NAPCO MAGNUM ALERT 1008e Installation Instructions Manual Download Page 25

MA1008e

 

/

 

1008eM 

Installation Instructions 

L

 NAPCO Security Systems  

 

Page 25

 

Select User(s) Opening  

See 

Opening Report

 

 

Selective Bypass 

(Locations 

194,195

Removal of one particular zone from the system.  Any or 

all Zones 1-7 programmed for Selective Bypass may be re-
moved from the system, but each must be removed sepa-
rately. 

Selectively bypass a zone by pressing Bypass Key [B] 

followed by the zone number.  The next time the panel is 
disarmed, all bypassed zones will automatically revert to 
non-bypassed zones. 

When one or more zones is bypassed, the yellow BY-

PASS LED on the keypad will light.  The zones bypassed 
may be confirmed by holding down Key [2] (

Display By-

pass

) until the function beep sounds; with the key de-

pressed, the bypassed zones will be displayed. 

 

Sensor Watch

™  See 

P/R Zone

Time Selection 

 

 

Service Code  

See 

User 5 Service Code 

 

 

Single-Digit Format  

See 

Data Format

 

 

Smoke Detectors 

(Terminals 11 & 12) 

Connect smoke detectors as shown on the Wring Dia-

gram.  Note that Terminals 11 and 12 may be used for the 
Fire Zone only.  Up to 10 compatible two-wire smoke detec-
tors may be "daisy-chained" together.  Subtract smoke-
detector alarm current from auxiliary standby current.  See 

COMPATIBLE UL-LISTED DEVICES

Note:

  If they are of the self-resetting type, power 4-wire 

smokes from the Constant Auxiliary Voltage Output at Ter-
minal 5 instead of Terminal 11. 

 

Sounder Output on Lug E4 

(Location 

180

When an "8" is programmed in Location 

180

, Lug E4 will 

go low whenever the keypad sounder is activated.  This fea-
ture disables Lug E4 for use as an Arm Lug (see 

Arm Lug

). 

 

Split Reporting 

(Location 

179

Split Reporting causes all reports except Openings, 

Closings, and Test Timer to be sent to Telephone No. 1, 
while Openings, Closings, and Test Timer report to Tele-
phone No. 2.  (

Split Reporting 

overrides 

Backup Reporting 

or 

Double Reporting 

if either combination is programmed).  

Enter Subscriber ID's (Locations 

132-143

) and other infor-

mation (Locations 

144-163

) required for Telephone 2.  Note 

that Subscriber ID Numbers for Telephones 1 and 2 must 
be entered, even if they are the same. 

 

Status Report  

See 

Closing Report

 

 

Subscriber Identification Numbers 

(Locations 

100-111

132-143

Different 

Subscriber Identification Numbers 

(account 

numbers) may be used by the central station to distinguish 
Alarm and Restore Reports (Locations 

100-107

) from 

Opening and Closing Reports (Locations 

108-111

).  Simi-

larly, different numbers may be used to distinguish Alarm/
Restore Reports for Group-1 Zones (Zones 1-7) from Group 
Zones (Fire to Low Battery).  Both groups must be pro-
grammed, even if both use the same number.  See 

Report 

on Alarm; Restore Report; Opening Report; Closing Report.

 

Furthermore, if a second telephone is used, different 

Subscriber Identification Numbers may be required for 
Alarm/Restore Reports (Locations 

132-139

) and Opening/

Closing Reports (Locations 

140-143

).  As above; both 

groups must be programmed, even if both use the same 
number.  See 

Double Reporting; Backup Reporting

Note: 

1. If the central station cannot accept two-digit or ex-

tended event codes, the Alarm and Restore Codes 
may be the same as the Opening and Closing Codes; 
or, the Alarm/Restore Codes may be the same for 
Groups 1 and 2 if the respective Subscriber Identifica-
tion Numbers are different. 

2. Starting at the left-most location, enter at least 3 digits 

for each Subscriber Identification Number, even if the 
first two are zeros.  A fourth digit is available for those 
receivers capable of recognizing 4-digit subscriber 
codes. 

 

Sum Check  

See 

Data Format

 

 

Swinger Shutdown 

(Locations 

084-085

When programmed, Zones 1 through 7 with 

Auto-Reset 

will only reset twice (3 alarms) until rearmed in order to pre-
vent "swingers" (intermittents) from causing repeated false 
alarms.  (Do not program for UL installations).  See 

Auto-

Reset

 

Telephone Numbers 

(Locations 

117-131; 149-163

To report to a central station, Telephone Number 1 

(Locations 

117-131

) must be programmed.  Telephone 

Number 2 (Locations 

149-163

) is programmed if 

Backup 

Reporting, Split Reporting 

or 

Double Reporting 

is selected. 

 

Telephone Number 1 will be preceded by at least one 

Dial-Tone Detection 

entry ("E" in Location 116) or 

Pre-Dial 

Delay 

entry ("D" in Location 

114

) to ensure that the commu-

nicator detects a dial tone or waits a reasonable time to ac-
cess a telephone line before dialing.  (See 

Dial Tone Detec-

tion; Pre-Dial Delay

.) Furthermore, private telephone sys-

tems may require a separate Dial Tone Detection or Pre-
Dial Delay digit, followed by an Access Number (Location 

115

) to obtain an outside line.  (See 

Access Number for 

Outside Line

). 

It should be noted here that Telephone Number 1 need 

not actually start in Location 

117 

nor end in Location 

131

as extra locations have been provided to allow for additional 
prefix digits, if required.  What is important is that Telephone 
Number 1, with its associated 

Pre-Dial Delay, Access Num-

ber

, and 

Dial-Tone Detection

, be wholly contained within 

Locations 

114-131

, and that they be in their proper se-

quence.  It may, in fact, be advantageous to leave one or 
two blank locations before entering the telephone number to 
allow for the unexpected (an additional Pre-Dial Delay, for 
example).  The above applies to 

Telephone Number 2 

(Locations 

149-163

) and the 

Callback Telephone Number 

(Locations 

270-285

; PROM Page-1 Locations 

014-029

) as 

well. 

Note:

  An "F" in any location will be ignored by the com-

municator when dialing. 

 

Test Timer 

(Locations 

024, 025;169

)  

Reset Test Timer on Report 

(Location 

181

When a "1 " is programmed into Location 169, a daily 

test report will be transmitted to the central station from the 
time the panel is powered up.  The respective Alarm Code 
is programmed into Locations 024, 025. 

Summary of Contents for MAGNUM ALERT 1008e

Page 1: ...e M CONTROL PANEL COMMUNICATOR WI587E 8 07 NAPCO 2007 R UL cUL Listed MA1008e Household Fire Burglary Warning System Control Unit MA1008eM Commercial Burglar Alarm System Control Unit See page 10 for...

Page 2: ...ATIONS 4 ORDERING INFORMATION 4 UL CUL LISTINGS 4 COMPATIBLE UL LISTED DEVICES 4 SUMMARY OF UL REQUIREMENTS 5 2 INSTALLATION 6 CONTROL PANEL MOUNTING 6 KEYPAD MOUNTING 6 WIRING TO A MERCANTILE BELL 7...

Page 3: ...Find mode Bypass Priority with Bypass and Power Up Delay Key B Alarm History indicates last alarmed zone s The panels may be programmed in a variety of ways a from the keypad in its secondary Dealer P...

Page 4: ...atings 24VDC 2A resistive Auxiliary Output Commercial 12VDC regulated Residen tial 10 6 12 5VDC Combined Standby Current Remote Power Aux Output Relay Output 450mA maximum with standard TRF12 500mA ma...

Page 5: ...if using 4 wire smoke detectors Minimum alarm timeout of 4 minutes Maximum exit time 60 seconds maximum entry time 45 seconds Do not program Don t Wait for Handshake Telco 1 2 Swinger Shutdown Force A...

Page 6: ...liding La bel Plate with label and felt backing affixed and handle facing forward down the guides at the rear of the keypad until it snaps into place Once installed the Sliding Label Plate can not be...

Page 7: ...re than one floor additional smoke detectors should be installed on each level including the basement The living area and basement smoke detectors should be installed near the stairway of the next upp...

Page 8: ...enabled Alarm Trouble Codes Zones 1 7 31 37 Panic 21 Fire 11 Ambush 22 Fire Trouble F1 No AC F9 Low Battery F8 Restore Codes Zones 1 7 E1 E7 Fire E1 Fire Trouble EF No AC E9 Low Battery E8 Closing Cod...

Page 9: ...to a central station activate an audible alarm or both Note that the key pairs must be pressed at the same time to activate panic See Panic Zone In the Glossary also see Section 2 Keypad Jumper Optio...

Page 10: ...then try again to auto download the program TESTING THE SYSTEM After installation is completed test the system a follows Call the central station to inform them of the test Initiate an alarm preferabl...

Page 11: ...the Dealer Program Code within 10 seconds to exit Key B Set Sets the location to be programmed After pressing Key B enter a three digit location number To exit the Dealer Program Mode hold down Key 8...

Page 12: ...e respective locations The display will show the entry numerically but will display 0 for the number 10 and letters B C D E and F for the numbers 11 through 15 respectively To program a 10 enter 0 To...

Page 13: ...com puter operator should be familiar with the operation When a high pitched tone is heard at the site phone arm the panel disarm then access Hold Down Function 6 Manual Download within 5 seconds the...

Page 14: ...S ALARM RESTORE ID SEE NOTE 3 OPENING CLOSING ID GROUP 1 GROUP 2 SEE NOTE 4 TELEPHONE 1 100 101 102 103 104 105 106 107 108 109 110 111 TELEPHONE 2 132 133 134 135 136 137 138 139 140 141 142 143 FORM...

Page 15: ...T ENTRY FOLLOWER 206 207 1 2 4 8 1 2 4 8 SEE NOTE 7 ABORT DELAY 208 209 ALSO SEE TIMES TIMEOUTS LOC 232 233 1 2 4 8 1 2 4 8 BURGLARY OUTPUT 210 211 ALSO SEE TIMES TIMEOUTS LOC 224 225 228 229 1 2 4 8...

Page 16: ...TATUS 4 USER 5 REPORT AS USER 1 8 DOUBLE REPORTING 8 KEY INPUT ON ZONE 7 8 LOCATION 079 ENTRY LOCATION 179 ENTRY LOCATION 304 ENTRY USER 5 SERVICE CODE 1 OPENING REPORT AFTER ALARM 1 DON T WAIT FOR HA...

Page 17: ...Alarm Codes See Report on Alarm Alarm History Hold Down Key B will display on the digital readout all alarm conditions that have occurred While holding down Key B note the number s displayed indicati...

Page 18: ...a the cause of the alarm has been removed and b the panel is dis armed Also see Swinger Shutdown Backup Reporting Location 178 When Backup Reporting is selected and the communicator does not reach the...

Page 19: ...es the communicator will transmit 678C Subscriber 678 has closed CCC3 Closing User 3 Extended Format may be used with most central station receivers Most receivers capable of recognizing multiple repo...

Page 20: ...h Code Disable Bell Test Location 182 Program an 8 in Location 182 to prevent unauthorized persons from sounding the bell Disable Callback Method Download Location 080 Data may be remotely downloaded...

Page 21: ...not pro grammed exit time will be 60 seconds entry delay will be 30 seconds In UL installations exit time may not exceed 60 seconds entry time may not exceed 45 seconds Entry delay may be cancelled b...

Page 22: ...If the installation requires one connect a Listen In module to Lug E5 The 12V at Lug E5 will drop to zero when the com municator goes off hook The voltage will return when the transmission is complete...

Page 23: ...oca tions 094 095 are left blank PIR Zones will still be delayed on power up but they will not be monitored for activity If this feature is selected and any other zones are pro grammed as Day Zones a...

Page 24: ...rminals 11 and 12 for two wire devices or Terminals 11 and 13 for four wire devices see Wiring Diagram Holding down Reset Key 9 until the sounder beeps will momentarily remove power from Terminal 11 R...

Page 25: ...tification Numbers may be required for Alarm Restore Reports Locations 132 139 and Opening Closing Reports Locations 140 143 As above both groups must be programmed even if both use the same number Se...

Page 26: ...s of the 1st Box to 16 times the contents of the 2nd Box Remember that a zero entry represents 10 Example 1 Program Entry Delay 1 for 1 minutes 1 Entry Delay 1 Locations 220 221 is in units of sec ond...

Page 27: ...Lug is programmed 2 in Location 078 Lug E15 will go low after 9 unsuccessful transmissions and remain low until either a transmission or a Telco Test is successful If Keypad Aux Alarm on NTO Lug is p...

Page 28: ...9 CHIME ON WITH GROUP BYPASS 18 22 CHIME ZONE 18 CLOSING REPORT 19 COMMUNICATOR FEATURES 4 14 COMMUNICATOR CONFIDENCE TEST 9 21 COMPATIBLE UL LISTED DEVICES 4 CONTROL PANEL MOUNTING 6 CONTROL PANEL R...

Page 29: ...N 9 KEYPAD PANIC 9 22 KEYPAD PROGRAMMING 11 KEYPAD PROGRAMMING 11 KEYPAD SOUNDER ON ALARM 21 KEYPAD TACTILE BEEP 21 KEYPAD WIRING 6 LINE REVERSAL MODULE 22 LISTEN IN LUG 22 LOCAL DOWNLOADING 13 LOOP R...

Page 30: ...OUNDER SIGNALS 4 SPECIFICATIONS 4 SPLIT REPORTING 25 STATUS REPORT 19 25 SUBSCRIBER IDENTIFICATION NUMBERS 25 SUM CHECK 25 SUM CHECK FORMAT 19 SUMMARY OF UL REQUIREMENTS 5 SWINGER SHUTDOWN 25 SYSTEM F...

Page 31: ...MA1008e 1008eM Installation Instructions L NAPCO Security Systems Page 31 6 WIRING DIAGRAM...

Page 32: ...sumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be liable...

Reviews: