WI1370 XP-400 Installation Instructions  

Site

 

At the site perform the following three steps: 

1. Arm the panel. 
2. Disarm the panel. 
3. Enter 

A6

.  The panel will now call 

the download computer running 
PCPreset.  PCPreset will answer the 
call, establish a connection, and then 
download the account that matches the 

Auto Download ID Number

 [93] with the 

account of the same number in the list 
that PCPreset is currently running.  

 
Dealer Programming 

 

[94]Dealer Code 

The default Dealer Code is 

4567

.  Program 

a new 4-digit Dealer Code.  When the panel 
is defaulted the Dealer Code will be 
changed back to the default  Dealer Code of 

4567

 only if 

Dealer Code Lockout

 [96-1] 

has not been programmed. 
 

[95]User 1 Code 

The 1st User code is a program code as 
well as an Arm/Disarm code.  The default 
User Code is 

1234

.  If User 1 Code Lockout 

is programmed the User 1 Code cannot be 
programmed from User Program Mode. 

 

[96]Dealer Options 1 

(1) Dealer Code Lockout

 - Program to 

prevent the Dealer Code from changing with 
a panel default. 

(2) User 1 Code Lockout

 - If programmed 

the User 1 Code cannot be programmed 
from User Program Mode. 

(3) Reserved 

 

(4) Reserved

 

 
[97]Dealer Options 2 

 
(1) International Dialing Protocol 

- No 

dialing if no dial tone, 60 seconds between 
attempts and 4 s wait for dial tone. 

(2) Invert Bell Output

 - Inverts the Bell 

polarity and removes supervision from the 
bell circuit. 

(3) System Trouble Auto Restore

 - 

Normally, System troubles require 
acknowledgment (View System Trouble) in 
order to restore.  If this option is selected 
troubles will restore without requiring 
acknowledgment. 

(4) User 1 Code-Program only  

- If enabled 

User 1 Code will function only as the User 
Program Code and will not Arm/Disarm the 
panel. 
 
Note:  All programming within Programming 
Blocks [96] & [97] will not change if the 
panel is defaulted. 

 
[98] Number of Re-Dials 

The Number of re-dial attempts made by the 
panel before indicating a Fail-to-
Communicate.  

 

 

Summary of Contents for RPXP4GT

Page 1: ...XP 400 RPXP4GT keypad Control Panel Communicator Installation Instructions WI1370 1 05 NAPCO 2005...

Page 2: ...Cut Detection Answering Machine Override Second Call Communicator 2 Telephone Numbers Backup Reporting Pager Format Point ID Format Individually Report 4 Users Opening after Alarm Report Cancel Code C...

Page 3: ...12V 4 AH Rechargeable Change Battery every 5 years or as required Maximum Charging Current 165 mA Maximum Input Current 2 58 A Loop Characteristics Loop Voltage 5 Volts Loop Current Zones 1 2 0 9 mA...

Page 4: ...ification HARMONIZED STANDARDS EN50081 1 and EN50082 1 EC DIRECTIVES 89 336 EEC Electromagnetic Compatibility Directive Optional Accessories Wireless Receiver Window Door Transmitter Key Fob Transmitt...

Page 5: ...ng PCPreset For Site Initiated Downloaded see Auto Download ID Number 93 Local Downloading Wire as shown in Figure 1 Use the power up or A6 method of establishing a connection The power up method is r...

Page 6: ...as shown in the wiring diagram in the back of this manual WARNING The FCC restricts the use of this equipment on certain telephone lines Read the FCC statement on the back of this manual to ensure co...

Page 7: ...ode when the Bell or PGM is ON Bell and PGM will turn OFF Keypad LEDs W ARMED LED DEFINITION Armed ON Instant Mode Rapid Flash Zone in Alarm Flashing X READY LED DEFINITION Ready to be Armed ON Zone f...

Page 8: ...entering the premises through an Exit Entry Zone the keypad will sound the Entry Delay Tone Enter a valid Arm Disarm code If a valid Arm Disarm code is entered the keypad will beep 6 times indicating...

Page 9: ...sing a zone Disarmed only Press the C key then the number of the zone to be unbypassed Group Bypass Press C C to Bypass all Exit Entry Follower Zones 02 or Home Away Zones 01 only if the system is pro...

Page 10: ...command to bypass all Exit Entry Follower Zones or Home Away Zones only if the system is programmed exclusively for Home Away with Delay zones A4 Instant Enter this command before or after arming to...

Page 11: ...eypad will sound a short beep for transmitters with signal strengths of 3 or less Zone Features 00 Exit Entry Zones Delay allows exit and entry through an Exit Entry Zone after the system is armed wit...

Page 12: ...s restored while the control panel is still armed the zone will automatically be unbypassed and any subsequent violations of the zone will cause an alarm condition 04 24 Hour Protection A zone that pr...

Page 13: ...am the interval in days between Test Timer reports Test Timer Interval may be programmed from 1 to 255 days 15 Line Cut Time to Fail Enable this feature by programming the delay time required to decla...

Page 14: ...winger Shutdown Automatically disables armed zones with excessive alarm restores swingers Non 24 Hour Protection zones allows only 3 alarms and 2 restores per zone per arming before the zone is disabl...

Page 15: ...ion is not permitted for UL installations Telephone Number 1 Programming 30 Subscriber ID Number For 4 2 format enter a 4 digit number If 3 1 format is required enter a 3 digit number then press the i...

Page 16: ...ager Format Selected Pager PIN Number Program if a PIN number is required by the paging system The digits in Telephone Number 2 will be added on to telephone number 1 and or telephone number 3 allowin...

Page 17: ...ne detection can be disabled by programming No Dial Tone Detection 46 1 To program any additional delay enter a D where required in the phone number 42 Receiver Format Telco 2 Select the format that w...

Page 18: ...tore code is the zone number of the restored zone For example if the Zone Restore Code 62 is programmed to E the restore code for that zone would be E4 4 2 format 62 2 Trouble Code Conditional Closing...

Page 19: ...al Closing Telco 3 see 67 1 3 Reserved 4 Reserved Wireless Up to two receivers can be wired to the XP 400 Each wireless transmitter can be mapped to a zone Only 1 wireless device is permitted per zone...

Page 20: ...c alarm when the M or N buttons on the Keyfob are pressed Additional programming required Keypad Panic GG 20 3 Panic Report to Telco 1 36 2 and or Telco 3 56 3 Audible Panic Optional 21 1 2 AUX Progra...

Page 21: ...t 91 2 Answering Machine Override Using the downloading computer call the panel When the operator has determined that the panel has received 1 2 rings pressing the u key will cause the downloading com...

Page 22: ...nnot be programmed from User Program Mode 96 Dealer Options 1 1 Dealer Code Lockout Program to prevent the Dealer Code from changing with a panel default 2 User 1 Code Lockout If programmed the User 1...

Page 23: ...will beep once every 10 seconds The keypad will continue to beep until the reset button is pressed or the trouble has been acknowledged by pressing the i key System Trouble Reporting The following sys...

Page 24: ...EOL2 2K resistor must be installed 3 Rcvr Fail to Respond Rcvr Tamper The receiver is not responding to the panel The red LED on the receiver should be flashing refer to WI848 The cover is off the rec...

Page 25: ...t loop current flowing through the Bell circuit for supervision To eliminate this cut resistor R26 which is located directly above Terminal 9 just below the heat sink 5 Where are the fuses The control...

Page 26: ...1 and point 2 is jumped out If using internal reed make sure J1 is cut and both Point 1 and Point 2 terminals are jumped out 10 Keypad LEDs Flicker The Keypad is not receiving a POLL from the Panel Ch...

Page 27: ...esistors AUX POWER OUTPUT 10 12 5 VDC XP 400 WIRING DIAGRAM REFER TO INSTALLATION INSTRUCTIONS WI1371 RESIDENTIAL BURG 4 HOUR STANDBY COMBINED STANDBY 350 mA BELL 2 0 AMP 1 Z NOT USED Normally Open Zo...

Page 28: ...sting and due to but not limited to any or all of the following criminal tampering electrical or communications disruption it is possible for the system to fail to perform as expected NAPCO does not r...

Reviews: