W415-0973 / B / 08.28.13
7
IOM
FIGURE 1 - FURNACE DIMENSIONS
TOP
LEFT SIDE
RIGHT SIDE
1 1/2"
(38mm)
3/4"
(19mm)
0"
Top
NOTES:
S - Service clearance 24 inches (610mm) or more.
C - Combustible floor (but not carpet or non-ceramic tile).
All models approved for closet installation.
Plenum
1/2" (13mm)
on all sides
0"
0"
0"
0"
H12.11.2
UPFLOW DOWNFLOW
HORIZONTAL
TOP
0
0
0
PLENUM TOP
1/2" (13mm)
0
1/2" (13mm)
FRONT
0*
0*
0*
BACK
0
0
0
SIDES
0
0
0**
BOTTOM
0***
0
0
FLUE PIPE
0
0
0
ENCLOSURE
CLOSET
CLOSET
CLOSET
*24" (610mm) REQUIRED FOR SERVICE
**SUPPLY AIR OUTLET / 1/2"
(13mm)
RETURN AIR INLET
*** CERTIFIED FOR CLOSET INSTALATION ON COMBUSTIBLE FLOORING.
H3.6
WARNING
!
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE
INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN
18” (457 mm) ABOVE THE FLOOR TO PREVENT THE RISK OF IGNITING FLAMMABLE
VAPORS WHICH MAY BE PRESENT IN THE GARAGE.
THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY
VEHICLES.
FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING
IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
TABLE A - FURNACE DIMENSIONS
INPUT
OUTPUT
HIGH
Width
Depth
Height
Supply Air
Return Air
K/Btu/hr K/Btu/hr
A
B
C
(F x G)
(D x E)
45
43
17 1/2”
(445mm)
29 1/2”
(749mm)
32 7/8”
(835mm)
16 1/4” x 19 5/8”
(413mm x 499mm)
14” x 23”
(356mm x 584mm)
60
57
80
76
100
95
22 1/2”
(572mm)
21 1/4” x 19 5/8”
(540mm x 499mm)
120
114
H12.6.3
TABLE B - MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
Summary of Contents for 9500 series
Page 25: ...W415 0973 B 08 28 13 25 IOM FIGURE 14A DIRECT VENT TERMINAL CLEARANCES...
Page 26: ...W415 0973 B 08 28 13 26 IOM IOM FIGURE 14B NON DIRECT VENT TERMINAL CLEARANCES...
Page 55: ...W415 0973 B 08 28 13 55 IOM 23 0 SERVICE HISTORY 43 1...
Page 56: ...W415 0973 B 08 28 13 56 IOM IOM 44 1 24 0 NOTES...