DESCRIPTION 

charger 

and a 

supervised power-limited supply

, the 

NP-P3ASUP converts low voltage AC input into a 
12VDC or 24VDC power limited output, with 3A of con-
tinuous supply current.

 

 

FEATURES 

Maximum charge current .5 amps. 

12VDC or 24VDC selectable output. 

3 amps continuous supply current at 12VDC-24VDC. 

Filtered and electronically regulated outputs. 

Built-in charger for sealed lead acid or gel type batter-
ies. 

Automatic switch over to stand-by battery when AC 
fails (zero voltage drop). 

AC input and DC output LED indicators. 

AC fail supervision (form "C" contacts). 

Low battery supervision (form "C" contacts). 

Short circuit and thermal overload protection. 

Includes battery leads. 

Board Dimensions:  179.3mm(L) x 108.7mm(W) x45mm(H) 

Specified at 25° C ambient. 

INSTALLATION INSTRUCTIONS 

The NP-P3ASUP should be installed in accordance with 
The National Electrical Code and all applicable Local 
Regulations. 
1.    Mount the NP-P3ASUP in desired location. 
2.    Set the NP-P3ASUP to desired DC output voltage 

via SW1 (see Voltage Output/Transformer Selection 
Table). 

3. 

   Connect proper transformer to terminals marked 

[AC] (see Voltage Output/Transformer Selection Ta-
ble). 

      Use 18 AWG or larger for all power connections 

(Battery, DC output). 

      Use 22 AWG to 18 AWG for power limited circuits 

(AC Fail/Low Battery reporting). 

4.    Connect devices to be powered to terminals marked 

[+ DC -]. 

       Note: 

It is important to measure output voltage be-

fore connecting devices.  This helps avoid potential 
damage. 

5.    When the use of stand-by batteries are desired, they 

must be lead acid or gel type. 

       Connect battery to terminals marked [+ BAT -] on the 

board (battery leads included). 

       Use two (2) 12VDC batteries connected in series for 

24VDC operation. 

       Note:   

When batteries are not used a loss of AC will 

result in the loss of output voltage. 

6.    Connect appropriate signaling notification devices to 

AC Fail & Low battery supervisory relay outputs 
marked [N.C., C, N.O.]. 

R

333 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 

NP-P3ASUP 

3 AMP SUPERVISED  

POWER SUPPLY/ CHARGER 

WI1339A  12/05 

© NAPCO 2005 

Red  

(DC) 

Green 

(AC) 

Power Supply Status 

ON 

ON 

Normal operating condition. 

ON 

OFF  Loss of AC, Stand-by battery supplying power. 

OFF 

ON 

No DC output.  Short circuit or thermal overload condition. 

OFF 

OFF  No DC output.  Loss of AC.  Discharged or no battery. 

LED DIAGNOSTICS

 

VOLTAGE OUTPUT/TRANSFORMER SELECTION TABLE 

Output  

VDC 

Switch  

Position 

Max.  

Load DC 

Transformer Requirements 

12VDC 

SW1-1  

OFF 

3 amps 

24VAC / 100VA 

24VDC 

SW1-1  

ON 

3 amps 

28VAC / 175VA-  

TERMINAL IDENTIFICATION 

Terminal 

Legend 

Function/Description 

AC/AC 

Low voltage AC input (see voltage output/transformer selection table). 
For 12VDC output use 24VAC or higher with 100 VA power rating or 
higher. 
For 24VDC output use 28VAC with 175VA power rating or higher. 
Caution: Do not apply voltages above 28VAC (28 VAC is maximum 
input rating) 

+ DC - 

12VDC/24VDC @ 3 amps continuous power limited output. 

AC FAIL 
N.C., C, N.O. 
 

Used to notify loss of AC power, e.g. connect to audible device or alarm 
NC, C, NO panel. Relay normally energized when AC power is present. 
Contact rating 1 amp @ 120VAC / 28VDC 

Low Battery 
N.C., C, N.O. 

Used to indicate low battery condition, e.g. connect to alarm panel. 
NC, NO, C Relay normally energized when DC power is present. 
Contact rating 1 amp @ 120VAC / 28VDC. 
Low battery threshold: 
12VDC output threshold set @ approximately 10.5VDC, 
24VDC output threshold set @ approximately 21VDC. 

+ BAT - 

Stand-by battery connections. Maximum charge rate .5 amp. 

 