background image

27

W415-0381 / H / 12.07.07

Pilot will not light.

-  check if pilot can be lit by a match
-  check that the wire is connected to the push button igniter.
-  check if the push button igniter needs tightening.
-  replace the wire if the wire insulation is broken or frayed.
-  replace the electrode if the ceramic insulator is cracked or broken.
-  replace the push button igniter.

 No spark at pilot burner

-  fi ll the tank.

Out of propane gas

Spark gap is incorrect

-  spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) from the electrode 
tip and the pilot burner. To ensure proper electrode location, tighten securing nut 
(fi nger tight plus 1/4 turn).

No gas at the pilot burner

-  check that the manual valve is turned on.
-  check the pilot orifi ce for blockage.
-  replace the valve.
-  call the gas distributor.

Main burner goes out; 
pilot stays on.

Pilot fl ame is not large enough or 
not engulfi ng the thermopile

-  turn up pilot fl ame.

- replace pilot assembly.

Thermopile shorting

- clean thermopile connection to the valve. Reconnect.

- replace thermopile / valve.

Remote wall switch wire is too 
long; too much resistance in the 
system.

-  shorten wire to correct length or wire gauge.

Faulty thermostat or switch.

-  replace.

5" fl exible vent has become dis-
connected from fi replace.

Pilot goes out when the 
gas knob is released.

The gas valve has 
an interlock device 
which will not allow 
the pilot burner to be 
lit until the thermo-
couple has cooled. 
Allow approximately 
60 seconds for the 
t h e r m o c o u p l e   t o 
cool.

System is not correctly purged.

-  purge the gas line with the glass door removed.

Out of propane gas.

-  fi ll the tank.

Pilot fl ame is not large enough

-  turn up the pilot fl ame.

-  gently twist the pilot head to improve the fl ame pattern around the thermo-
couple.

Pilot fl ame is not engulfi ng the 
thermocouple.
Thermocouple shorting / faulty.

-  loosen and tighten thermocouple.
-  clean thermocouple and valve connection.
-  replace thermocouple.
-  replace valve.

Faulty valve.

-  replace.

Pilot burning; no gas 
to main burner; gas 
knob is on 'HI'; wall 
switch / thermostat 
is on.

Thermostat or switch is defec-
tive.

-  connect a jumper wire across the wall switch terminals; if main burner lights, 
replace switch / thermostat.

Main burner orifi ce is plugged.

-  remove stoppage in orifi ce.

Faulty valve.

-  replace.

Wall switch wiring is defective.

-  disconnect the switch wires & connect a jumper wire across terminals 1 & 3; if 
the main burner lights, check the wires for defects and / or replace wires.

Main burner goes out; 
pilot goes out.

Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON"

Vent is blocked

Vent is re-circulating

-  check for vent blockage.

-  check joint seals and installation.

-  re-attach to fi replace.

TROUBLE SHOOTING GUIDE

SYMPTOM

PROBLEM

TEST SOLUTION

B

EFORE

 

ATTEMPTING

 

TO

 

TROUBLESHOOT

PURGE

 

YOUR

 

UNIT

 

AND

 

INITIALLY

 

LIGHT

 

THE

 

PILOT

 

AND

 

THE

 

MAIN

 

BURNER

 

WITH

 

THE

 

GLASS

 

DOOR

 

REMOVED

.

Flames are consist-
ently too large or too 
small. Carboning oc-
curs.

-  check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clockwise 2 or 3 
turns and then placing pressure gauge tubing over the test point. Gauge should 
read 7" (minimum 4.5") water column for natural gas or 13" (11" minimum) water 
column for propane. Check that main burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B). Gauge 
should read 3.5" water column for natural gas or 10" water column for propane. 
Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN SCREWS CLOCK-
WISE FIRMLY TO RESEAL. DO NOT OVERTORQUE.
Leak test with a soap and water solution.

Unit is over-fi red or under-fi red.

Pilot goes out while 
standing; Main burner 
is in 'OFF' position.

Gas piping is undersized.

-  turn on all gas appliances and see if pilot fl ame fl utters, diminishes or extin-
guishes, especially when main burner ignites. Monitor appliance supply working 
pressure.

-  check if supply piping size is to code. Correct all undersized piping.

Summary of Contents for BGD42

Page 1: ...1 W415 0381 H 12 07 07 W415 0381 H 12 07 07 10 00...

Page 2: ...nts toddlers from touching hot surfaces Even after the fireplace is out the glass and or screen will remain hot for an extended period of time Check with your local hearth specialty dealer for safety...

Page 3: ...venting components used in the installation of the replace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life subject to the following conditions During...

Page 4: ...rity having jurisdiction the certi ed high altitude input rating shall be reduced at the rate of 4 for each additional 1 000ft Maximum output for natural gas is 19 500 BTU hr at an ef ciency of 68 5 w...

Page 5: ...5 W415 0381 H 12 07 07 FIGURE 1 INSTALLATION OVERVIEW FIGURE 2...

Page 6: ...Direct Temp and American Metal Amerivent follow the installation procedure provided with the venting components All outer pipe joints of these venting systems must be sealed using Red RTV Hight Temper...

Page 7: ...AIR TERMINAL LOCATION CLEARANCES 32 32 32 32 32 32 4 Using a soffit heat shield W585 0096 or equivalent the distance may be reduced to a minimum of 18 It is recommended to maximize the distance to th...

Page 8: ...at when nal grading is completed the bottom air slot is located a minimum of 12 above grade FIGURES 4 a b FIGURE 5 TYPICAL VENT INSTALLATIONS NOTE When terminating vertically the restrictor plate W500...

Page 9: ...tal run horizontal run verti cal rise to maximum of 40 feet vertical rise is less than horizontal run horizontal run verti cal rise to maximum of 24 75 feet 4 2timesthe vertical rise equal to or great...

Page 10: ...of offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the rst 45 and 90 offset has a zero value and is shown in the f...

Page 11: ...T when HT VT Simple venting con guration only one 45 and 90 elbow Example 2 V1 4 ft V2 1 5 ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Page 12: ...et 25 9 40 Since both formulas are met this vent con guration is acceptable when HT VT Simple venting con gurations FIGURE 10 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET...

Page 13: ...40 Since both formulas are met this vent con guration is acceptable REQUIRED VERTICAL R I S E I N FEET VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT FIGURE 12 The shaded area within the lines represe...

Page 14: ...learance of 2 all around the vent pipe on all horizontal runs to combustibles is required Use restop spacer W010 1778 supplied VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all ver...

Page 15: ...combus tion air collar and secure with 3 8 screws 6 If more liner needs to be used to reach the replace couple them together as illustrated The vent system must be supported approximately every 3 feet...

Page 16: ...erminal sleeves engage into the vent pipes and sealant Secure the terminal to the exterior wall and make weather tight by sealing with caulking not supplied Theairterminalmountingplatemaybe recessed i...

Page 17: ...h a 5 collapsed telescopic pipe to the last section of rigid piping Secure with screws and seal Repeat using a 8 telescopic pipe 10 Run a bead of high temperature sealant W573 0007 not sup plied Mill...

Page 18: ...is positioned and the vent system is installed Use 2x4 s and frame to local building codes FIGURES 33 It is not necessary to install a hearth extension with this replace system When roughing in the r...

Page 19: ...Centre the nailing tab vertically on the corner post Figure 36 a Drill through the centre of the top and bottom slots in the nailing tab Secure using the two sheet metal screws supplied This allows t...

Page 20: ...clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of the clips forward while push ing the louvre assembly back Lift the clip B HING...

Page 21: ...g embers for a maximum glowing effect Log colours may vary During the initial use of the replace the colours will become more uniform as colour pigments burn in during the heat activated curing proces...

Page 22: ...ll automatically start approxi mately 10 minutes after lighting the fireplace and will run for ap proximately 30 45 minutes after the fireplace has been turned off Use of the fan increases the output...

Page 23: ...valve has an interlock device which will not al low the pilot burner to be lit until the thermocouple has cooled Allow approximately 60 seconds for the thermocouple to cool When lighting and re lighti...

Page 24: ...e gasket Adjust the pilot screw to provide properly sized ame Turn in a clockwise direction to reduce the gas ow Air shutters have been factory set open according to the chart below These settings are...

Page 25: ...LANT 39 W175 0166 5 COUPLER 39 W175 0002 8 COUPLER 40 L42K LOUVRE KIT UPPER LOWER BLACK 40 L42PB LOUVRE KIT UPPER LOWER POLISHED BRASS 40 L42SS LOUVRE KIT UPPER LOWER BRUSHED STAINLESS STEEL 41 GDOI42...

Page 26: ...26 W415 0381 H 12 07 07...

Page 27: ...le and valve connection replace thermocouple replace valve Faulty valve replace Pilot burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defec tive co...

Page 28: ...door gasketing is not broken or missing and that the seal is tight check that both 5 and 8 vent liners are free of holes and well sealed at all joints check that minimum rise per foot has been adhered...

Reviews: