NAPCO StarLink Connect Series Getting Started Download Page 13

NAPCO StarLink Fire:  Getting Started Guide 

13

 

The following summarizes the minimum required NOC programming (

h

Ʃ

p://NapcoNOC.com

) and system wiring when connec

Ɵ

ng a StarLink Fire Communica-

tor to the DACT of an FACP, u

Ɵ

lizing dial capture mode repor

Ɵ

ng.  Check the installa

Ɵ

on and programming instruc

Ɵ

ons for addi

Ɵ

onal wiring and programming 

op

Ɵ

ons.  Be sure all items in the following checklist are performed:   

 

1.

 

Central Sta

Ɵ

on Receiver Telephone numbers are programmed in the "

Dealer

 

Entered

 

Programming

" sec

Ɵ

on (see image at right):   

 

2.

 

UL

 

Poll

 

Fail

 

Timeout

 is set (200 seconds NFPA 2007 service plan; 5 min. for 

NFPA 2010 plan; 60 min. for NFPA 2013 plan or 24hr backup only): 

 

3.

 

(

PGM1

) is wired to a trouble zone in the FACP.  Wire the control panel Listed 

EOLR in series (terminal 3 PGM Output #1 and ground terminal #8) to a zone or 
point programmed to monitor communicator troubles.  

 

 
 

 

Installation Quick Start / Checklist for Fire Alarm Control Panel DACT Connect Operation 

WI2162A  04/16 

 

15 

14 

13 

12 

11 

9  10 

4  5 

17 

16 

StarLink Terminals

 

(STARLINK HOUSING) 

All connections are power limited except AC Mains, 

Telco and battery terminals.   

Terminals 14-17:  No connections permitted.   

RED 

GREEN 

9LE10KHARN installed in FACP: 

Blue/Red normally closed relay open on trouble 

Red/Black normally open relay short on alarm  

To FACP Ground /

Common Terminal  

(not earth ground) 

To panel Telco if using 

DACT reporting 

+V 

(12/24V) 

(

) PGM1 

PGM2 

PGM3 IN1  IN2 GND IN3 

RING 

TIP 

RTS 

(R) 

PANEL  

TX (B) 

PANEL  

RX (G) 

CTS 

PANEL  

RING (+) 

PANEL  

TIP (–) 

(Use FACP Listed 
EOLR) 

To FACP conventional 

zone positive terminal 

programmed for 

communicator trouble 

See 
Note 3 

If using addressable input for 

communicator supervision, 

connect Form C relay as 

shown below. 

– 

EOLR 

EOLR 

C 

N/C 

N/O 

See 

Note 4 

Note:  All wiring diagrams and programming depicted in this guide assume the wiring between the radio and the FACP is protected by conduit. 

Notes:

 

1. For NAPCO control panel downloading or 

remote

 

upgrading

 

of

 

radio

 

fi

rmware

, radio jumper 

X5_J1

 must be removed.   

2. Upon ac

Ɵ

va

Ɵ

on of the 

fi

re trouble relay (open between blue and red harness wires), a 

fi

re trouble signal will be transmi

Ʃ

ed to the central sta

Ɵ

on.   

3. For StarLink models SLECDMA-CFB-PS and SLE3/4G-CFB-PS, connect to charger board terminal labeled 

N/O

.   

4. If using external relay for radio supervision, relay must be rated for radio input voltage, (12VDC, max current draw=50mA OR 24VDC, max current 

draw=25mA).  A listed low current relay, such as 

Space Age Electronics 

model SSU-MR-311/C/R is recommended. 

Summary of Contents for StarLink Connect Series

Page 1: ...ng for Dial Capture DACT Installations Quick Start NOC Configuration and Communicator Wiring for a Panel Relay Triggered Installation AHJ Testing of Communicator Take the guesswork out of testing the...

Page 2: ...2 NAPCO StarLink Fire Getting Started Guide...

Page 3: ...rLink Fire Dual Path models have an I in the part number indicating Internet The requirement for Dual Path is typicality determined by the municipality or the local AHJ Note that you may purchase and...

Page 4: ...4 NAPCO StarLink Fire Getting Started Guide...

Page 5: ...NAPCO StarLink Fire Getting Started Guide 5...

Page 6: ...6 NAPCO StarLink Fire Getting Started Guide...

Page 7: ...NAPCO StarLink Fire Getting Started Guide 7...

Page 8: ...8 NAPCO StarLink Fire Getting Started Guide...

Page 9: ...Type the Device ID Radio ID into the Unit ID field for the respective device Service Plan then click Go NAPCO Remote Services ComNet Activation Guide WI2113BLF 3 18 333 Bayview Avenue Amityville New...

Page 10: ...Guide 4 Click the Click for Details text to review the details of the service plan 5 Click Add to add the service plan to the shopping cart 6 Click New for a new subscriber or Existing to add the devi...

Page 11: ...iew the subscriber information then click Add to Cart 9 Click Close if you do not want additional features 10 In the Shopping Cart see below click Process Order to complete the activation process John...

Page 12: ...12 NAPCO StarLink Fire Getting Started Guide...

Page 13: ...connections permitted RED GREEN 9LE10KHARN installed in FACP Blue Red normally closed relay open on trouble Red Black normally open relay short on alarm To FACP Ground Common Terminal not earth groun...

Page 14: ...of radio firmware radio jumper X5_J1 must be removed 2 Note Upon ac va on of the fire alarm relay short on black and red harness wires an alarm signal will be transmi ed to the central sta on Upon ac...

Page 15: ...EDs display as follows AC Failure Test Remove radio AC power and observe the following SLEULPS R power supply indications Restore radio AC power No Battery Low Battery Test Disconnect the radio batter...

Page 16: ...perly even with the antenna removed LED Verify this Condition Passed Red Trouble LED D5 Blinks 5 times Yellow Trouble LED on SLE ULPS R Blinks 4 times Trouble Relay Output on SLE ULPS R Activates with...

Page 17: ...EDs display as follows AC Failure Test Remove radio AC power and observe the following SLEULPS R power supply indications Restore radio AC power No Battery Low Battery Test Disconnect the radio batter...

Page 18: ...erly even with the antenna removed LED Verify this Condition Passed Red Trouble LED D5 Blinks 5 times Yellow Trouble LED on SLE ULPS R Blinks 4 times Trouble Relay Output on SLE ULPS R Activates withi...

Page 19: ...dio in standby mode ensure the LEDs display as follows AC Failure Test No Battery Low Battery Test The SLE CDMA FIRE and SLECDMA CFB models are powered directly from the FACP power supply radio AC Fai...

Page 20: ...possibility that the radio may operate properly even with the antenna removed Red Trouble LED D5 Turns off Yellow Trouble LED on SLE ULPS R Turns off Trouble Relay Output on SLE ULPS R Restores check...

Page 21: ...SLECDMA CFB in standby mode ensure the LEDs display as follows AC Failure Test No Battery Low Battery Test The SLE CDMA FIRE and SLECDMA CFB models are powered directly from the FACP power supply rad...

Page 22: ...possibility that the radio may operate properly even with the antenna removed Red Trouble LED D5 Turns off Yellow Trouble LED on SLE ULPS R Turns off Trouble Relay Output on SLE ULPS R Restores check...

Page 23: ...tions With the SLECDMAI CFB PS or SLE3 4GI CFB PS in standby mode ensure the LEDs display as follows AC Failure Test Remove radio AC power and observe the following SLEULPS R power supply indications...

Page 24: ...cable and observe the following indications continued Yellow Trouble LED Turns off Trouble Relay Output Restores check for proper trouble restoral at FACP LED Verify this Condition Passed Red Trouble...

Page 25: ...DHCP Red Trouble LED DS16 Turns off Yellow Trouble LED DS15 Slow blink Trouble Relay Output on SLEULPS R Trouble LED Turns off Supervisory restore signal R356 will be received by the central station w...

Page 26: ...26 NAPCO StarLink Fire Getting Started Guide...

Page 27: ...tions With the SLECDMAI CFB PS or SLE3 4GI CFB PS in standby mode ensure the LEDs display as follows AC Failure Test Remove radio AC power and observe the following SLEULPS R power supply indications...

Page 28: ...cable and observe the following indications continued Yellow Trouble LED Turns off Trouble Relay Output Restores check for proper trouble restoral at FACP LED Verify this Condition Passed Red Trouble...

Page 29: ...DHCP Red Trouble LED DS16 Turns off Yellow Trouble LED DS15 Slow blink Trouble Relay Output on SLEULPS R Trouble LED Turns off Supervisory restore signal R356 will be received by the central station w...

Page 30: ...30 NAPCO StarLink Fire Getting Started Guide...

Page 31: ...Failure tests are not required Signal Loss Test This test ensures that the SLE CDMAI FIRE SLE GSMI FIRE or SLECDMAI CFB SLE3 4GI CFB will indicate a supervisory trouble condition to the FACP and centr...

Page 32: ...uble restoral at FACP Supervisory restore signal R788 zone 1 will be received by the cen tral station within 24 hours of the antenna being reconnected LED Verify this Condition Passed Red Trouble LED...

Page 33: ...by the central station within 24 hours of the Ethernet cable and antenna being reconnected Green IP Network LED DS14 1 Blink Static IP or 2 Blinks DHCP Red Trouble LED D5 Turns off LED Verify this Co...

Page 34: ...34 NAPCO StarLink Fire Getting Started Guide...

Page 35: ...D Indications With the unit in standby mode ensure the LEDs display as follows AC Failure Test No Battery Low Battery Test The SLE CDMAI FIRE SLE GSMI FIRE and SLECDMAI CFB SLE3 4GI CFB models are pow...

Page 36: ...rouble restoral at FACP Supervisory restore signal R788 zone 1 will be received by the cen tral station within 6 hours of the antenna being reconnected LED Verify this Condition Passed Red Trouble LED...

Page 37: ...ed by the central station within 6 hours of the Ethernet cable and antenna being reconnected Green IP Network LED DS14 1 Blink Static IP or 2 Blinks DHCP Red Trouble LED D5 Turns off LED Verify this C...

Page 38: ...38 NAPCO StarLink Fire Getting Started Guide...

Page 39: ...94MHz and 1850 1990MHz bands and are designed to minimize loss and maximize gain The antenna is foam filled for vibration stabilization and long lasting performance in extreme conditions A UV stable p...

Page 40: ...40 NAPCO StarLink Fire Getting Started Guide...

Reviews: