background image

21

W415-0299 / C / 03.12.03

FIGURE 40

FIGURE 39

1. 

Move the fireplace into position.

2. 

Fasten the roof support to the roof using the screws

provided. The roof support is optional. In this case the vent-
ing is to be adequately supported using either an alternate
method suitable to the authority
having jurisdiction or the optional
roof support.

3.

 Apply high temperature sealant

to the outer edge of the inner sleeve
of the air terminal. Slip a 5" diam-
eter coupler a minimum of 2" over
the sleeve and secure using 3
screws.

5

.

 Apply high temperature sealant

to the outer edge of the of the out-
side sleeve of the air terminal. Slip
a 8" diameter coupler over the sleeve and secure as
before.Trim the 8" coupler even with the 5" coupler end.

5

.

 Thread the air terminal pipe assembly down through the

roof  support and attach, ensuring that a minimum 16" of
air terminal will penetrate the roof when fastened. 

If the

attic space is tight, we recommend threading the Wolf
Steel vent pipe collar or equivalent loosely onto the air
terminal assembly as it is passed through the attic.
 

The air terminal must be located vertically and plumb.

6

.

 Remove nails from the shingles, above and to the sides

of the chimney. Place the flashing over the air terminal and
slide it underneath the sides and upper edge of the
shingles. Ensure that the air terminal is properly centered
within the flashing, giving a 3/5" margin all around. Fasten
to the roof. Do NOT nail through the lower portion of the
flashing. Make weather-tight by sealing with caulking. Where
possible, cover the sides and top edges of the flashing
with roofing material.

For optimum performance it is recommended that all
horizontal runs have a ¼ inch rise per foot.
For safe and proper operation of the fireplace, follow
the venting instructions exactly.

The vent system must be supported approximately every 3
feet for both vertical and horizontal runs.  Use Napoleon
vent spacers 

W615-0033

 every 3 feet and on either side of

each elbow to maintain the minimum 1¼" clearance be-
tween the outer and inner vent pipes. Use Napoleon sup-
port ring assembly 

W010-0380

 or equivalent noncombus-

tible strapping to maintain the minimum 1" clearance to
combustibles for both vertical and horizontal runs.

1. 

Move the fireplace into position. Measure the vent

length required between terminal and fireplace taking into
account the additional length needed for the finished wall
surface and any 1¼" overlaps between venting compo-
nents.

2. 

Apply high temperature sealant to the outer edge of the

5" inner collar of the fireplace.  Attach the first vent compo-
nent and secure using 3 self tapping screws. Repeat us-
ing 8" piping.

3. 

Holding the air terminal (lettering in an upright, readable

position), insert into both vent pipes with a twisting motion
to ensure that both the terminal sleeves engage into the
vent pipes and the sealant. Secure the terminal to the exte-
rior wall and make weather tight by sealing with caulking
(not supplied). 

 The air teminal may be recessed into the

exterior wall or siding by 1½", the depth of the return
flange.

USING RIGID VENT COMPONENTS

5. 

Remove nails from the shingles, above and to the sides

of the chimney. Place the flashing over the air terminal and
slide it underneath the sides and upper edge of the
shingles. Ensure that the air terminal is properly centered
within the flashing, giving a 3/5" margin all around. Fasten
to the roof. Do 

not

 nail through the lower portion of the

flashing. Make weather-tight by sealing with caulking.
Where possible, cover the sides and top edges of the flash-
ing with roofing material.

6. 

Apply a heavy bead of weatherproof caulking 2 inches

above the flashing. Slide the storm collar around the air
terminal and down to the caulking. Tighten to ensure that a
weather-tight seal between the air terminal and the collar
is achieved. Attach the other storm collar centered between
the air intake and the air exhaust slots onto the air termi-
nal. Tighten securely. Attach the vertical rain cap.

Spacers are attached to the 5" inner flex liner at prede-
termined intervals to maintain a 1-1/5" air gap to the 8"
outer liner. These spacers must not be removed.

7. 

If more liner needs to be used to reach the fireplace,

couple them together as illustrated. The vent system must
be supported approximately every 3 feet for both vertical and
horizontal runs. Use Wolf Steel support ring assembly 

W010-

0370

 or equivalent noncombustible strapping to maintain a

clearance to combustibles of 1".

HORIZONTAL AIR TERMINAL INSTALLATION

VERTICAL AIR TERMINAL INSTALLATION

FIREPLACE VENT CONNECTION

1. 

Install the 5 inch diameter

aluminum flexible liner to the fire-
place. Secure with 3 screws and
flat washers. Seal
the joint and screw
holes using the high
temperature sealant
provided.

2. 

Install the 8 inch

diameter aluminum
flexible liner to the
fireplace. Attach and
seal the joints.

FIGURE 41

Summary of Contents for BGD40-N

Page 1: ...Z21 88 FOR VENTED GAS FIREPLACE HEATERS WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YO...

Page 2: ...ildren when they are in the same room as the fireplace Due to high temperatures the fireplace should be located out of traffic and away from furniture and draperies Clothing or other flammable materia...

Page 3: ...fficial Labour costs to the however requires the prior approval of an authorized company official Labour costs to the account of account of account of account of account of NAPOLEON NAPOLEON NAPOLEON...

Page 4: ...nches FOR YOUR SATISFACTION ALL BURNER ASSEMBLIES HAVE BEEN TEST FIRED TO ASSURE THEIR OPERA TIONS AND QUALITY Maximum input is 30 000 BTU h for natural gas and propane When the fireplace is installed...

Page 5: ...rawl spaces should be insulated with the insulation wrapped in a protective sleeve to minimize condensation Objects placed in front of the fireplace must be kept a minimum of 48 away from the glass fr...

Page 6: ...ions when using aluminum flex ible venting For optimum flame appearance and fireplace perform ance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at a...

Page 7: ...en Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to un...

Page 8: ...e vertical rise is less than is less than is less than is less than is less than horizontal horizontal horizontal horizontal horizontal run run run run run horizontal horizontal horizontal horizontal...

Page 9: ...f fireplace as illustrated When venting the horizontal run must be kept to a mini mum of 10 inches or a maximum of 20 feet If a 20 foot horizontal run is required the fireplace must have a mini mum ve...

Page 10: ...6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the formula as 45 and 90 respectively or 135 when combined For vent configurations requiring more t...

Page 11: ...HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft VT V1 4 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45 elbow three 90 elbow 135 03 315 135...

Page 12: ...onfiguration is ac ceptable when HT VT Simple venting configurations FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent configurations requiring mo...

Page 13: ...40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 5 V...

Page 14: ...e fireplace face flush with the finished wall position the framework to accommodate the thickness of the finished wall Care should be taken to maintain sufficient clearance for the vent installation A...

Page 15: ...ned for will interfere with the opening of the lower access door and the installation of many decorative flashing accessories Objects placed in front of the fireplace should be kept a minimum of 48 aw...

Page 16: ...in position bend down the tab to secure DE TAIL 6 A A 25 minus finishing material thickness each side FIGURES21a c FIGURE20 Combustible materials may be installed flush with the front of the fireplac...

Page 17: ...TAIL5 6 Combustible materials may be installed flush with the front of the fireplace but must not cover any of the black face areas of the fireplace Non combustible material brick stone or ceramic til...

Page 18: ...d all venting options See pages 14 17 FIGURE26 FIGURE27 Horizontal Vent Off Fireplace Vertical Vent Off Fireplace A 42 using flexible vent components A 38 using Wolf Steel rigid vent components B 45 u...

Page 19: ...s to or der the specific kit re quired 1 Determine the air ter minal location cut and frame 10 inch open ings in the ceiling and the roof to provide the minimum clearance be tween the fireplace pipe l...

Page 20: ...er tight by sealing with caulking not supplied 6 If more liner needs to be used to reach the fireplace couple them together as illustrated The vent system must be supported approximately every 3 feet...

Page 21: ...taking into account the additional length needed for the finished wall surface and any 1 overlaps between venting compo nents 2 Apply high temperature sealant to the outer edge of the 5 inner collar...

Page 22: ...lar is achieved Attach the other storm collar centered between the air intake and air exhaust slots onto the air terminal Tighten securely Attach the rain cap 8 Continue adding rigid venting sections...

Page 23: ...ce 3a is the base of log 3 The base sits diagonally in the designated area lo cated between logs 1 and fits tight up against 2 4 The slot in the under side of piece 3b fits over 3a Place the end of pi...

Page 24: ...them Fine dust found in bottom of bag not to be used PHAZERTM logs and embers glow when exposed to direct flame Use only certified PHAZERTM logs glowing embers and char coal embers available from you...

Page 25: ...TION FIGURE 57 L36 LOUVRE INSTALLATION FIGURE 54a c HOOD Attach the hood by pressing the top flange into the clips along the top of the louvre opening Secure using a screw through the centre slot LOWE...

Page 26: ...automatically start approximately 10 minutes after lighting the fireplace and will run for approximately 30 45 minutes after the fireplace has been turned off Use of the fan increases the output of he...

Page 27: ...information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and hold gas knob while lighting the pilot with the push button ignitor...

Page 28: ...final flame colour to be established FIGURE66 FIGURE64 FIGURE65 AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BYA QUALIFIEDGASINSTALLER WARNING This is a fast act ing thermocouple It is an in tegral safety...

Page 29: ...0 0801 NATURAL GAS PILOT ASSEMBLY 35 W010 0800 PROPANE GAS PILOTASSEMBLY 36 W455 0069 NATURAL GAS PILOT INJECTOR 36 W455 0067 PROPANE GAS PILOT INJECTOR 37 W660 0005 BURNER ON OFF SWITCH 38 W680 0004...

Page 30: ...30 W415 0299 C 03 12 03 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Page 31: ...SET BRUSHED COPPER PLATED 17 DOIBG 1 DIAMOND ORNAMENTAL INSET BRUSHED GOLD PLATED 18 EDOIG 1 END DIAMOND ORNAMENTAL INSET GOLD PLATED 18 EDOIKG 1 END DIAMOND ORNAMENTAL INSET BLACK GOLD PLATED 18 EDOI...

Page 32: ...L O F F O Main burner flame is a blue lazy t r a n s p a r e n t flame Blockage in vent remove blockage In really cold conditions ice buildup may occur on the terminal and should be removed as require...

Page 33: ...needs tightening replace the wire if the wire insulation is broken or frayed replace the electrode if the ceramic insulator is cracked or broken replace the push button ignitor No spark at pilot burn...

Page 34: ...34 W415 0299 C 03 12 03 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 35: ...35 W415 0299 C 03 12 03 NOTES...

Page 36: ...36 W415 0299 C 03 12 03 NOTES...

Reviews: