorized dealer distributor See accessories to order specific kits required A Determine the air terminal location cut and frame a square opening as illustrated in the ceiling and the roof t...

Page 25: ...PERATURE SEALANT 8 X 1 2 SELF DRILLING SCREWS 4 1 4 HORIZONTAL AIR TERMINAL INSTALLATION TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE RETURN FLANGE OF THE MOUNTING P...

Page 26: ...73 0007 Mill Pac not supplied to the inner sleeve of the air terminal Slip the vent pipe a minimum of 2 50 8mm over the inner sleeve of the air terminal and secure with 3 8 screws B Using the outer ri...

Page 27: ...ving a min 3 4 19mm of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure that the air terminal connector is...

Page 28: ...is supplied with the mobile home appliance Conversion Kits This appliance is field convertible between Natural Gas NG and Propane LP To convert from one gas to another consult your Authorized dealer...

Page 29: ...inimum clearance to combustible construction from appliance and vent surfaces A 2 51mm B 5 127mm C 2 51mm Combustible Framing 1 25mm to bottom and sides of the vent pipe 2 51mm to top of the vent pipe...

Page 30: ...NON COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE 35 1 2 902mm 5 127mm 2 51mm TOP EXIT The appliance requires a minimum ceiling height of 51 1295mm for a top vent horizontal termination For to...

Page 31: ...ght Accent Light Switch The main burner on off switch and Night LightTM switch is located behind lower access panel For ease of accessibility optional remote wall switches may be installed in a conven...

Page 32: ...latches Pull forward on the latches and away from the door to release Slide the door forward off its support and lift straight up to remove INSTALLATION Slide the door in between the cast front and a...

Page 33: ...side of the rear log 6 2 DOOR GLASS REPLACEMENT A Place the door frame face down careful not to scratch the paint B Center the gasketed glass inside the door frame with the thick side of the gasket fa...

Page 34: ...ering all of the burner Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow The ember material will only glow when exposed...

Page 35: ...e the variable speed switch using the nut provided Reinstall the switch housing Install the variable speed switch knob WHITE RED BLACK GREEN GROUND THERMAL SWITCH VARIABLE SPEED SWITCH BLOWER WIRE EXT...

Page 36: ...ll a qualified service technician to inspect the appliance and replace any part of the control system and any gas control which has been under water Turn off all gas to the appliance Open windows Do n...

Page 37: ...that a continuous flow is at the burner before re installing the door WARNING 9 2 PRESSURE CHECK Check Pressure Readings Inlet pressure can be checked by turning screw A counter clockwise 2 or 3 turn...

Page 38: ...lame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30 minutes for the final flame colour to be established AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFI...

Page 39: ...al installation I Cleaning the safety barrier may be necessary due to excessive lint dust from carpeting pets etc simply vacuum using the brush attachment 40 1C MAINTENANCE MAINTENANCE MAINTENANCE TUR...

Page 40: ...and door from the firebox B Run the wires up through the lens hole C Align key hole with lens assembly D Snap into place E Replace light shields attach the wires and replace the door to the firebox A...

Page 41: ...REQUIRED TO HONOUR THE CLAIM When ordering replacement parts always give the following information Model Serial Number of appliance Installation date of appliance Part number Description of part Fini...

Page 42: ...LEON LOGO W135 0294 DOOR CASTING W135 0292 FRONT CASTING W565 0156 SAFETY SCREEN W010 2166 DOOR ASSEMBLY W062 0024 BLOWER ASSEMBLY W655 0523 DOOR SUPPORT W655 0331 DOOR SUPPORT PART NUMBER 17 18 19 20...

Page 43: ...T PRP19 W475 0556 BAFFLE PANEL GD839KT W475 0521 FRONT SANDSTONE BRICK PANEL X2 GD839KT W475 0520 LS SANDSTONE BRICK PANEL GD839KT W475 0518 REAR SANDSTONE BRICK PANEL GD839KT W475 0519 RS SANDSTONE B...

Page 44: ...100 0069 PILOT ASSEMBLY NG W010 3050 BURNER ASSEMBLY W035 0159 BURNER BASE W456 0042 BURNER ORIFICE 42 W725 0032 ELECTRONIC IGNITION VALVE 7 4 10 W105 0001 7 8 BUSHING W175 0055 3 8 CONNECTOR W175 022...

Page 45: ...NT KIT C W GD201 PERISCOPE 1 2 1 4 1 9 1 10 GD 201 PERISCOPE GD 301 HEAT GUARD RP4 RESTRICTOR PLATE 4 8 9 15 16 17 1 11 1 13 W010 0300 4 x 10 FLEX LINER C W SPACERS 1 15 1 16 W025 0001 DECORATIVE BRAS...

Page 46: ...dule Check voltage of the transformer under load at the spade connections on the module with the ON OFF switch in the ON position Acceptable readings of a good transformer are between 6 2 and 7 0 volt...

Page 47: ...e rectification Verify correct pilot orifice is installed and inlet gas specifications to manual Remember the flame carries the rectification current not the gas If the flame lifts from pilot hood the...

Page 48: ...or plate See RESTRICTING VENTS section if applicable Main burner flame is a blue lazy transparent flame Blockage in vent Remove blockage In really cold conditions ice buildup may occur on the terminal...

Page 49: ...damaging chemicals or cleaners will not be the responsibility of NAPOLEON All parts replaced under the President s Limited Lifetime Warranty Policy are subject to a single claim During the first 10 y...

Page 50: ...W415 1333 06 25 14 50 EN 18 0 SERVICE HISTORY 43 1...

Page 51: ...W415 1333 06 25 14 51 EN 19 0 NOTES 44 1...

Page 52: ...ting Cooling call 705 721 1212 Grills call 705 726 4278 napoleonproducts com 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden...

Page 53: ...vice des incendies L installation et l entretien doivent tre faits par un installateur qualifi une agence d entretien ou le fournisseur Cet appareil peut tre install dans une maison pr fabriqu e mobil...

Page 54: ...1 6 INSTALLATION DE LA TERMINAISON VERTICALE 81 4 2 INSTALLATION DANS UNE MAISON MOBILE 82 4 3 BRANCHEMENT DU GAZ 83 4 4 D GAGEMENTS MINIMAUX AUX MAT RIAUX COMBUSTIBLES 84 5 0 BRANCHEMENT LECTRIQUE 8...

Page 55: ...VEMENT DE LA PORTE VITR E Plaque d homologation voir la section INFORMATION SUR LA PLAQUE D HOMOLOGATION vacuation sur le dessus voir la section CONVERSION EN VACUATION L ARRI RE vacuation voir la se...

Page 56: ...sp cialiste en entretien Un entretien plus fr quent pourrait tre n cessaire en raison des peluches provenant des tapis literie etc L emplacement de l appareil doit tre gard libre de tous mat riaux com...

Page 57: ...normes actuelles pour les maisons mobiles quip es au gaz CAN CSAZ240 S RIE MM au Canada ou selon les normesANSI Z223 1 et NFPA54 aux tats Unis ALLUMEZ TOUJOURS LA VEILLEUSE QUE CE SOIT POUR LA PREMI...

Page 58: ...ational Electrical Code ANSI NFPA70 aux tats Unis Nous sugg rons que nos appareils au gaz soient install s et que l entretien soit effectu par des professionnels certi fi s par le National Fireplace I...

Page 59: ...NT APRES AVOIR ASSURE LE MAINTIEN DU SYSTEME DE PRISE D AIR DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES SERIAL NUMBER NO DESERIE 0 4500ft 25 000 BTU h 20 000 BTU h CDVS26N GDS26P CDVS26P WOLF STEE...

Page 60: ...nier lorsque les murs int rieurs le plancher ou le plafond sont travers s NOTE Si pour une raison quelconque le syst me d vents de prise d air est d mont r installez le selon les instructions fournies...

Page 61: ...semble de terminaison pour toit de pente 1 12 7 12 GD110 ensemble de terminaison pour toit de pente 8 12 12 12 GD111 ensemble de terminaison pour toit plat GD112 ou ensemble p riscopique GD180 pour p...

Page 62: ...TYPIQUES D VENTS 45 1 2 156mm MINIMUM PLUS L L VATION Voir la section VACUATION 16 406mm MINIMUM 40 PI 12m MAXIMUM 3 PI 1m MINIMUM 35 1 2 902mm 35 1 2 902mm 10 254mm MINIMUM 24 610mm MAXIMUM FR W415...

Page 63: ...29 1 8 740mm MINIMUM PLUS L L VATION Voir la section VACUATION 16 406mm MINIMUM 40 PI 12m MAXIMUM 3 PI 1m MINIMUM 29 1 8 740mm 20 508mm MAXIMUM FR W415 1333 06 26 14 63...

Page 64: ...ATIONS PARTICULI RES D VENTS 3 3 1 ENSEMBLE P RISCOPIQUE 12 305mm MINIMUM AU NIVEAU DU SOL 12 305mm MINIMUM AU NIVEAU DU SOL 24 610mm MINIMUM 35 1 2 902mm 24 610mm MINIMUM FR W415 1333 06 26 14 64 6 M...

Page 65: ...ssus du toit O 2 0 6m 2 0 6m D gagement des murs adjacents incluant les maisons voisines P 8 2 4m 8 2 4m Le toit doit tre incombustible et sans ouvertures Q 3 0 9m 3 0 9m Voir le tableau pour les dime...

Page 66: ...e horizontale La course verticale est plus petite que la course horizontale La course verticale est plus grande ou gale la course horizontale La course verticale est plus petite que la course horizont...

Page 67: ...T LONGUEUR DES COURSES HORIZONTALES PLUS LES D VIATIONS EN PIEDS M TRES HT PI 1 4m Lorsque la configuration de l vacuation exige plus d un coude de 90 les formules suivantes s appliquent Formule 1 HT...

Page 68: ...03 180 90 2 7PI 0 8m HT HR HO 8PI 2 4m 2 7PI 0 8m 10 7PI 3 3m HT VT 10 7PI 3 3m 6PI 1 8m 16 7PI 5 1m Formule 1 HT 4 2 VT 4 2 VT 4 2PI 1 3m x 6PI 1 8m 25 2PI 7 7m 10 7PI 3 3m 25 2PI 7 7m Formule 2 HT V...

Page 69: ...des lignes repr sente des valeurs acceptables pour HT et VT HT VT 16 3A Lorsque la configuration de l vacuation exige plus qu un coude de 90 les formules suivantess appliquent Formule 1 HT VT Formule...

Page 70: ...sque la configuration de l vacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT 3 5VT Formule 2 HT VT 24 75 pieds 7 5m Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4...

Page 71: ...ation sur le dessus ou un coude de 90 vacuation l arri re les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 5 PI 1 5m V2 6 PI 1 8m V3 10 PI 3 1m VT V1 V2 V3...

Page 72: ...ppliquent Formule 1 HT 3 VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 2 PI 0 6m V2 1 PI 0 3m V3 1 5 PI 0 5m VT V1 V2 V3 2PI 0 6m 1PI 0 3m 1 5PI 0 5m 4 5PI 1 4m H1 6 PI 1 8m H2 2 PI 0 6m HR H1 H2 6PI 1...

Page 73: ...3 9m HO 0 03 quatre coudes 90 un coude 45 90 0 03 360 45 90 6 75 PI 2 1m HT HR HO 12 75PI 3 9m 6 75PI 2 1m 19 5PI 5 9m HT VT 19 5 PI 5 9m 6 5 PI 2m 26 PI 7 9m Formule 1 HT 3 VT 3 VT 3PI 0 9m x 6 5PI 2...

Page 74: ...n cessaire directement partir de l appareil Suivez les instructions d installation du fabricant du syst me d vacuation Des composants d vacuation de diff rents fabricants ne doivent pas tre combin s...

Page 75: ...l Remettez les composants 7 10 sur le dessus de l appareil Avant de remettre l cran arri re ins rez y le conduit d vacuation de quelques pouces puis fixez le conduit aux collets de 4 102mm et 7 178mm...

Page 76: ...VENT N EST PAS AD QUATEMENT SOUTENU IL RISQUE DE FL CHIR OU DE SE S PARER UTILISEZ DES SUPPORTS DE CONDUIT ET RACCORDEZ LES SECTIONS DE CONDUITS SELON LES INSTRUCTIONS D INSTALLATION RISQUE D INCENDI...

Page 77: ...mais doit se prolonger sur toute la profondeur du mur combustible A Appliquez un joint de calfeutrage non fourni tout autour de la bordure de la face int rieure de l espaceur coupe feu installez l esp...

Page 78: ...nt michemin entre deux solives pour ne pas tre oblig de les couper Utilisez du fil plomb pour aligner le centre des ouvertures Un protecteur de conduit d vacuation emp chera tout mat riau tel que l is...

Page 79: ...pports incombustibles afin de maintenir le d gagement minimal aux mat riaux combustibles La plaque de montage de la terminaison peut tre ench ss e dans le mur ou le rev tement ext rieur n exc dant pas...

Page 80: ...ant les conduits int rieurs et ext rieurs Assurez vous que tous les conduits int rieurs et les coudes aient suffisamment d espaceurs et que chaque composant est scell et fix solidement celui qui le pr...

Page 81: ...nt un minimum de 3 4 19 1mm de connecteur de terminaison visible au dessus du haut du solin Glissez le solin sous les c t s et le bord sup rieur des bardeaux Assurez vous que le connecteur de terminai...

Page 82: ...ne installation dans une maison mobile l appareil doit tre fix au plancher Fixez l aide de vis 10 t te hexagonale ins r es dans les trous de la base teignez toujours la veilleuse et l alimentation en...

Page 83: ...gaz en appliquant une solution d eau savonneuse N utilisez pas une flamme nue AVERTISSEMENT RISQUE D INCENDIE D EXPLOSION OU D ASPHYXIE ASSUREZ VOUS QU IL N Y AIT AUCUNE SOURCE D ALLUMAGE COMME DES TI...

Page 84: ...la soufflerie D gagements minimaux de l appareil aux mat riaux combustibles A 2 51mm B 5 127mm C 2 51mm Ossature combustible 1 25mm des c t s et du dessous du conduit d vent 2 51mm au dessus du condui...

Page 85: ...m 35 1 2 902mm 51 1295mm 2 51mm VACUATION SUR LE DESSUS Le plafond o l appareil est install doit avoir une hauteur minimale de 51 1295mm pour une vacuation sur le dessus avec terminaison horizontale P...

Page 86: ...pteur mural optionnel GD 660 Interrupteur de br leur Brun Illustr e la position OFF NOTE LES TIQUETTES DE FIL SONT ENTRE PAREN TH SES 20 6 1m Fil de l interrupteur fourni Les interrupteurs du br leur...

Page 87: ...u caisson Tirez sur les loquets vers l avant pour les d verrouiller Glissez la porte vers l avant hors de son support puis soulevez la pour la retirer INSTALLATION Glissez la porte entre la fa ade en...

Page 88: ...E DE PORTE PATTE DE RETENUE AVERTISSEMENT N UTILISEZ PAS DE MAT RIAUX DE SUBSTITUTION LA VITRE PEUT TRE CHAUDE NE TOUCHEZ PAS LA VITRE JUSQU CE QU ELLE AIT REFROIDI USEZ DE PRUDENCE LORSQUE VOUS ENLEV...

Page 89: ...Placez la b che arri re tel qu illustr en vous assurant que les trous sous la b che soient plac s sur les 2 tiges du support b ches Pour installer les b ches la porte vitr e doit tre enlev e Voir la...

Page 90: ...andescentes en morceaux et placez les le long des orifices du br leur en prenant soin de couvrir tout le br leur Les braises devraient tre d chir es tr s soigneusement en petits morceaux minces irr gu...

Page 91: ...cal Code ANSI NFPA 70 aux tats Unis A Retirez les plaques poin onn es de la soufflerie et de l interrupteur thermique sur le panneau arri re B Faites passer l extension de fils dans le trou de la souf...

Page 92: ...n utilisez aucun t l phone dans votre immeuble 1 ARR TEZ Lisez les consignes de s curit sur l tiquette de fonctionnement 2 Mettez l interrupteur mural la position OFF 3 Coupez l alimentation lectrique...

Page 93: ...OPTIONNELLE Lorsqu il est install cet interrupteur place la soufflerie sous tension et sert r gler la vitesse de la soufflerie Il y a aussi un interrupteur thermique qui mettra en marche la soufflerie...

Page 94: ...INJECTEUR DE BR LEUR A Coupez l alimentation lectrique et en gaz l appareil B Retirez la fa ade en fonte la porte vitr e et les b ches C Retirez les deux vis de fixation glissez le br leur vers la dr...

Page 95: ...eut ne pas tre jaune imm diatement allouez de 15 30 minutes pour que la couleur finale de la flamme se stabilise LE R GLAGE DU VOLET D AIR DOIT TRE EX CUT PAR UN TECHNICIEN OU INSTALLATEUR QUALIFI VEN...

Page 96: ...haut et le bas de la porte ne sont pas bris s ou manquants Remplacez si n cessaire H Si pour une raison quelconque le syst me d vents de prise d air est d mont r installez et rescellez le selon les i...

Page 97: ...couvercle de la lentille en vous assurant que la rondelle demeure en place NOTE Lorsque vous manipulez l ampoule ne la laissez pas entrer en contact direct avec vos doigts prot gez la avec un linge pr...

Page 98: ...DE Lorsque vous commandez des pi ces donnez toujours l information suivante Mod le et num ro de s rie de l appareil Date d installation de l appareil Num ro de la pi ce Description de la pi ce Fini ID...

Page 99: ...UTON W500 0391 PLATEAU DE L AIMANT W430 0013 LOQUET DE PORTE AIMANT W080 0831 SUPPORT DU FIXATION DE FONTE W010 2109 LOQUET DE PORTE X4 W655 0265 SUPPORT DES B CHES ARRI RE W135 0581 DESSUS EN FONTE W...

Page 100: ...W475 0518 PANNEAU BRIQUE VICTORIEN ARRI RE GD839KT W475 0519 PANNEAU BRIQUE VICTORIEN C TE DROITE GD839KT W090 0153 PANNEAU DE PORCELAINE DU C T X2 PRP19 1 2 3 4 5 6 7 W090 0152 PANNEAU DE PORCELAINE...

Page 101: ...5 0021 6 7 7 6 13 1 14 1 15 1 16 16 CES ARTICLES PEUT DIFF RER DE CELLE ILLUSTR SUPPORT DE VEILLEUSE ASSEMBLAGE DE VEILLEUSE GN ASSEMBLAGE DE BR LEUR BAGUE 7 8 BASE DU BR LEUR CROU COLLECTEUR 3 8 SUPP...

Page 102: ...ARTICLES PEUT DIFF RER DE CELLE ILLUSTR ATTELAGE 4 TERMINAISON POUR TOIT 1 12 7 12 PENTE TERMINAISON POUR TOIT 8 12 12 12 PENTE TERMINAISON POUR TOIT PLAT TERMINAISON POUR TOIT AVEC COLLET DE SOLIN E...

Page 103: ...l ensemble de b ches tincelle la veilleuse mais celle ci ne s allume pas Alimentation en gaz V rifiez si la soupape bille de la conduite d arriv e du gaz est Ouverte V rifiez si la pression d arriv e...

Page 104: ...rant de la flamme V rifiez si le bon injecteur de veilleuse est install et que l alimentation en gaz est conforme aux sp cifications du manuel Souvenez vous que la flamme transporte le courant redress...

Page 105: ...y a lieu La flamme du br leur principal est bleue paresseuse et transparente Syst me d vacuation bloqu Enlevez ce qui obstrue Dans des conditions de froid extr me une accumulation de glace peut se for...

Page 106: ...u produits d entretien nuisibles ne seront pas la responsabilit de NAPOL ON Toutes les pi ces remplac es en vertu de la politique de Garantie vie limit e du Pr sident ne peuvent faire l objet que d un...

Page 107: ...UE D ENTRETIEN Date 43 1 Probl mes particuliers Travail effectu Nom du technicien D taillant Historique d entretien Wolf Steel Cet appareil doit tre entretenu annuellement selon son usage FR W415 1333...

Page 108: ...s lectriques Foyers ext rieurs Grils gaz de qualit Foyers Chauffage et Climatisation Grils composez 514 737 6294 napoleonproducts com 7200 Route Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Roa...

Reviews: